background image

TE-6300M Series Well Insertion Temperature Sensors Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Applications 

 

Installation 

Dimensions  

Mounting

Location Considerations

Consider the following mounting location guidelines:

Avoid areas subject to the effects of excessive 
vibration, electrical noise, direct sunlight, or radiant 
heat.

Keep electrical wiring as short as possible to 
minimize temperature error.

Mounting the Temperature Sensor

See Figure 2 and mount the temperature sensor:  

IMPORTANT:

The TE-6300M Series Well Insertion 

Temperature Sensors are intended to provide an 
input to equipment under normal operating 
conditions. Where failure or malfunction of the 
sensor could lead to personal injury or property 
damage to the controlled equipment or other 
property, additional precautions must be designed 
into the control system. Incorporate and maintain 
other devices, such as supervisory or alarm systems 
or safety or limit controls, intended to warn of or 
protect against failure or malfunction of the sensor.

IMPORTANT :

Le TE-6300M Series Well Insertion 

Temperature Sensor est destiné à transmettre des 
données entrantes à un équipement dans des 
conditions normales de fonctionnement. Lorsqu'une 
défaillance ou un dysfonctionnement du sensor 
risque de provoquer des blessures ou 
d'endommager l'équipement contrôlé ou un autre 
équipement, la conception du système de contrôle 
doit intégrer des dispositifs de protection 
supplémentaires. Veiller dans ce cas à intégrer de 
façon permanente d'autres dispositifs, tels que des 
systèmes de supervision ou d'alarme, ou des 
dispositifs de sécurité ou de limitation, ayant une 
fonction d'avertissement ou de protection en cas de 
défaillance ou de dysfonctionnement du sensor.

IMPORTANT:

Do not install the TE-6300M Series 

Well Insertion Temperature Sensor in ambient 
temperatures beyond the specified -50 to 220°F
(-46 to 104°C) temperature range. Installing the 
temperature sensor in ambient temperatures 
beyond this range may damage the unit and void the 
warranty.

Figure 1: Sensor Dimensions, in. (mm)

F

IG

sn

s_

d

im

1.80 (45.7)

0.875
(22.2)

Side View

1.20

(30.5)

1.87 (47.5)

1.87

(47.5)

0.60 (15.2)

Front View

4.73 (120.1) maximum
7.73 (196.3) maximum

Figure 2: Installing the Well Insertion Sensor

F

IG

s

n

s

_

in

s

t

or

 

Sensor

Probe

TE-6300W-101
TE-6300W-102

Thermowell

Direct Mount for

6 in. (152 mm) Probe Models

Set Screw

1/2 in.

NPT

Threaded Mount for

8 in. (203 mm) Probe Models

Well Adaptor

Set Screw

TE-6300W-110 Thermowell

TE-6300M Series Well Insertion Temperature Sensors

Installation Instructions

TE-631xM, TE-635xM,
TE-634xM, TE-636xM

Part No. 24-4034-182, Rev. G

Issued March 2016

2 4 - 4 0 3 4 - 1 8 2 ,   Re v .   G