background image

TFP633

Page 4 of 8

all other guidelines of the “BLAZEMAS-

TER — Installation Instructions & Tech-

nical Manual” must be met. When using 

1 in. (DN25) or larger pipe, a hanger 

must be located at the truss nearest a 

sprig for purposes of restraint. If using 

3/4 in. (DN19) piping, all sprigs over 

12 inches (305 mm) must be laterally 

braced using methods described in the 

NFPA standards.
Where the CPVC must be offset up 

and over an obstruction and the pipe 

exceeds the allowed horizontal posi-

tioning requirements specified above 

as well as shown in Figure 2 and 3, 

additional Model CC3 Sprinklers are 

to be installed as shown in Figures 2 

and 3 to protect the BLAZEMASTER 

CPVC product.
A minimum lateral distance of 18 in. 

(460 mm) must be maintained between 

the CPVC pipe and heat pumps, fan 

motors, and heat lamps.

Design Criteria, 

Steel Pipe

Area of Use (Steel Pipe)

Horizontal (slope not exceeding 2:12) 

combustible concealed spaces of:
•  Unobstructed wood truss construc-

tion or unobstructed bar joist con-

struction.  See Figure 4.

•  Solid wood joist construction (see 

Figure 5) where the upper deck and 

ceiling joists may have a maximum 

depth of 12 inches (300 mm) and 

typical on center joist spacing of 

minimum 16 inches (400 mm).

•  Non-combustible insulation-filled 

solid wood joist or wood composite 

joist construction. See Figure 6.

•  Obstructed wood truss construction. 

See Figure 7.

NOTE: In order to be considered “non-

combustible insulation-filled solid 

wood joist or composite wood joist 

construction”, the insulation (includ-

ing insulation provided with a combus-

tible vapor barrier), must completely fill 

the pockets between the joists to the 

bottom of the joists, and the insulation 

must be secured in place with metal 

wire netting. The metal wire netting is 

intended to hold the insulation in place 

should the insulation become wetted 

by the operation of the Model CC3 

Sprinklers in the event of a fire.

Concealed Space Area (Steel Pipe)

The area of the concealed space is not 

limited; however,
•  For unobstructed wood truss con-

struction or concealed spaces of 

non-combustible, unobstructed bar 

joist construction (see Figure 4) draft 

curtains or full height walls must be 

provided at 1000 ft² (93 m²) areas. 

In addition, the 5.6K sprinkler is UL 

Listed for a 2000 ft² (186 m²) draft 

curtain area for solid wood open 

truss construction on edge or on 

face.
This draft curtain shall be at least 1/3 

the depth of the concealed space or 

8 in. (200 mm), whichever is greater, 

and be constructed using a mate-

rial that will not allow heat to escape 

through or above the draft curtain.

•  For solid wood joist construction 

(see Figure 5) and obstructed wood 

truss construction (see Figure 7):
Blocking must be provided in each 

upper deck and ceiling joist channel 

at a maximum 32 ft (9,75 m) inter-

vals. This blocking shall be installed 

to the full depth of the joists and be 

installed so as to not allow heat to 

escape through or above the block-

ing. The blocking must be con-

structed using a non-combustible 

material or the joist construction 

material.
Draft curtains must protrude below 

the joist a minimum of 6 inches (150 

mm) or 1/3 the depth of the con-

cealed space, whichever is greater, 

and run parallel with the joist spaced 

at 31 ft (9,4 m) width maximum to 

limit the area to a maximum of 

1000 ft² (93 m²). For information 

about antifreeze compatibility and 

approved constructions, see the 

Technical Data section.
The draft curtains are to be con-

structed using a material that will 

not allow heat to escape through or 

above the draft curtain.

•  For non-combustible, insulation-filled 

solid wood joist or composite wood 

joist construction (see Figure 6), the 

requirement for draft curtains and 

blocking does not apply.

•  For information about antifreeze 

compatibility and approved con-

figurations, see the Technical Data 

section.

Concealed Space Size (Steel Pipe)

The minimum and maximum concealed 

space depth is as follows:
For unobstructed wood truss construc-

tion or concealed spaces of unob-

structed bar joist construction (see 

Figure 4) the maximum depth of the 

concealed space is 60 in. (1524 mm) 

from bottom of upper deck to top of 

ceiling, and the minimum depth is 6 in. 

(152 mm) from the bottom of the upper 

chords to the top of the lower chords.
For solid wood joist construction 

 

(see Figure 5) and solid wood or com-

posite wood joist construction the 

maximum depth of the concealed 

space is 84 in. (2134 mm) from bottom 

of upper deck to top of ceiling, and the 

minimum depth is 6 in. (152 mm) from 

the bottom of the upper deck joists to 

the top of the ceiling joists. If joist con-

struction is filled with non-combustible 

insulation the maximum height of the 

space is 84 in. (2134 mm). See Figure 6.
For obstructed wood truss construc-

tion (see Figure 7), the maximum 

depth of the concealed space is 

84 in. (2134 mm) from bottom of upper 

deck to top of ceiling, and the minimum 

depth is 6 in. (152 mm) from the bottom 

of the upper chord to the top of the 

lower chord.

System Type (Steel Pipe)

Light hazard, wet or dry pipe system

NOTES: Use of the 4.2K sprinklers in 

dry pipe systems is permitted by section 

8.3.4.4 of NFPA 13 (2013 edition) where 

piping is corrosion resistant or internally 

galvanized.

Maximum Distance Between Model 

CC3 Sprinklers (Steel Pipe)

TY2199 4.2K. . . . . . . . . . . . . .  14 ft (4,3 m)
TY3199 5.6K. . . . . . . . . . . . . .  16 ft (4,9 m)

Maximum Coverage Area (Steel 

Pipe)

TY2199 4.2K. . . . . . . . . . . 196 ft² (18,2 m²)
TY3199 5.6K. . . . . . . . . . . 256 ft² (23,8 m²)

Minimum Distance Between Model 

CC3 Sprinklers (Steel Pipe)

Minimum sprinkler spacing is 7 ft 

(2,1 m)

Deflector Position (Steel Pipe)

1-1/2 in. to 4 in. (40 mm to 100 mm) 

below upper deck for wood truss con-

struction or concealed spaces of non-

combustible bar joist construction. See 

Figure 4.
1-1/2 in. to 2 in. (40 to 50 mm) below 

solid wood joist (see Figure 5) or top 

chord of a wood truss that has a depth 

greater than 4 in. See Figure 7.
1-1/2 in. to 4 in. (40 to 100 mm) below 

non-combustible insulation-filled solid 

wood joists or composite wood joists. 

See Figure 6.

Remote Area (Steel Pipe)

The remote area for wood truss con-

struction or bar joist construction 

(see Figure 4), solid wood joist con-

struction (see Figure 5), or obstructed 

wood truss construction (see Figure 7) 

is 1000 ft² (93 m²) for wet pipe or dry 

pipe systems.
The remote area for non-combusti-

ble insulation-filled solid wood joist 

or wood composite joist construction 

(see Figure 6) without draft curtains is 

to be calculated per the requirements 

of NFPA 13.

Содержание tyco CC3

Страница 1: ...m from floor to ceiling 60 in 1524 mm maximum height for truss and bar joist The 4 2K and 5 6K sprinklers are UL Listed for use with LFP Antifreeze For information about antifreeze compatibility and a...

Страница 2: ...oncealed space is 60 in 1524 mm maximum to 6 in 152 mm minimum System Type CPVC Pipe Light hazard wet pipe system Maximum Distance Between Model CC3 Sprinklers CPVC Pipe TY2199 4 2K 14 ft 4 3 m TY3199...

Страница 3: ...ECK NON COMBUSTIBLE INSULATION 6 152 mm MINIMUM 60 1524 mm MAXIMUM 1 1 2 40 mm MINIMUM 4 102 mm MAXIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER M...

Страница 4: ...ches 150 mm or 1 3 the depth of the con cealed space whichever is greater and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a maximum of 1000 ft 93 m For informa...

Страница 5: ...AXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 84 2134 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 60 1524 mm MAXIMUM M...

Страница 6: ...E ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK MODEL CC3 SPRINKLER CEILING FRAMING 2x FLOOR SOLID WOOD JOISTS NON COMBUSTIBLE INSULATION COMPOSITE WOOD JOISTS 1 1 2 38 mm MINIM...

Страница 7: ...read sealant applied to the pipe threads use only the W Type 6 End A Sprinkler Wrench see Figure 9 for installation of the Model CC3 Sprin klers by applying the wrench to the sprinkler wrench flats on...

Страница 8: ...e completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Spri...

Отзывы: