TE-6800 Series Temperature Sensors Installation Instructions

6

Temperature Setpoint

Adjust the setpoint using the setpoint adjustment dial. 
Rotate clockwise to raise the temperature. Rotate 
counterclockwise to lower the temperature.

Troubleshooting

TE-6800 Series Temperature Sensors are 
recommended for use only with Johnson Controls® 
digital controllers. If the TE-6800 is not functioning 
properly, use the following procedure to identify the 
problem and determine a solution:

1.

Check that the TE-6800 is mounted in a location 
indicative of the space temperature (for example, 
away from drafts or sunlight).

2.

Check the wiring:

Verify that the wiring is correct. The modular 
jack connector must be inserted with the 
proper polarity (not reversed). Misalignment 
can cause damage.

Check all supply voltage connections. See 
Figure 2, Figure 3, or Figure 4, if necessary.

3.

Check the settings:

Verify that any scaling modifications, setpoint 
adjustments, and overrides have been saved 
and downloaded to the controller.

Check the override status (Temporary 
Occupancy mode vs. Unoccupied mode) at the 
controller.

Check the setpoint settings.

4.

Confirm DIP switch positions if:

the LED remains on or is dim

the room sensor reading is outside of the 
normal range for the space being sensed

Note:

Make sure the DIP switch setting is correct for 

the controller used with the TE-6800.

5.

Replace the TE-6800 if the troubleshooting 
suggestions fail to remedy the problem.

DIP switch in the 

default position.

ON

1    2    3

LED

MODE

REMOVING THE CIRCUIT

BOARD VOIDS WARRANTY

OFF

ON

NO 

PB

Key:

Switch is in the up position (On).

Switch is in the down position (Off).

Note: Read the switch positions 
from left to right. 

Figure 5: DIP Switch Positions 

Table 3:  Controller Compatibility with LED Mode and PB

Types of 
TE-6800

LED Mode 
(Figure 5)

Features 
Enabled on 
TE-6800

Features Recognized by Controller

AHU

UNT1100

VAV1xx or 
UNT1xx

VMA1200 

Series

1

VMA1400 

Series

1

Warmer/
Cooler 
Setpoint

LED Off

2

Sensor and 
Manual 
Override

No

Yes

Yes

Yes

Yes

LED On

Sensor, 
Manual 
Override, and 
LED

No

No

No

Yes

Yes

No PB

Room Sensor 
Only

Yes

Yes

Yes

Yes

Yes

1.

For these controllers, the LED appears brighter when the manual override PB is pushed.

2.

Holding the manual Override PB for more than 2 seconds may affect the sensor reading.

Содержание TE-6800 Series

Страница 1: ... Temperature Sensor on a wallbox requires accessory NS WALLPLATE 0 ordered separately IMPORTANT The TE 6800 Series Temperature Sensor is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the sensor could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the ...

Страница 2: ...e Note Confirm that the mounting base is positioned with the proper edge up The mounting base is positioned properly when the security screw is located on the top edge of the base 5 Secure the mounting base to the wall using the appropriate mounting hardware field furnished 6 Set DIP switches for the desired operation See Setup and Adjustments and Internal Wiring Diagrams for additional informatio...

Страница 3: ...Figure 5 for an explanation of the Light Emitting Diode LED and Push Button PB modes Make connections pairing the following wires sensor Terminal 1 and Terminal 2 setpoint Terminal 3 and Terminal 4 Zone Bus and Common COM Terminals 6 and 7 Shielding is not required If used follow the system controller s recommendations for grounding the shield Note The Manual Override PB does not respond when the ...

Страница 4: ...rnal wiring diagram with DIP switches set as shown on the right LED Mode OFF and Manual Override push button enabled ON term_bloc2 Not Connected Modular Jack Pin Numbers Figure 4 Terminal Block Location and Wiring Table 1 Terminal Block Wiring Part 1 of 2 Terminal Signal Designation 1 Temperature Sensor and Manual Override 2 Temperature Sensor Common 3 Setpoint Common and LED Common 4 Setpoint 5 2...

Страница 5: ...tor into the 8 pin jack on the back of the TE 6800 Temperature Sensor to prevent damaging the modular jack Table 2 Modular Jack Pin Designations Modular Jack Pin Number Signal Designation 1 LED and Manual Override 2 Setpoint 3 Temperature Sensor and Manual Override 4 Temperature Sensor Common 5 24 VAC 15 VDC VMA only 1 1 The 15 VDC power supply is used only when a TE 6800 Series sensor is connecte...

Страница 6: ...rary Occupancy mode vs Unoccupied mode at the controller Check the setpoint settings 4 Confirm DIP switch positions if the LED remains on or is dim the room sensor reading is outside of the normal range for the space being sensed Note Make sure the DIP switch setting is correct for the controller used with the TE 6800 5 Replace the TE 6800 if the troubleshooting suggestions fail to remedy the prob...

Страница 7: ...jack connector Terminal Block Screw type terminals for 18 to 24 AWG wire Zone Bus Access 6 pin connector with front bottom access for a laptop with HVAC PRO software and CVTPRO converter Manual Override Integral momentary push button DIP switch selectable LED Light Green LED light indicates two modes of operation VMA1200 and VMA1400 Series controllers only Ambient Operating Conditions 32 to 131 F ...

Страница 8: ... nominal and conform to acceptable industry standards For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damage resulting from misapplication or misuse of its products European Single Point of Contact NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERM...

Отзывы: