To set the maximum heating setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the maximum 

heating setpoint prompt appears in the display. 
Press YES to enter the maximum heating setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum heating setpoint temperature. Press 
YES to store the value. 

The display now shows the minimum cooling setpoint 
prompt. See 

Setting the Minimum Cooling Setpoint 

(Cool min)

 section for instructions. 

Setting the Minimum Cooling Setpoint (Cool min) 

The minimum cooling setpoint establishes the 
minimum temperature in the cooling setpoint range 
that can be adjusted from the Main User Menu for both 
occupied and unoccupied periods. The parameter is 
adjustable from 54 to 100

°

F (12 to 37.5

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the minimum cooling setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the minimum 

cooling setpoint prompt appears in the display. 
Press YES to enter the minimum cooling setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum cooling setpoint temperature. Press YES 
to store the value. 

The display now shows the anti-short cycle timer 
prompt. See 

Setting the Anti-short Cycle Timer 

(Anticycl)

 section for instructions. 

Setting the Anti-short Cycle Timer (Anticycl) 

The anti-short cycle timer establishes the minimum 
on/off times for the cooling and heating stages. The 
timer is adjustable from 0 to 5 minutes in 1-minute 
increments. Set the anti-short cycle to 0 for equipment 
that possesses its own anti-short cycle timer. 

!

  CAUTION:  Risk of Property Damage. 

Do not set the T600MEP-2 anti-short cycling timer to 
0 minutes if the controlled equipment is not 
protected by its own internal anti-short cycling timer. 
Doing so may result in damage to the controlled 
equipment. 

To set the anti-short cycle time while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the anti-short cycle 

timer prompt appears in the display. Press YES to 
enter the anti-short cycle timer menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum on/off times for the heating and cooling 
stages. Press YES to store the value. 

The display now shows the heating cycles per hour 
setup prompt. See 

Setting the Heating Cycles per 

Hour (Heat cph)

 section for instructions. 

Setting the Maximum Heating Cycles per Hour 
(Heat cph) 

The heating cycles per hour establishes the number of 
times the equipment or stages are turned on and off in 
one hour. The selection ranges from three to eight 
cycles per hour. 

Note: 

A higher number of heating cycles per hour 

results in more accurate temperature control, but could 
accelerate the wear of mechanical components in the 
equipment. 

To set the maximum number of heating cycles per 
hour while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating cycles 

per hour prompt appears in the display. Press 
YES to enter the heating cycles per hour menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum number of heating cycles per hour. 
Press YES to store the value. 

The display now shows the cooling cycles per hour 
setup prompt. See 

Setting the Cooling Cycles per 

Hour (Cool cph)

 section for instructions. 

Setting the Maximum Cooling Cycles per Hour 
(Cool cph) 

The cooling cycles per hour establishes the number of 
times the equipment or stages are turned on and off in 
one hour. The selection ranges from three to four 
cycles per hour. 

Note: 

A higher number of cooling cycles per hour 

results in more accurate temperature control, but could 
accelerate the wear of mechanical components in the 
equipment. 

To set the maximum number of cooling cycles per 
hour while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling cycles 

per hour prompt appears in the display. Press 
YES to enter the cooling cycles per hour menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum number of cooling cycles per hour. 
Press YES to store the value. 

8    

T600MEP-2 Programmable Economizer Thermostat Installation Instructions 

Содержание T600MEP-2

Страница 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Страница 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Страница 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Страница 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Страница 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Страница 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Страница 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Страница 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Страница 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Страница 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Страница 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Страница 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Страница 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Страница 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Страница 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Страница 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Страница 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Страница 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...

Отзывы: