Table 1: Installer Configuration Menu (Cont.) 

 

Sets the Duration for Temporary 
Occupancy Time 
Default: Three Hours 

(3.0 hrs)

 

See the 

Establishing the Temporary 

Occupancy Time (TOccTime) 

section. 

 

Room Air Sensor Calibration (Offset) 
Default: 

0.0

°

F (0.0

°

C) 

See the 

Room Air Sensor Calibration 

(Cal RS) 

section. 

 

Outdoor Air Sensor Calibration (Offset)
Default: 

0.0

°

F (0.0

°

C) 

See the 

Outdoor Air Sensor 

Calibration (Cal OS) 

section. 

 

Enable/Disable Second Heating Stage
Default: 

Two Stages

 

See the 

Enable/Disable Second 

Heating Stage (H Stage) 

section.

 

 

Enable/Disable Second Cooling Stage
Default: 

Two Stages

 

See the 

Enable/Disable Second 

Cooling Stage (C Stage) 

section. 

 

Disables Heating Operation based on 
Outdoor Air Temperature 
Default: 

120

°

F (49

°

C) 

See the 

Setting the Heating Lockout 

(H lock) 

section. 

 

Disables Cooling Operation based on 
Outdoor Air Temperature 
Default: 

-40

°

F (-40

°

C) 

See the 

Setting the Cooling Lockout 

(C lock) 

section. 

 

Sets the Number of Events in 24-Hour 
Period 
Default: Two Events 

(2.0) 

See the 

Selecting the Number of 

Events (2/4event) 

section. 

 

Sets the Auxiliary Contact as Normally 
Open or Normally Closed 
Default: Normally Open 

(N.O.) 

See the 

Configuring the Auxiliary 

Contact (Aux cont) 

section. 

 

Enable/Disable Progressive Recovery 
Default: 

Off 

See the 

Enable/Disable Progressive 

Recovery (Prog Rec) 

section. 

 

Sets the Economizer Changeover 
Temperature 
Default: 

55

°

F (13

°

C)

 

See the 

Setting the Economizer 

Changeover Temperature (Chngstpt) 

section. 

 

Sets the Outdoor Air Damper Minimum 
Position 
Default: 

0%

 

See the 

Setting the Outdoor Air 

Damper Minimum Position (Min pos). 

section. 

 

Sets the Mechanical Cooling Mode 
Default: 

Off

 

See the 

Setting the Mechanical 

Cooling Mode (C mech) 

section. 

 

Sets the Mixed Air Temperature 
Setpoint 
Default: 

55

°

F (13

°

C)

 

See the 

Setting the Mixed Air 

Temperature Setpoint (Mix stpt) 

section. 

 

Displays the Mixed Air Temperature 
Default: 

None

 

See the 

Displaying the Mixed Air 

Temperature (Display) 

section. 

Min pos
set? Y/N 

TOccTime 
set? Y/N 

C mech
set? Y/N 

Cal RS 
set? Y/N 

Mix stpt
set? Y/N 

Cal OS 
set? Y/N 

Display
MS? Y/N 

H Stage 
set? Y/N 

 

C Stage 
set? Y/N 

Configuring the Digital Inputs (DI1 and DI2) 

Press the configuration menu access key. The first 
prompt is to program Digital Inputs DI1 and DI2. 

The digital inputs display an alarm condition when the 
input is closed. An alarm message is included on the 
scrolling Status Display Menu and when the message 
is displayed, the backlight momentarily lights up. 

H lock 
set? Y/N 

Each digital input can be programmed in one of five 
conditions. 

C lock 
set? Y/N 

• 

None

 – No function is associated with the input. 

• 

Service

 – A Service alarm is displayed. 

• 

Filter

 – A Filter alarm is displayed. 

2/4event 
set? Y/N 

• 

RemNSB

 – Remote Night Setback (NSB) timer 

clock input. The scheduling is set per the digital 
input when this option is selected. The time 
continues to be displayed, but the menu related to 
scheduling is disabled and no longer accessible. 

Aux cont 
set? Y/N 

− 

Open Contact = Occupied setpoints 

− 

Closed Contacts = Unoccupied setpoints 

• 

RemOVR

 – Remote override contact. This 

disables all override menu functions of the 
thermostat. The override function is controlled 
manually by a remote, momentarily closed 
contact. When configured in this mode, the input 
operates in a toggle mode. With this function 
enabled, it is now possible to toggle between 
unoccupied and occupied setpoints for the amount 
of time set by the temporary occupancy time 
parameter. 

Prog Rec 
set? Y/N 

Chngstpt 
set? Y/N 

6    

T600MEP-2 Programmable Economizer Thermostat Installation Instructions 

Содержание T600MEP-2

Страница 1: ...ver using a Phillips head screwdriver Open the thermostat by pulling on the bottom side of the thermostat cover Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs t...

Страница 2: ...einsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire...

Страница 3: ...common from equipment transformer 24 VAC for heating stages Energizes on a call for first stage heating Energizes on a call for second stage heating Configurable auxiliary output Configurable digital...

Страница 4: ...keys to adjust values activate a Temporary Setpoint Backlit Liquid Crystal Display LCD The T600MEP 2 uses a two line eight character display Low level backlighting is present during normal operation a...

Страница 5: ...nputs DI1 and DI2 section Configures Digital Input 2 Default No Function None See the Configuring the Digital Inputs DI1 and DI2 section Sets Keypad Lockout Level Default No Lockout 0 See the Enabling...

Страница 6: ...oling Mode C mech section Sets the Mixed Air Temperature Setpoint Default 55 F 13 C See the Setting the Mixed Air Temperature Setpoint Mix stpt section Displays the Mixed Air Temperature Default None...

Страница 7: ...ay before any operation is authorized fan cooling and heating The delay time is adjustable between 10 and 120 seconds This parameter can also be used to sequence the start up of multiple units in one...

Страница 8: ...uration Menu 1 Answer NO to all prompts until the anti short cycle timer prompt appears in the display Press YES to enter the anti short cycle timer menu 2 Use the UP DOWN arrow keys to adjust the min...

Страница 9: ...er NO to all prompts until the fan delay prompt appears in the display Press YES to enter the fan delay menu 2 Using the UP DOWN arrow keys select on or off Press YES to store the selection The displa...

Страница 10: ...temperature is above the heating lockout temperature heating operation is disabled The heating lockout temperature parameter is adjustable from 15 to 120 F 26 to 49 C in increments of 5 F C To change...

Страница 11: ...to select on or off Press YES to store the selection The display now shows the economizer changeover setpoint menu See Setting the Economizer Changeover Temperature Chngstpt section for instructions S...

Страница 12: ...YES to store the temperature The display mixed air temperature prompt is now displayed See Displaying the Mixed Air Temperature Display section for instructions Displaying the Mixed Air Temperature Di...

Страница 13: ...User Menu Override schd Y N 1 Answer NO to all prompts until the Override Schedule prompt appears If the Thermostat is in the unoccupied state this is the first prompt 2 Press YES to enable the occupi...

Страница 14: ...current mode of operation Temperat set Y N Note Whether the thermostat is heating or cooling the respective setpoint is temporarily adjusted Cooling set Y N Note To toggle between the temporary heatin...

Страница 15: ...the time press the UP DOWN arrow keys to change the time in 1 minute increments Hold the keys down to change the time in 30 minute increments Note Programming one of the digital inputs to remote NSB d...

Страница 16: ...uling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday selecting NO leaves the thermostat in th...

Страница 17: ...the UP DOWN arrow keys to adjust the day When the correct day is displayed press YES to store the day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP...

Страница 18: ...t Operating Conditions 32 to 122 F 0 to 50 C 0 to 95 RH noncondensing Ambient Storage Conditions 22 to 122 F 30 to 50 C 0 to 95 RH noncondensing Dimensions H x W x D 4 94 x 3 38 x 1 13 in 125 x 86 x 2...

Отзывы: