TEC2001-4 and TEC2001-4+PIR Single-Stage Wireless Thermostat Controllers Installation Instructions
11
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
thermostat controller is in the
Unoccupied mode) when a
Schedule Override Function is
enabled using either the Main User
Menu or DI1 or DI2 configured as a
temporary override remote contact
(RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN
arrow keys.
Default:
3.0 hrs
Range:
0.0
to
12.0 hrs
adjustable in 1-hour increments
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0C°/0.0F°
Range:
-2.5C°/-5.0F°
to
2.5C°/5.0F°
adjustable in 0.5C°/1.0F°
increments
Cal OS
Sets the desired outdoor air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default:
0.0C°/0.0F°
Range:
-2.5C°/-5.0F°
to
2.5C°/5.0F°
adjustable in 0.5C°/1.0F°
increments
H lock
Disables heating stage(s) operation
when the outside air temperature is
greater than the configured value. If
the fan mode is set to Auto or
Smart, the fan output is also
disabled. Requires that an outside
air temperature sensor be installed
and connected.
Default:
120°F/49°C
Range:
-15°F/-26°C
to
120°F/49°C
adjustable in 5F°/5C°
increments
C lock
Disables cooling stage(s) operation
when the outside air temperature is
less than the configured value. If the
fan mode is set to Auto or Smart,
the fan output is also disabled.
Requires that an outside air
temperature sensor be installed and
connected.
Default:
-40°F/-40°C
Range:
-40°F/-40°C
to
95°F/35°C
adjustable in 5F°/5C° increments
Unocc TM
Sets the time delay between the
moment when the thermostat
controller toggles from the Occupied
mode to the Unoccupied mode after
the last motion is detected by the
occupancy sensor.
Default:
0.5 hours
Range:
0.5 hours
to
24.0 hours
adjustable in 0.5 hour increments
Table 3: Installer Configuration Menu (Part 4 of 5)
Parameter
Appearing
on Display
Description and Default
Selection Options