TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions

11

TOccTime

Sets the duration of the Temporary 
Occupancy Time (when the 
thermostat controller is in the 
Unoccupied mode) when a 
Schedule Override Function is 
enabled using either the Main User 
Menu or DI1 or DI2 configured as a 
temporary override remote contact 
(RemOVR).
Sets the effective duration of the 
Temporary heating or cooling 
setpoints set using the 

UP/DOWN

arrow keys.

Default: 

3.0 hrs

Range: 

0.0

 to 

12.0 hrs

 adjustable in 1-hour increments

Cal RS

Sets the desired room air 
temperature sensor calibration 
(offset). The offset can be added to 
or subtracted from the actual 
displayed room temperature.
Default: 

0.0C°/0.0F°

Range:

 

-2.5C°/-5.0F°

 to 

2.5C°/5.0F°

 adjustable in 0.5C°/1.0F° 

increments

Cal OS

Sets the desired outdoor air 
temperature sensor calibration 
(offset). The offset can be added to 
or subtracted from the actual 
displayed room temperature.
Default: 

0.0C°/0.0F°

Range: 

-2.5C°/-5.0F°

 to 

2.5C°/5.0F°

 adjustable in 0.5C°/1.0F° 

increments

H lock

Disables heating stage(s) operation 
when the outside air temperature is 
greater than the configured value. If 
the fan mode is set to Auto or 
Smart, the fan output is also 
disabled. Requires that an outside 
air temperature sensor be installed 
and connected.
Default: 

120°F/49°C

Range: 

-15°F/-26°C

 to 

120°F/49°C

 adjustable in 5F°/5C° 

increments

C lock

Disables cooling stage(s) operation 
when the outside air temperature is 
less than the configured value. If the 
fan mode is set to Auto or Smart, 
the fan output is also disabled. 
Requires that an outside air 
temperature sensor be installed and 
connected.
Default: 

-40°F/-40°C

Range: 

-40°F/-40°C

 to 

95°F/35°C

 adjustable in 5F°/5C° increments

Unocc TM

Sets the time delay between the 
moment when the thermostat 
controller toggles from the Occupied 
mode to the Unoccupied mode after 
the last motion is detected by the 
occupancy sensor.
Default: 

0.5 hours

Range: 

0.5 hours

 to 

24.0 hours

 adjustable in 0.5 hour increments

Table 3:  Installer Configuration Menu  (Part 4 of 5)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2001-4

Страница 1: ...o equipment under normal operating conditions Where failure or malfunction of the thermostat controller could lead to personal injury or property damage to the controlled equipment or other property a...

Страница 2: ...Thermostat Controller Follow these steps to install the thermostat controller 1 Use a Phillips head screwdriver to remove the security screw if it is installed on the bottom of the thermostat controll...

Страница 3: ...ng covers and avoid smaller 1 1 2 x 4 in 38 x 101 mm square or 3 x 2 in 76 x 51 mm boxes This procedure ensures you have enough space for cabling and end of line devices if needed Note For surface mou...

Страница 4: ...king electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wire...

Страница 5: ...ys to change the configuration parameters and activate a setpoint adjustment Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The fan LED...

Страница 6: ...ce to access the Main User Menu This menu is most commonly used by the zone occupant The Main User Menu includes the following parameters Temperature Setpoints System Mode Fan Mode The Main User Menu...

Страница 7: ...through the parameters When the thermostat controller is in the Installer Configuration Menu and left unattended for approximately 8 seconds the thermostat controller reverts to the Status Display Men...

Страница 8: ...to 26 Note Setting this parameter to 10 disables the function GET FROM Parameter not available at this time N A DI1 Configuration of Digital Input 1 Default None None No function is associated with an...

Страница 9: ...ut if no airflow is detected 10 seconds after the fan Terminal G is energized Contact open no airflow contact closed airflow present MenuScro Gives the option of having the display continuously scroll...

Страница 10: ...cph Sets the maximum number of Heating cycles per hour Default 4 0 Range 3 0 to 8 0 cycles per hour Cool cph Sets the maximum number of Cooling cycles per hour Default 4 0 Range 3 0 or 4 0 cycles per...

Страница 11: ...t 0 0C 0 0F Range 2 5C 5 0F to 2 5C 5 0F adjustable in 0 5C 1 0F increments H lock Disables heating stage s operation when the outside air temperature is greater than the configured value If the fan m...

Страница 12: ...n scrolling through the Status Display Menu Override now appears for the schedule status parameter Resuming the Programmed Schedule This menu only appears when the thermostat controller is in the over...

Страница 13: ...ser Menu Press the NO key to all prompts until the temperature setpoint prompt appears on the display it may be the first prompt Press the YES key to enter the temperature setting menu Press the YES k...

Страница 14: ...s on the display Press the YES key to set the fan mode 2 Press the UP DOWN arrow keys to locate the desired fan mode Press the YES key to select the desired fan mode 3 Press the YES key to return to t...

Страница 15: ...f 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals RC and C at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay Triac Contact Rating 19 to 30 VAC 1 0 A Maximum 15 mA Minimum 3 0...

Страница 16: ...ipment FCC Compliant to Part 15 247 Regulations for Low Power Unlicensed Transmitters Canada UL Listed File E27734 CCN XAPX7 Under CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Indus...

Отзывы: