background image

 

 
 

Installation Instructions   

 

Issue Date  February 24, 2006  

 

© 

2006 Johnson Controls, Inc. 

1

 

 

Part No. 24-9890-48, Rev. C 

www.johnsoncontrols.com 

 

TEC2103-1 Networked Multi-Stage Thermostat 

 

Application 

The TEC2103-1 is an N2 networked thermostat that 
provides control of multi-stage Heating, Ventilating, 
and Air Conditioning (HVAC) equipment. The 
TEC2103-1 provides exceptional accuracy through the 
use of a unique Proportional-Integral (PI) time 
proportioning algorithm. The algorithm virtually 
eliminates temperature offset associated with 
traditional, differential-based on/off thermostats. The 
TEC2103-1 also uses an adaptive control logic 
algorithm to control the space temperature during 
recovery to minimize overshoot while providing 
maximum comfort. 

The TEC2103-1 has Metasys® N2 communication 
capability. This communication allows the user to view 
and adjust parameters from a remote workstation. 
Additionally, the menu driven backlit display, plain text 
menus, and five keys on the TEC2103-1 make 
operating the thermostat easy and intuitive. 

Note: 

In this document, Building Automation System 

(BAS) is a generic term that refers to the Metasys 
Network (Network Control Module [NCM] or N30 
Series), and Companion (CPN) supervisory systems. 
The specific system names are used when referring to 
system specific applications. 

Installation 

Location Considerations 

Locate the TEC2103-1 thermostat: 

 

on a partitioning interior wall, and approximately 
5 ft. (1.5 m) above the floor in a location of 
average temperature 

 

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors 

 

away from steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical 
interference 

To install the thermostat: 

1. 

Remove the security screw on the bottom of the 
thermostat cover using a Phillips-head 
screwdriver. Open the thermostat by pulling on 
the bottom side of the thermostat cover 
(Figure 1). 

2. 

Unlock the Printed Circuit Board (PCB) by 
carefully pressing the locking tabs to the right 
(Figure 2). Open the thermostat’s PCB to the left. 

3. 

Pull out approximately 6 in. (152 mm) of wires 
from the wall and insert the cable through the 
hole in the base. 

4. 

Align the base on the wall, and using the base as 
a template, mark the location of the two mounting 
holes on the wall. Confirm the thermostat base is 
installed with the proper side up. 

5. 

Use the supplied anchors and screws for 
mounting on drywall or plaster. Drill two 3/16 in. 
(4.7 mm) holes at the marked locations and tap 
nylon anchors flush to wall surface (Figure 3). 

6. 

Position base on the wall, insert screws through 
mounting base, and fasten into wall anchors. Do 
not overtighten screws. 

7. 

Swing the thermostat PCB back to the right to 
close. Gently press on the PCB to secure each of 
the locking tabs. 

8. 

Pull out the screw terminal blocks using the 
pull-tabs on each connector (Figure 4). 

Note: 

The number of terminals on the terminal 

blocks varies depending on the TEC model. 

Содержание TEC2103-1

Страница 1: ...a partitioning interior wall and approximately 5 ft 1 5 m above the floor in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills st...

Страница 2: ...re or malfunction of the TEC2103 1 fig1 b Figure 1 Removing the Thermostat Cover PCB Locking Tabs fig2 b Figure 2 Opening the Thermostat PCB fig3 b Figure 3 Mounting the Thermostat Base fig4 b Figure...

Страница 3: ...sformer 24 VAC common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable digital input Configura...

Страница 4: ...5 to 32 C Setback Cooling SP a g Unoccupied Cooling SP ADI 6 N2 AO CSAD 54 to 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C...

Страница 5: ...selects System Mode On at the TEC keypad the TEC ends up with the System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode...

Страница 6: ...u item MENU key to access the Main User Menu or exit the menu down arrow key to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manua...

Страница 7: ...he configuration key Figure 7 Exit the Installer Configuration Menu any time by pressing the MENU key and at the exit prompt pressing the YES key To pass over a parameter without changing it press the...

Страница 8: ...scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each digital input can be programmed in one of four conditions None No function is associated with...

Страница 9: ...tions Enabling Frost Protection Frost pr Frost protection establishes a minimum heating setpoint of 42 F 5 5 C to prevent freezing in the zone controlled by the thermostat If enabled frost protection...

Страница 10: ...erature control but could accelerate the wear of mechanical components in the equipment To set the maximum number of heating cycles per hour while in the Installer Configuration Menu 1 Answer NO to al...

Страница 11: ...ess YES to store the address The display now shows the temporary occupancy time prompt See the Establishing the Temporary Occupancy Time ToccTime section for instructions Note Pressing the YES and NO...

Страница 12: ...ages prompt appears in the display Press YES to enter the setting cooling stages menu 2 Using the UP DOWN arrow keys select 1 0 or 2 0 stages Press YES to store the selection The display now shows the...

Страница 13: ...e Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule only appears when in the Override Mode To resume the schedule while in the Main User Menu...

Страница 14: ...to advance to the unoccupied heating setpoint Use the UP DOWN arrow keys to set temperature Press YES to store value and advance to next menu Press YES to change the unoccupied heating setpoint Press...

Страница 15: ...ed periods even if the system mode is set to off Automatic Fan Mode auto Operates the fan only on a call for heating or cooling for both occupied and unoccupied periods This is the default setting Sma...

Страница 16: ...able runs are broken Locate and correct the wiring TEC2103 1 does not come online Device type is incorrect TEC2103 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed I...

Страница 17: ...50082 2 EMC Immunity Pending FCC Compliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules The...

Отзывы: