Model CC1 — 2.8 K-factor 

Combustible Concealed Space Sprinklers 

Specific Application, Upright

Page 1 of 8 

DECEMBER 2018 

TFP630

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The Model CC1 Combustible Con-

cealed Sprinklers are fast response, 

upright, specific application sprin-

klers designed to provide protection 

of light hazard combustible, as well as  

non- combustible, concealed spaces 

requiring sprinkler protection. The  CC1 

Sprinklers comply with the criterion for 

the protection of combustible con-

cealed spaces as described in NFPA 

13.
The Model CC1 Sprinklers can in some 

cases allow for the use of BLAZEMAS-

TER CPVC piping or other UL Listed 

CPVC pipe products within concealed 

spaces requiring automatic sprinkler 

protection. At one time, the listing of 

CPVC piping for fire protection systems 

did not allow the use of CPVC piping in 

combustible concealed spaces requir-

ing automatic sprinkler protection. 

With the extensive full scale fire testing 

of the Model CC1 Combustible Con-

cealed Space Sprinklers, performed 

at UL, BLAZEMASTER CPVC may now 

be used in the specified combustible 

concealed spaces requiring automatic 

sprinkler protection, when installed in 

accordance with this technical data 

sheet.
The effectiveness of the Model CC1 

Sprinklers, in the combustible con-

cealed spaces investigated, was clearly 

evident during the full scale fire testing 

for this product. Concealed spaces 

between floors, as well as low pitch 

attics are inherently shallow. Standard 

spray sprinklers, by design, have an 

umbrella like spray pattern that poses 

a difficult challenge when trying to 

achieve effective coverage within a 

shallow space. The Model CC1 Com-

bustible Concealed Space Sprin-

klers have addressed this difficult fire 

challenge.

NOTICE

The Model CC1 Combustible Con-

cealed Sprinklers described herein 

must be installed and maintained in 

compliance with this document, as well 

as with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION, in addition to the standards of 

any other authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions

Sprinkler 

Identification 

Numbers (SINs)

TY1189 - Upright, 2.8K

TY1189 is a redesignation for C1189.

Technical 

Data

Approvals

UL Listed 

(Listings and approvals only apply to the 

service conditions indicated in the Design 

Criteria sections.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1/2 in. NPT

Discharge Coefficient

K = 2.8 gpm/psi

½

 (40,3 lpm/bar

½

)

Temperature Rating

175°F (79°C)

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . . . Stainless Steel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . . . . .Glass (3 mm)

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb allowing the sprinkler to acti-

vate and flow water.

Design 

Criteria

Design criteria is provided as follows:
•  175°F (79°C), Model CC1 Combusti-

ble Concealed Sprinklers with CPVC 

Pipe and horizontal slope above 

sprinklers not exceeding 2:12 (Refer 

to Page 2).

•  175°F (79°C), Model CC1 Combusti-

ble Concealed Sprinklers with Steel 

Pipe and horizontal slope above 

sprinklers not exceeding 2:12 (Refer 

to Page 4).

Содержание tyco CC1

Страница 1: ...this product Concealed spaces between floors as well as low pitch attics are inherently shallow Standard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challeng...

Страница 2: ...R CPVC that is offset over an obstruction Required Density CPVC Pipe 0 10 gpm ft 4 1 mm min Minimum Operating Pressure CPVC Pipe 10 psi 0 7 bar Obstructions CPVC Pipe All obstruction criteria per NFPA...

Страница 3: ...SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE PIPE RUN OBSTRUCTION CEILING MODEL CC1 SPRINKLER UPPER DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 2 51 mm MAXIMUM 6...

Страница 4: ...ay be constructed of 1 4 in 6 4 mm plywood to prevent heat from escaping beyond the area For non combustible insulation filled solid wood joist or composite wood joist construction Ref Figure 6 the re...

Страница 5: ...ITH PIPE RUN CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH JOISTS NOT NECESSARILY WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6...

Страница 6: ...15 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INSTALLED PARALLEL WITH TRUSSES NOT NECESSARILY WITH PIPE RUN UPPER DECK MODEL CC1 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER...

Страница 7: ...the W Type 20 End B Sprinkler Wrench Ref Figure 9 for installation of the Model CC1 Sprinklers by applying the wrench to the sprinkler wrench flats only 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7...

Страница 8: ...cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers dama...

Отзывы: