TFP633

Page 3 of 8

MODEL CC3

SPRINKLER

6" (152 mm)

MINIMUM

60" (1524 mm)

MAXIMUM

1-1/2" (40 mm)

MINIMUM

4" (102 mm)

MAXIMUM

6" (152 mm)

MAXIMUM FOR

CPVC PIPE

FRAME ARMS OF

SPRINKLER MUST

BE INSTALLED

IN-LINE WITH

PIPE RUN

WHEN OFFSETTING CPVC PIPE OVER AN

OBSTRUCTION, A MODEL CC3 SPRINKLER

MUST BE INSTALLED DIRECTLY ON THE

CPVC PIPE OVER THE OBSTRUCTION

6" (152 mm) MAXIMUM ABOVE

CEILING TO BOTTOM OF PIPE OR

NON-COMBUSTIBLE CEILING INSULATION,

OR 1/3 THE DEPTH OF CONCEALED SPACE

(AS MEASURED FROM TOP SURFACE OF

CEILING TO BOTTOM OF DECK ABOVE),

WHICHEVER IS SMALLER

BOTTOM

OF PIPE

TOP CHORD

4" (102 mm)

OR LESS

CEILING

OBSTRUCTION

UPPER DECK

TOP OF CHORD

4-1/2" (114 mm) MINIMUM

FROM FACE OF WOOD TRUSS

OR TOP CHORD OF BAR JOIST

MODEL CC3

SPRINKLER

UPPER

DECK

NON-COMBUSTIBLE

INSULATION

6" (152 mm)

MINIMUM

60" (1524 mm)

MAXIMUM

1-1/2" (40 mm)

MINIMUM

4" (102 mm)

MAXIMUM

6" (152 mm)

MAXIMUM FOR

CPVC PIPE

COMPOSITE

WOOD JOISTS

SOLID WOOD

JOISTS

FRAME ARMS OF

SPRINKLER MUST

BE INSTALLED

IN-LINE WITH

PIPE RUN

WHEN OFFSETTING CPVC PIPE OVER AN

OBSTRUCTION, A MODEL CC3 SPRINKLER

MUST BE INSTALLED DIRECTLY ON THE

CPVC PIPE OVER THE OBSTRUCTION

6" (152 mm) MAXIMUM ABOVE

CEILING TO BOTTOM OF PIPE OR

NON-COMBUSTIBLE CEILING INSULATION,

OR 1/3 THE DEPTH OF CONCEALED SPACE

(AS MEASURED FROM TOP SURFACE

OF CEILING TO BOTTOM SURFACE

OF JOIST INSULATION ABOVE),

WHICHEVER IS SMALLER

BOTTOM

OF PIPE

TOP OF

CHORD

OBSTRUCTION

CEILING

72" (1829 mm)

MAXIMUM

FIGURE 3 

NON-COMBUSTIBLE INSULATION-FILLED UPPER DECK 

SOLID WOOD OR COMPOSITE WOOD JOIST CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

CPVC PIPE

FIGURE 2 

UNOBSTRUCTED WOOD TRUSS CONSTRUCTION 

OR UNOBSTRUCTED BAR JOIST CONSTRUCTION 

CROSS SECTION ELEVATION VIEW 

CPVC PIPE

Содержание tyco CC3

Страница 1: ...m from floor to ceiling 60 in 1524 mm maximum height for truss and bar joist The 4 2K and 5 6K sprinklers are UL Listed for use with LFP Antifreeze For information about antifreeze compatibility and a...

Страница 2: ...oncealed space is 60 in 1524 mm maximum to 6 in 152 mm minimum System Type CPVC Pipe Light hazard wet pipe system Maximum Distance Between Model CC3 Sprinklers CPVC Pipe TY2199 4 2K 14 ft 4 3 m TY3199...

Страница 3: ...ECK NON COMBUSTIBLE INSULATION 6 152 mm MINIMUM 60 1524 mm MAXIMUM 1 1 2 40 mm MINIMUM 4 102 mm MAXIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER M...

Страница 4: ...ches 150 mm or 1 3 the depth of the con cealed space whichever is greater and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a maximum of 1000 ft 93 m For informa...

Страница 5: ...AXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 84 2134 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 60 1524 mm MAXIMUM M...

Страница 6: ...E ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK MODEL CC3 SPRINKLER CEILING FRAMING 2x FLOOR SOLID WOOD JOISTS NON COMBUSTIBLE INSULATION COMPOSITE WOOD JOISTS 1 1 2 38 mm MINIM...

Страница 7: ...read sealant applied to the pipe threads use only the W Type 6 End A Sprinkler Wrench see Figure 9 for installation of the Model CC3 Sprin klers by applying the wrench to the sprinkler wrench flats on...

Страница 8: ...e completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Spri...

Отзывы: