3.

Carefully pull the locking tabs on the right side of 
the mounting base and unlock the PCB. Open the 
PCB to the left as illustrated in Figure 2.

4.

Pull approximately 152 mm (6 in.) of wire from the 
wall and insert the wire through the hole in the 
mounting base.

5.

Align the mounting base on the wall and use the 
base as a template to mark the two mounting hole 
locations.

6.

Position the thermostat controller mounting base 
so that the arrow on the base points upward to 
indicate the top of the thermostat controller.

Note:

If you need to install the thermostat on an 

electrical junction box, use 2-1/2 x 4 in. 
(63 x 101 mm) square boxes with mud ring covers, 
and avoid smaller 1-1/2 x 4 in. (38 x 101 mm) 
square or 3 x 2 in. (76 x 51 mm) boxes. This 
procedure ensures you have enough space for 
cabling and end-of-line devices, if needed.

Note:

For surface-mount applications, use 

durable mounting hardware such as Molly bolt 
anchors that cannot be easily pulled out of the 
mounting surface.

7.

Secure the mounting base to the wall surface using 
two mounting screws as illustrated in Figure 3.

Note:

Be careful not to overtighten the mounting 

screws.

8.

Swing the PCB back to the right and carefully snap 
it into the locking tabs on the mounting base.

9.

Remove the screw terminal blocks that are 
attached to a disposable adhesive. Figure 4 
illustrates the locations of the screw terminal 
blocks on the thermostat controller.

Figure 2: Opening the PCB

F

IG

:p

rn

t_

c

ir

c_

b

rd

PCB
Locking
Tabs

Figure 3: Securing the 

Mounting Base to the Wall

F

IG

:m

n

tn

g

_

b

s

Figure 4: Removing the Screw Terminal Blocks

F

IG

:t

rm

n

l_

b

lc

k

s

Содержание TEC2001-4

Страница 1: ...o equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property a...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...ng covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mou...

Страница 4: ...king electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wire...

Страница 5: ...ys to change the configuration parameters and activate a setpoint adjustment Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The fan LED...

Страница 6: ...ce to access the Main User Menu This menu is most commonly used by the zone occupant The Main User Menu includes the following parameters Temperature Setpoints System Mode Fan Mode The Main User Menu...

Страница 7: ...through the parameters When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds the thermostat controller reverts to the Status Display Men...

Страница 8: ...to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated with an...

Страница 9: ...ut if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously scroll...

Страница 10: ...cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cycles per...

Страница 11: ...t 0 0C 0 0F Range 2 5C 5 0F to 2 5C 5 0F adjustable in 0 5C 1 0F increments H lock Disables heating stage s operation when the outside air temperature is greater than the configured value If the fan m...

Страница 12: ...n scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule This menu only appears when the thermostat controller is in the over...

Страница 13: ...ser Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES k...

Страница 14: ...s on the display Press the YES key to set the fan mode 2 Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the desired fan mode 3 Press the YES key to return to t...

Страница 15: ...f 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay Triac Contact Rating 19 to 30 VAC 1 0 A Maximum 15 mA Minimum 3 0...

Страница 16: ...ipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Canada UL Listed File E27734 CCN XAPX7 Under CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Indus...

Отзывы: