TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions

7

These setpoints and Unoccupied time are adjustable to 
allow for customization, as dictated by the individual 
space requirements. See Figure 7 for an example of 
increasing room temperature setpoints.  

Configuring the Thermostat Controller

The thermostat controller ships from the factory with 
default settings for all configurable parameters. The 
default settings are shown in Table 3. To reconfigure 
the parameters via the thermostat controller, follow the 
steps in this section.

1.

To access the Installer Configuration Menu, press 
and hold the 

MENU

 key for approximately 

8 seconds. 

Note:

If the 

Password

 parameter is configured, 

Password 0 appears on the thermostat controller 
display indicating that the configured password is 
required to proceed. Use the 

UP/DOWN

 arrow 

keys to indicate the configured password, then 
press the 

MENU

 key to proceed through the 

Installer Configuration Menu parameters.

2.

Once the Installer Configuration Menu begins, 
release and press the 

NO

 key to scroll through the 

parameters listed in Table 3. 

3.

When the desired parameter is displayed, use the 

YES

 key to choose the desired selection option. 

4.

Press the 

YES

 key and then the 

NO

 key to 

continue scrolling through the parameters.

When the thermostat controller is in the Installer 
Configuration Menu and left unattended for 
approximately 8 seconds, the thermostat controller 
reverts to the Status Display Menu.

Configuring Inputs DI1 and DI2

When DI1 and DI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

Both inputs can be configured to the Selection Options 
included in Table 3. 

Configuring the Wireless Mesh Network 
Settings

Use the following process to configure the wireless 
mesh network settings.

1.

Select a 

PAN ID

 and 

Channel

. Use these same 

values for every TEC Wireless Thermostat 
Controller (and the associated coordinator) on the 
same wireless mesh network.

2.

Select a 

Com Address

 for each thermostat 

controller (1 to 254). This address must be unique 
to each TEC Wireless Thermostat Controller on the 
same wireless network (that is, unique to the 

PAN 

ID

 and 

Channel

 combination).

After configuring the wireless mesh network settings, 
refer to the 

TEC20xx-4 and TEC20xx-4+PIR Series 

Wireless Thermostat Controller System Technical 
Bulletin (LIT-12011596)

 for directions on integrating the 

TEC Wireless Thermostat Controllers and TEC20 
Coordinator with a supervisory controller. 

Figure 7: Increasing Room Temperature Setpoints

Occ Heat

= 72°F

Occ Cool

= 75°F

Unocc Heat

= 65°F

Room Temperature

FI

G

:r

m

_t

m

p

Содержание TEC2001-4

Страница 1: ...o equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property a...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...ng covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mou...

Страница 4: ...king electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wire...

Страница 5: ...ys to change the configuration parameters and activate a setpoint adjustment Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The fan LED...

Страница 6: ...ce to access the Main User Menu This menu is most commonly used by the zone occupant The Main User Menu includes the following parameters Temperature Setpoints System Mode Fan Mode The Main User Menu...

Страница 7: ...through the parameters When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds the thermostat controller reverts to the Status Display Men...

Страница 8: ...to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated with an...

Страница 9: ...ut if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously scroll...

Страница 10: ...cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cycles per...

Страница 11: ...t 0 0C 0 0F Range 2 5C 5 0F to 2 5C 5 0F adjustable in 0 5C 1 0F increments H lock Disables heating stage s operation when the outside air temperature is greater than the configured value If the fan m...

Страница 12: ...n scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule This menu only appears when the thermostat controller is in the over...

Страница 13: ...ser Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES k...

Страница 14: ...s on the display Press the YES key to set the fan mode 2 Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the desired fan mode 3 Press the YES key to return to t...

Страница 15: ...f 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay Triac Contact Rating 19 to 30 VAC 1 0 A Maximum 15 mA Minimum 3 0...

Страница 16: ...ipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Canada UL Listed File E27734 CCN XAPX7 Under CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Indus...

Отзывы: