To change the outdoor air sensor calibration/offset 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the outdoor sensor 

calibration prompt appears in the display. Press 
YES to enter the outdoor sensor calibration menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

correction that should be applied to the sensor 
reading. Press YES to store the offset. 

The display now shows the heating stage setting 
prompt. See 

Enable/Disable Second Heating Stage 

(H Stage)

 section for instructions. 

Enable/Disable Second Heating Stage (H Stage) 

This parameter reverts the operation of two-stage 
thermostats to a single stage when the second heating 
stage is not needed. 

To enable or disable the second heating stage while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting heating 

stages prompt appears in the display. Press YES 
to enter the setting heating stages menu. 

2.  Using the UP/DOWN arrow keys; select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the cooling stage setting 
prompt. See 

Enable/Disable Second Cooling Stage 

(C Stage)

 section for instructions. 

Enable/Disable Second Cooling Stage (C Stage) 

This parameter reverts the operation of two-stage 
thermostats to a single stage when the second cooling 
stage is not needed. 

To enable or disable the second cooling stage while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting cooling 

stages prompt appears in the display. Press YES 
to enter the setting cooling stages menu. 

2.  Using the UP/DOWN arrow keys, select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the heating lockout prompt. 
See 

Setting the Heating Lockout (H lock)

 section for 

instructions. 

Setting the Heating Lockout (H lock) 

This feature disables heating operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is above 
the heating lockout temperature, heating operation is 
disabled. 

The heating lockout temperature parameter is 
adjustable from -15 to 120

°

F (-26 to 49

°

C) in 

increments of 5 F/C

°

To change the outdoor air temperature heating lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating lockout 

prompt appears in the display. Press YES to enter 
the heating lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the cooling lockout prompt. 
See 

Setting the Cooling Lockout (C lock)

 section for 

instructions. 

Setting the Cooling Lockout (C lock) 

This feature disables cooling operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is below 
the cooling lockout temperature, cooling operation is 
disabled. 

The cooling lockout temperature parameter is 
adjustable from -40 to 95

°

F (-40 to 35

°

C) in 

increments of 5 F/C

°

To change the outdoor air temperature cooling lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling lockout 

prompt appears in the display. Press YES to enter 
the cooling lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the number of events prompt. 
See 

Selecting the

 

Number of Events (2/4event) 

section for instructions. 

Selecting the Number of Events (2/4event) 

This feature sets the number of events per 24-hour 
period that can be programmed into the daily 
schedule. 

Two events select one occupied and one unoccupied 
period per 24 hours and four events selects two 
occupied and two unoccupied periods per 24 hours. 

To change the number of events in a 24-hour period 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the number of 

events prompt appears in the display. Press YES 
to enter the number of events menu. 

2.  Use the UP/DOWN arrow keys to select 2 or 

4 events. Press YES to store the value. 

10    

T600MEP-2 Programmable Economizer Thermostat Installation Instructions 

Содержание T600MEP-2

Страница 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Страница 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Страница 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Страница 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Страница 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Страница 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Страница 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Страница 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Страница 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Страница 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Страница 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Страница 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Страница 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Страница 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Страница 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Страница 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Страница 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Страница 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...

Отзывы: