TEC2102-3 N2 Networked Heat Pump Thermostat Installation Instructions

14

To enter the permanent heating and cooling setpoints 
for the Occupied and Unoccupied Modes, follow the 
steps in Table 3. When changing the temperatures, 
press the keys once to change the temperature in 
0.5F°/0.5C° increments; press and hold down the keys 
to change the temperature in 5.0F°/5.0C° increments. 

Entering Temporary Temperature Setpoints

To temporarily change the setpoint, press the 

UP/DOWN

 arrow keys to change the temporary 

setpoint for the current mode of operation.

Note:

Whether the thermostat is heating or cooling, 

the respective setpoint is temporarily adjusted. To 
toggle between the temporary heating and cooling 
setpoints, press the 

NO

 key while changing the 

temporary setpoints.

Ending Temporary Temperature Setpoints

The temporary setpoints remain in effect for the 
duration set in the 

TOccTime

 parameter or until 

manually released.

To release the temporary setpoint sooner, while in the 
Main User Menu:

1.

Press the 

YES

 key to the first prompt that appears.

2.

If the thermostat does not immediately return to the 
Status Display Menu, press the 

MENU

 key again 

and press the 

YES

 key to exit the Main User Menu.

The setpoint reverts to the Permanent Temperature 
Setpoint.

Table 3:  Entering Permanent Temperature 

Setpoints (Part 1 of 2)

Thermostat 
Display

Description

Press the 

MENU

 key while in the 

Status Display Menu to enter the 
Main User Menu.

Press the 

NO

 key to all prompts until 

the temperature setpoint prompt 
appears on the display (it may be the 
first prompt). Press the 

YES

 key to 

enter the temperature setting menu.

Press the 

YES

 key to change the 

occupied cooling setpoint. Press the 

NO

 key to advance to the occupied 

heating setpoint menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

occupied heating setpoint. Press the 

NO

 key to advance to the unoccupied 

cooling setpoint menu.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to change the 

unoccupied cooling setpoint. Press 
the 

NO

 key to advance to the 

unoccupied heating setpoint.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

RoomTemp 
75.0

°

Temperat 
set? Y/N 

Cooling 
set? Y/N 

Cooling 
75.0

°

Heating 
set? Y/N 

Heating 
68.0

°

Unocc CL 
set? Y/N

 

Unocc CL 
80.0

°

Press the 

YES

 key to change the 

unoccupied heating setpoint. Press 
the 

NO

 key to advance to the 

temperature display units.

Press the 

UP/DOWN

 arrow keys to 

set the temperature. Press the 

YES

 

key to store the value and advance to 
the next menu.

Press the 

YES

 key to set the display 

units to °F or °C. Press the 

NO

 key to 

advance to the temperature setpoint 
type menu.

Press the 

YES

 key to return to the 

Status Display Menu or press the 

NO

 

key to reenter the temperature 
setting menu.

Table 3:  Entering Permanent Temperature 

Setpoints (Part 2 of 2)

Thermostat 
Display

Description

Unocc HT
set? Y/N 

Unocc HT
62.0

°

F

 

°

F/

°

set? Y/N 

Exit?
 Y/N 

Содержание TEC2102-3

Страница 1: ... damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the thermostat This equipment has been tested and found to comply with the limits for a Class A digital device pu...

Страница 2: ...rmostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with the thermostat flush to the wall surface 7 Position the thermostat mounting base on the wall and use the two mounting screws included with the thermostat to secure the base to the surface as illus...

Страница 3: ...material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB 4 Reattach the thermostat cover to the mounting base top side first 5 Use a Phillips head screwdriver to reinstall the security screw on the bottom of the thermostat cover CAUTION Risk of Electric Shock Disconnect the power supply before making electrical connections to avoi...

Страница 4: ...ut 1 Configurable Digital Input 2 Remote Room Temperature Sensor Sensor Common Outdoor Air Sensor N2 Bus Mixed Air or Discharge Air Sensor Function Y1 Y2 G RC C RH W1 O B Aux DI1 DI2 RS Scom OS REF MS Terminal DI1 DI2 If using the same power source for the thermostat and heating loads install a jumper across RC and RH Scom OS Outdoor Air Sensor 24 VAC Thermostat Power Y2 Y1 RC C Aux Heat RH W1 Aux...

Страница 5: ...cent N2 command received by any of the Object Types listed in Table 1 controls the thermostat Overrides take priority over any local adjustment or command in the thermostat If a setpoint is overridden the thermostat adjusts the other setpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C...

Страница 6: ...del Point Type Override Range Room Temp1 ADI 1 N2 AI CSAD 32 to 122 F 0 to 50 C Aux Temp Outdoor Temp1 ADI 2 N2 AI CSAD 40 to 122 F 40 to 50 C Heating SP1 2 Occupied Heating SP ADI 3 N2 AO CSAD 40 to 90 F 4 5 to 32 C Cooling SP1 2 Occupied Cooling SP ADI 4 N2 AO CSAD 54 to 100 F 12 to 37 5 C Setback Heating SP1 2 Unoccupied Heating SP ADI 5 N2 AO CSAD 40 to 90 F 4 5 to 32 C Setback Cooling SP1 2 U...

Страница 7: ...10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum deadband between the setpoints The setpoints can be spread further apart but can never be adjusted closer than the current minimum deadband value Failure to stay within the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2102 3 thermostat Overrides take ...

Страница 8: ...menu item stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu Note When the thermostat is left unattended for 45 seconds the thermostat display resumes scrolling Use the NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu See the Programming Overview section acce...

Страница 9: ... the YES key to choose the desired selection option 4 Press the YES key and then the NO key to continue scrolling through the parameters To exit the Installer Configuration Menu at any time press the MENU key and press the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for appro...

Страница 10: ...ess Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time period at thermostat powerup or at each time power is removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 ...

Страница 11: ...fan operation after a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the supervisory controller Default 4 Range 1 to 255 TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Override Function is en...

Страница 12: ...pump operation may still be used above the high balance point Lo b p 3 Sets the low balance point the outdoor air temperature at which the heat pump operation terminates when the heat pump is in the heating mode Default 12 0 F 24 0 C Range 40 0 F 40 C to 30 0 F 1 0 C Below the low balance point only the auxiliary heat is used to maintain the heating setpoint Heat pump operation may still be used b...

Страница 13: ... mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first prompt 2 Press the YES key to resume the programmed schedule The thermostat returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User ...

Страница 14: ... to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to store the value and advance to the next men...

Страница 15: ...he fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To select the fan mode while in the Main User Menu 1 Press the NO key to all prompts until the fan mode prompt appears on the display Press the YES key to set the fan mode 2 Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the des...

Страница 16: ...o not exceed the maximum number of devices allowed on the N2 Bus per supervisory controller limitations The thermostat does not have power Apply power to the thermostat The N2 cable runs are broken Locate the break and correct the wiring The thermostat device type is incorrect Change the thermostat device type to VND N2 Bus is Offline The wiring on the N2 Bus is broken Repair the wiring No point m...

Страница 17: ...0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Default Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Noncondensing Compliance United St...

Отзывы: