background image

TE-6300M Series Well Insertion Temperature Sensors Installation Instructions

2

Note:

The Johnson Controls® TE-6300W-101 

thermowell contains thermal compound. The 
TE-6300W-102 and TE6300W-110 do not contain 
thermal compound. Add thermal compound 
(F-1000-182, or equivalent) before inserting the probe 
if the well does not include thermal compound. For 
proper sensor function, mount the well so that any 
condensation that forms drains out of the probe.

1.

If the thermowell is:

Direct Mount

 (TE-63xAM-2), loosen the set 

screw

Threaded 

(TE-63x2M), screw the well adaptor 

into the thermowell and loosen the well adaptor 
set screw

2.

Insert the sensor probe into the thermowell until it  
touches the bottom.

3.

Pull back the probe approximately 1/8 in. (3 mm) 
and then tighten the set screw.

4.

Wire the sensor to the controller.

5.

Reposition the cover and tighten the cover screws.

Wiring

For 1k ohm nickel temperature sensors, wire resistance can 
cause about 1F° (0.56C°) of error for every 250 ft (76 m) run 
of 18 AWG (1.0 mm diameter) wire, or every 100 ft (31 m) run 
of 22 AWG (0.6 mm diameter) wire.

For 1k ohm platinum temperature sensors, wire resistance 
can cause about 1F

(0.56C

) of error for every 150 ft (46 m) 

run of 18 AWG (1.0 mm diameter) wire, or every 50 ft (15 m) 
run of 22 AWG (0.6 mm diameter) wire. To minimize error 
due to field wiring, limit total resistance of all nickel 
temperature sensor wiring to 3 ohms, and all platinum 
temperature sensor wiring to 2 ohms.The 2.2k and 10k ohm 

thermistor applications permit wiring to be relatively long 
before wire resistance adds significantly to total resistance 
measured at the controller. As a general rule, a 150 ft (46 m) 
two-wire 18 AWG (1.0 mm diameter) run contributes 2 ohms 
of error, or less than 1F

(0.56C

) error over the sensor 

operating temperature range.

Refer to the appropriate controller documentation for 
recommended sensor wiring. Secure the wiring bushing or 
conduit only to the temperature sensor base. See Table 1 for 
an explanation of the lead wiring color convention

     

Repair Information

I

f the TE-6300M Series Well Insertion Temperature Sensor 

fails to operate within its specifications, replace the unit. For a 
replacement sensor, contact the nearest Johnson Controls 
representative.

Table 1:  Lead Wiring Color Code

Sensor Type

Lead Color

1k ohm Nickel

White

1k ohm Platinum

White with Blue Stripe

2.2k ohm Thermistor

Red

10k ohm Thermistor

White with Green Stripe

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit 
ou connectés de façon incorrecte 
risquent d'endommager 
irrémédiablement l'équipement.

IMPORTANT:

Use copper conductors only. Make 

all wiring connections in accordance with local, 
national, and regional regulations. Do not exceed 
the TE-6300M Series Well Insertion Temperature 
Sensor’s electrical ratings.