background image

TEC2102-3 N2 Networked Heat Pump Thermostat Installation Instructions 

7

The Controller Point Type is the fixed-point definition 
inside the controller. The BAS Model Point type is the 
definition inside the model file. Use an NCM CS object 
to retrieve the data.

The most recent N2 command received by any of the 
N2 Bus Objects listed in Table 1 controls the 
thermostat.

If an Analog Data (AD) object is overridden by the 
Metasys system, all local changes attempted through 
the thermostat keypad for that AD object are ignored 
until the override is released. For example, if the 
Metasys system sends a write command to turn 
System Mode Off, and then the occupant selects 
System Mode On at the TEC keypad, the TEC ends up 
with the System Mode On; however, if the Metasys 
system sends an override command to turn System 
Mode Off, and then the occupant selects System Mode 
On at the TEC keypad, the TEC keeps the System 
Mode Off.

Once an override is released, the AD object may once 
again be changed through the thermostat keypad, but 
the thermostat does not retain any data entered at the 
TEC keypad during the override.

The value for Heating SP (ADI-3) and Setback 
Heating SP (ADI-5) must stay within the limits 
established in the controller by Minimum Heat SP 
(ADI-7 read-only) and Maximum Heat SP (ADI-8).

The value for Cooling SP (ADI-4) and Setback 
Cooling SP (ADI-6) must stay within the limits 
established in the controller by Minimum Cool SP 
(ADI-9) and Maximum Cool SP (ADI-10 read-only).

If a setpoint is overridden, the TEC, if necessary, 
adjusts the other setpoint to maintain the minimum 
deadband between the setpoints. The setpoints can be 
spread further apart but can never be adjusted closer 
than the current minimum deadband value.

Failure to stay within the limits for a command results in 
an N2 Negative Acknowledge (NAK) error from the 
TEC2102-3 thermostat.

Overrides take precedence over any local adjustment 
or command in the TEC2102-3 thermostat.

Occupancy Override

BD-10

N2 BI

CSBD

0 = No Override
1 = Override

Temporary Occupancy 
Time

1,3

BD-11

N2-MSO

CSMS

0 = 0 hours
1 = 1 hour
2 = 2 hours
.
.
12 = 12 hours

DI1

6,7

BI-1

N2 BI

CSBI

0 = Off
1 = On

Temp Alarm

6

BI-2

N2 BI

CSBI

0 = Normal
1 = Alarm

DI2

6,7

BI-3

N2 BI

CSBI

0 = Off
1 = On

1.

Commandable.

2.

If one setpoint is overridden, the other setpoint may be automatically overridden by the TEC2102-3 thermostat to maintain 
the minimum deadband between the two setpoints.

3.

The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs).

4.

When defining the N2 MSO, select TEC Mode from the States Text Menu. Type 4 for the TEC2102-3 thermostat.

5.

On the Metasys Network Control Module (NCM) system, map BD-9 

Temp Units Mode

 as a Binary Output (BO) object with 

Auto Restore and Local Control set.

6.

Can be a Change-of-State (COS) alarm to the BAS or N2 Dialer Module (NDM) to initiate a dial-out.

7.

The state of DI1 and DI2 is communicated over the N2 network even if the digital inputs are configured as 

None

 through 

the local interface at the thermostat.

Table 1:  N2 Bus Objects  (Part 2 of 2)

Point Name

TEC Point 
Type/Address

N30/NAE 
Object Type

BAS Model 
Point Type

Override Range

Содержание TEC2102-3

Страница 1: ... damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the thermostat This equipment has been tested and found to comply with the limits for a Class A digital device pu...

Страница 2: ...rmostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with the thermostat flush to the wall surface 7 Position the thermostat mounting base on the wall and use the two mounting screws included with the thermostat to secure the base to the surface as illus...

Страница 3: ...material to prevent drafts from affecting the ambient temperature readings 3 Reinsert the screw terminal blocks onto the PCB 4 Reattach the thermostat cover to the mounting base top side first 5 Use a Phillips head screwdriver to reinstall the security screw on the bottom of the thermostat cover CAUTION Risk of Electric Shock Disconnect the power supply before making electrical connections to avoi...

Страница 4: ...ut 1 Configurable Digital Input 2 Remote Room Temperature Sensor Sensor Common Outdoor Air Sensor N2 Bus Mixed Air or Discharge Air Sensor Function Y1 Y2 G RC C RH W1 O B Aux DI1 DI2 RS Scom OS REF MS Terminal DI1 DI2 If using the same power source for the thermostat and heating loads install a jumper across RC and RH Scom OS Outdoor Air Sensor 24 VAC Thermostat Power Y2 Y1 RC C Aux Heat RH W1 Aux...

Страница 5: ...cent N2 command received by any of the Object Types listed in Table 1 controls the thermostat Overrides take priority over any local adjustment or command in the thermostat If a setpoint is overridden the thermostat adjusts the other setpoint if necessary to maintain the minimum deadband between the two setpoints The setpoints can be spread farther apart but can never be adjusted closer than 2F 1C...

Страница 6: ...del Point Type Override Range Room Temp1 ADI 1 N2 AI CSAD 32 to 122 F 0 to 50 C Aux Temp Outdoor Temp1 ADI 2 N2 AI CSAD 40 to 122 F 40 to 50 C Heating SP1 2 Occupied Heating SP ADI 3 N2 AO CSAD 40 to 90 F 4 5 to 32 C Cooling SP1 2 Occupied Cooling SP ADI 4 N2 AO CSAD 54 to 100 F 12 to 37 5 C Setback Heating SP1 2 Unoccupied Heating SP ADI 5 N2 AO CSAD 40 to 90 F 4 5 to 32 C Setback Cooling SP1 2 U...

Страница 7: ...10 read only If a setpoint is overridden the TEC if necessary adjusts the other setpoint to maintain the minimum deadband between the setpoints The setpoints can be spread further apart but can never be adjusted closer than the current minimum deadband value Failure to stay within the limits for a command results in an N2 Negative Acknowledge NAK error from the TEC2102 3 thermostat Overrides take ...

Страница 8: ...menu item stop the Status Display Menu from scrolling and to manually scroll to the next parameter on the menu Note When the thermostat is left unattended for 45 seconds the thermostat display resumes scrolling Use the NO key to decline a parameter change and to advance to the next menu item Use the MENU key to access the Main User Menu or to exit the menu See the Programming Overview section acce...

Страница 9: ... the YES key to choose the desired selection option 4 Press the YES key and then the NO key to continue scrolling through the parameters To exit the Installer Configuration Menu at any time press the MENU key and press the YES key at the exit prompt To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for appro...

Страница 10: ...ess Temporary Temperature Setpoints Access Access No Access System Mode Setting Access No Access No Access Fan Mode Setting Access No Access No Access Pwr del1 Sets the delay time period at thermostat powerup or at each time power is removed and reapplied before any operation fan heating or cooling is authorized Also can be used to sequence the startup of multiple units in one location Default 10 ...

Страница 11: ...fan operation after a heating or cooling cycle has ended The fan delay is only active when the fan is in the Auto mode Com addr N2 network address at the thermostat coincides with the address assigned at the supervisory controller Default 4 Range 1 to 255 TOccTime Sets the duration of the Temporary Occupancy Time when the thermostat is in the Unoccupied mode when a Schedule Override Function is en...

Страница 12: ...pump operation may still be used above the high balance point Lo b p 3 Sets the low balance point the outdoor air temperature at which the heat pump operation terminates when the heat pump is in the heating mode Default 12 0 F 24 0 C Range 40 0 F 40 C to 30 0 F 1 0 C Below the low balance point only the auxiliary heat is used to maintain the heating setpoint Heat pump operation may still be used b...

Страница 13: ... mode To resume the schedule while in the Main User Menu 1 Press the NO key to all prompts until the Cancel ovrd Y N prompt appears If the thermostat is in the unoccupied override state this is the first prompt 2 Press the YES key to resume the programmed schedule The thermostat returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User ...

Страница 14: ... to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature Press the YES key to store the value and advance to the next men...

Страница 15: ...he fan all the time for occupied states and only on a call for heating or cooling in unoccupied states This is the default setting To select the fan mode while in the Main User Menu 1 Press the NO key to all prompts until the fan mode prompt appears on the display Press the YES key to set the fan mode 2 Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the des...

Страница 16: ...o not exceed the maximum number of devices allowed on the N2 Bus per supervisory controller limitations The thermostat does not have power Apply power to the thermostat The N2 cable runs are broken Locate the break and correct the wiring The thermostat device type is incorrect Change the thermostat device type to VND N2 Bus is Offline The wiring on the N2 Bus is broken Repair the wiring No point m...

Страница 17: ...0 C in 0 5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Default Minimum Deadband 2F 1C between Heating and Cooling Ambient Conditions Operating 32 to 122 F 0 to 50 C 95 RH Maximum Noncondensing Storage 22 to 122 F 30 to 50 C 95 RH Maximum Noncondensing Compliance United St...

Отзывы: