background image

TE-63xS Series Strap-Mount Temperature Sensors Installation Instructions

2

Wiring

For 1k ohm nickel temperature sensors, wire 
resistance can cause approximately 1F° (0.56C°) of 
error for every 250 ft (76 m) run of 18 AWG (1.0 mm 
diameter) wire, or every 100 ft (31 m) run of 22 AWG 
(0.6 mm diameter) wire. To minimize error due to field 
wiring, limit total resistance of all nickel temperature 
sensor wiring to 3 ohms.

The 10k ohm thermistor applications tolerate relatively 
long wiring before the wire resistance adds significantly 
to total resistance measured at the controller. As a 
general rule, a 150 ft (46 m) two-wire 18 AWG 
(1.0 mm diameter) run contributes 2 ohms of error, or 
less than 1F° (0.56C°) error over the sensor operating 
temperature range.

Refer to the appropriate controller documentation for 
recommended sensor wiring.    

Repair Information

If the TE-63xS Series Strap-Mount Temperature 
Sensor fails to operate within its specifications, replace 
the unit. For a replacement sensor, contact the nearest 
Johnson Controls

®

 representative.

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit 
ou connectés de façon incorrecte 
risquent d'endommager 
irrémédiablement l'équipement.

IMPORTANT:

Use copper conductors only. Make 

all wiring connections in accordance with local, 
national, and regional regulations. Do not exceed 
the TE-63xS Series Strap-Mount Temperature 
Sensor’s electrical ratings.