TEC2102-3 N2 Networked Heat Pump Thermostat Installation Instructions
11
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default:
4.0
Range:
3.0
to
8.0
cycles per hour
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default:
4.0
Range:
3.0
or
4.0
cycles per hour
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default:
2.0F°/1.0C°
Range:
2.0F°/1.0C°
to
4.0F°/2.0C°
adjustable in 1.0F°/0.5C°
increments
Fan cont
Determines how the fan is activated
in response to Emergency Heat
mode.
Fan cont
applies to W1
(auxiliary heat) and Fan Mode
auto
only.
Fan cont
does not affect fan
operation on a call for cooling or
heating to the compressor (Y1 and
Y2).
Default:
on
(off):
The thermostat does not activate the fan in response to a call
for Emergency Heat. The fan is activated by the equipment fan and
limit control.
(on):
Enables the thermostat to control the fan.
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default
off
(on):
Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off):
No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Com addr
N2 network address at the
thermostat; coincides with the
address assigned at the supervisory
controller.
Default:
4
Range:
1
to
255
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the up/down
arrow keys.
default:
3.0 hrs
Range:
0.0
to
12.0
hrs adjustable in 1-hour increments
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0F°/0.0C°
Range:
-5.0F°/-2.5C°
to
5.0F°/2.5C°
adjustable in 1.0F°/0.5C°
increments
Table 2: Installer Configuration Menu (Part 3 of 5)
Parameter
Appearing
on Display
Description and Default
Selection Options