Required Minimum Density 

(Steel Pipe)

0.10 gpm/ft² (4,1 mm/min)

Minimum Operating Pressure 

(Steel Pipe)

7 psi (0,48 bar)

Obstructions (Steel Pipe)

See Figure 8 in this data sheet for 

obstructions rules.

Installation

The Model CC3 Sprinklers must be 

installed in accordance with this 

section.

General Instructions

The Model CC3 Sprinklers are to be 

installed upright and with their frame 

arms (see Figure 1) in-line with the 

pipe run. See Figures 2 through 7, as 

applicable.
Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in.  

(1,6 mm) for the 200°F (93°C) tempera-

ture rating.
A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained with a torque of 7 to 

14 lb-ft (9,5 to 19,0 N

m). Higher levels 

of torque may distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
The Model CC3 Sprinklers must only 

be installed in the upright position with 

the deflector parallel to the upper deck. 

With pipe thread sealant applied to the 

pipe threads, use only the W-Type 6 

(End A) Sprinkler Wrench (see Figure 9) 

for installation of the Model CC3 Sprin-

klers by applying the wrench to the 

sprinkler wrench flats only.

WRENCH RECESS

(USE END "A"

ONLY)

0"

2-1/2"

(63,5 mm)

3-1/2"

(88,9 mm)

5-1/2"

(139,7 mm)

7-1/2"

(190,5 mm)

9-1/2"

(241,3 mm)

12"

(304,8 mm)

14"

(355,6 mm)

16-1/2"

(419,1 mm)

(0 mm)

Maximum Allowable

Distance of Deflector

Above Bottom of

Obstruction

(B)

Distance from

Centerline of

Sprinkler to Side

of Obstruction

(A)

A≥3C or 3D

A≤24" (609,6 mm)

(Use dimension C or D, whichever is greater)

<12"
<(304,8 mm)
12" to <18"
(304,8 mm to <457,2 mm)
18" to <24"

(457,2 mm to <609,6 mm)
24" to <30"

(609,6 mm to <762,0 mm)
30" to <36"

(762,0 mm to <914,4 mm)
36" to <42"

(914,4 mm to <1066,8 mm)
42" to <48"

(1066,8 mm to <1219,2 mm)
48" to <54"

(1219,2 mm to <1371,6 mm)
54" to <60"

(1371,6 mm to <1524,0 mm)

NOTE:
WEB MEMBERS AND GUSSETS

SHALL NOT BE CONSIDERED

OBSTRUCTIONS PROVIDED THE

MINIMUM 4-1/2 INCH LATERAL

DISTANCE (FIG. 2) REQUIRED

BY THE SPECIFIC APPLICATION

LISTING IS MAINTAINED.

OBSTRUCTION

MODEL CC3

SPRINKLER

C

D

A

OBSTRUCTION

UPPER

DECK

LOWER

DECK

A

MODEL CC3

SPRINKLER

MODEL CC3

SPRINKLER

A

UPPER DECK

OR BOTTOM OF

NON-COMUSTIBLE

INSULATION

B

ELEVATION VIEW

PLAN VIEW

C

D

OBSTRUCTION

FIGURE 9 

W-TYPE 6 SPRINKLER 

WRENCH

FIGURE 8 

NFPA 13 OBSTRUCTION TO WATER DISTRIBUTION CRITERIA 

(REFERENCE)

Содержание tyco CC3

Страница 1: ...m from floor to ceiling 60 in 1524 mm maximum height for truss and bar joist The 4 2K and 5 6K sprinklers are UL Listed for use with LFP Antifreeze For information about antifreeze compatibility and a...

Страница 2: ...oncealed space is 60 in 1524 mm maximum to 6 in 152 mm minimum System Type CPVC Pipe Light hazard wet pipe system Maximum Distance Between Model CC3 Sprinklers CPVC Pipe TY2199 4 2K 14 ft 4 3 m TY3199...

Страница 3: ...ECK NON COMBUSTIBLE INSULATION 6 152 mm MINIMUM 60 1524 mm MAXIMUM 1 1 2 40 mm MINIMUM 4 102 mm MAXIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER M...

Страница 4: ...ches 150 mm or 1 3 the depth of the con cealed space whichever is greater and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a maximum of 1000 ft 93 m For informa...

Страница 5: ...AXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 84 2134 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 60 1524 mm MAXIMUM M...

Страница 6: ...E ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK MODEL CC3 SPRINKLER CEILING FRAMING 2x FLOOR SOLID WOOD JOISTS NON COMBUSTIBLE INSULATION COMPOSITE WOOD JOISTS 1 1 2 38 mm MINIM...

Страница 7: ...read sealant applied to the pipe threads use only the W Type 6 End A Sprinkler Wrench see Figure 9 for installation of the Model CC3 Sprin klers by applying the wrench to the sprinkler wrench flats on...

Страница 8: ...e completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Spri...

Отзывы: