background image

 

The display now shows the minimum heating/cooling 
deadband prompt. See 

Setting the Heating/Cooling 

Deadband

 

(Deadband)

 section for instructions. 

Setting the Heating/Cooling Deadband (Deadband) 

The heating/cooling deadband setting establishes the 
minimum difference between the heating and cooling 
setpoints. The range is adjustable from 2 to 4 F

°

 

(1 to 2 C

°

). 

To change the minimum deadband between the 
heating and cooling setpoints while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the deadband 

setpoint prompt appears in the display. Press YES 
to enter the deadband setpoint menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum deadband between the heating and 
cooling setpoints. Press YES to store the value. 

The display now shows the fan control prompt. See 

Setting the Fan Control (Fan cont) 

section for 

instructions. 

Setting the Fan Control (Fan cont) 

This parameter controls how the fan activates in 
response to a call for heating. 

When the fan is in Auto Mode (as selected on the Main 
User Menu): 

• 

Selecting 

on

 enables the thermostat to control the 

fan on a call for heating or cooling. 

• 

Selecting 

off

 enables the thermostat to energize 

the fan on a call for cooling only. On a call for 
auxiliary heating, the fan is controlled by the 
equipment fan limit control. 

To set the fan control while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan control 

prompt appears in the display. Press YES to enter 
the fan control menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the fan delay prompt. See 

Setting the Fan Delay (Fan del)

 section for 

instructions. 

Setting the Fan Delay (Fan del) 

The fan delay extends the fan operation by 
60 seconds after the call for heating or cooling has 
ended. This feature is only active when the fan is in 
the 

Auto

 mode. 

To enable the fan delay while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan delay 

prompt appears in the display. Press YES to enter 
the fan delay menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the occupancy override 
prompt. See 

Establishing the Temporary Occupancy 

Time (TOccTime)

 section for instructions. 

Establishing the Temporary Occupancy Time 
(TOccTime) 

The temporary occupancy time is the length of time 
the occupied mode setpoints are used when the 
override function is enabled (the override function can 
be enabled from the Main User Menu or from one of 
the digital inputs) or a temporary setpoint is entered. 
The range is adjustable from 0 to 12 hours. 

To change the temporary occupancy time while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the temporary 

occupancy time prompt appears in the display. 
Press YES to enter the temporary occupancy time 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the length 

of time the temporary occupancy setpoint should 
be in effect. Press YES to store the time. 

The display now shows the room sensor calibration 
prompt. See 

Room Air Sensor Calibration (Cal RS)

 

section for instructions. 

Room Air Sensor Calibration (Cal RS) 

An offset can be added or subtracted to the actual 
displayed room temperature as needed. The range is 

±

5.0 F

°

 (

±

2.5 C

°

), adjustable in increments of 1 F

°

 

(0.5 C

°

). 

To change the room sensor calibration/offset while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the room sensor 

calibration prompt appears in the display. Press 
YES to enter the room sensor calibration menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

correction that should be applied to the sensor 
reading. Press YES to store the offset. 

The display now shows the outdoor air sensor 
calibration prompt. See 

Outdoor Air Sensor Calibration 

(Cal OS)

 section for instructions. 

Outdoor Air Sensor Calibration (Cal OS) 

An offset can be added or subtracted to the actual 
displayed outdoor air temperature as needed. The 
range is 

±

 5.0F

°

 (

±

 2.5C

°

), adjustable in increments of 

1 F

°

 (0.5 C

°

). 

T600MEP-2 Programmable Economizer Thermostat Installation Instructions    

9

 

Содержание T600MEP-2

Страница 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Страница 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Страница 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Страница 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Страница 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Страница 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Страница 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Страница 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Страница 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Страница 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Страница 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Страница 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Страница 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Страница 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Страница 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Страница 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Страница 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Страница 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...

Отзывы: