TE-6800 Series Temperature Sensors Installation Instructions
5
Modular Jack Wiring (TE-68xP Models)
The modular jack connection is shown in Figure 1.
Make modular jack electrical connections to the 8-pin
RJ45 connector, using 8 conductor standard or
plenum-rated telephone cables. Terminals are
identified in Table 2. Insert the modular jack connector
with the proper polarity (not reversed). Misalignment
can cause damage. Refer to the controller
documentation to determine the appropriate cable
assembly.
Setup and Adjustments
Controller Configuration Switch
A DIP switch configures the TE-6800 for use with the
desired controller by enabling or disabling the manual
override PB and the LED, in appropriate models.
To change the controller mode, use the three position
DIP switch located on the Printed Circuit Board (PCB).
See Figure 5 and consult
controller compatibility.
Warmer/Cooler Setpoint and No Setpoint Models
For the Warmer/Cooler Setpoint and No Setpoint
models, the factory default is the
LED Mode:ON
described as follows. The switch positions enable/
disable the following functions:
IMPORTANT:
Do not insert a 6-pin connector or
anything other than an RJ-45 8-pin connector into
the 8-pin jack on the back of the TE-6800
Temperature Sensor to prevent damaging the
modular jack.
Table 2: Modular Jack Pin Designations
Modular
Jack Pin
Number
Signal Designation
1
LED and Manual Override
2
Setpoint
3
Temperature Sensor and Manual Override
4
Temperature Sensor Common
5
24 VAC (+15 VDC - VMA only)
1
1.
The +15 VDC power supply is used only when a
TE-6800 Series sensor is connected to a VMA
controller.
6
Common (for Power, Zone Bus, or Manual
Override)
7
Setpoint Common
8
Zone Bus
Risk of Property Damage.
Do not use switch settings other than those shown in
Figure 5. Using other switch settings may cause
incorrect controller operation or damage to the
element, controller, [and/or] controlled equipment.
Risque de dégâts matériels.
Ne pas utiliser un paramétrage des commutateurs
différent de celui-ci illustré à la Figure 5. L'utilisation
d'autres paramètres de commutateurs risque de
provoquer un fonctionnement incorrect du contrôleur
ou d'endommager l'élément, le contrôleur [et/ou]
l'équipement contrôlé.
LED Mode: OFF
(LED Disabled, but Sensor
and PB Enabled)
Switch positions are
down, up, and down. The
LED remains off at all
times.
LED Mode: ON
(LED, Sensor, and PB
Enabled)
Switch positions are
factory set up, down, and
up. The controller
determines the LED
mode.
LED Mode: NO PB
(LED and PB Disabled, but
Sensor Enabled)
Switch positions are all
down. LED is off, and the
PB does not function.