background image

Model CC3 — 4.2 and 5.6 K-factor

Combustible Concealed Space Sprinklers

Specific Application, Upright

Page 1 of 8 

APRIL 2019 

TFP633

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The Model CC3 Combustible Con-

cealed Sprinklers are quick response, 

upright, specific application sprinklers 

designed to provide protection of spe-

cific light hazard combustible, as well 

as non-combustible, con cealed spaces 

requiring sprinkler protection. The 

Model CC3 Sprinklers comply with the 

criteria for the protection of combus-

tible concealed spaces as described 

in NFPA 13.
The Model CC3 Sprinklers are 

designed for installation on BLAZE-

MASTER CPVC wet pipe systems, 

other UL Listed CPVC pipe products, 

and steel wet pipe or dry pipe sprinkler 

systems (see the respective Design Cri-

teria sections). The Model CC3 Sprin-

klers are designed to be installed in the 

following arrangements for both wet 

CPVC and steel:
•  4.2K

14 ft (4,3 m) maximum between 

sprinklers
196 ft²

 

(18,2 m²) maximum cover-

age area

•  5.6K

16 ft (4,9 m) maximum between 

sprinklers
256 ft²

 

(23,8 m²) maximum cover-

age area

•  6 in. (152,4 mm) minimum height for 

joist with steel pipe or CPVC when 

insulation filled. 12 in. (305 mm) min-

imum height for all other arrange-

ments and sizes

•  60 in. (1524 mm) maximum height 

from joist to joist and 84 in. 

 

(2134 mm) from floor to ceiling

•  60 in. (1524 mm) maximum height for 

truss and bar joist

•  The 4.2K and 5.6K sprinklers are UL 

Listed for use with LFP

®

 Antifreeze. 

For information about antifreeze 

compatibility and approved con-

figurations, see the Technical Data 

section.

NOTICE

The Model CC3 Combustible Con-

cealed Sprinklers described herein 

must be installed and maintained in 

compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION (NFPA), in addition to 

the standards of any other authorities 

having jurisdiction. Failure to do so 

may impair the performance of these 

devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number

TY2199 – Upright, 4.2K

TY3199 – Upright, 5.6K

Technical 

Data

Approvals

UL Listed
(Listings and approvals only apply to the 

service conditions indicated in the Design 

Criteria sections.)

Antifreeze Compatibility

Model CC3 TY2199 4.2K and TY3199 5.6K 

Sprinklers are UL Listed for use with LFP

®

 

Antifreeze within 1000 ft² (93 m²) draft curtain 

areas in all construction types described in 

this document.
Model CC3 TY3199 5.6K Sprinkler is also UL 

Listed for use with LFP

®

 Antifreeze within 

2000 ft² (186 m²) draft curtain areas in solid 

wood open truss construction on edge or 

on face.
The use of LFP

®

 Antifreeze should be in 

accordance with LFP

®

 Antifreeze Agency 

Listed Solution for Fire Sprinkler Systems 

(Technical Data Sheet TFP1680). There is 

no system volume limit for this application.

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

½ in. NPT

Discharge Coefficient

K = 4.2 GPM/psi

½

 (60,5 LPM/bar

½

K = 5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Temperature Rating

200°F (93°C)

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . . . . .Glass (3 mm)

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Содержание tyco CC3

Страница 1: ...m from floor to ceiling 60 in 1524 mm maximum height for truss and bar joist The 4 2K and 5 6K sprinklers are UL Listed for use with LFP Antifreeze For information about antifreeze compatibility and a...

Страница 2: ...oncealed space is 60 in 1524 mm maximum to 6 in 152 mm minimum System Type CPVC Pipe Light hazard wet pipe system Maximum Distance Between Model CC3 Sprinklers CPVC Pipe TY2199 4 2K 14 ft 4 3 m TY3199...

Страница 3: ...ECK NON COMBUSTIBLE INSULATION 6 152 mm MINIMUM 60 1524 mm MAXIMUM 1 1 2 40 mm MINIMUM 4 102 mm MAXIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER M...

Страница 4: ...ches 150 mm or 1 3 the depth of the con cealed space whichever is greater and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a maximum of 1000 ft 93 m For informa...

Страница 5: ...AXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 84 2134 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 60 1524 mm MAXIMUM M...