Operating manual - SAB 120-151 A-frame (including ATEX)
56/61
008668 en 2019.08
*
Optional
Note:
Always keep approximately 25% extra oil available to refill at first start-up.
8.6
Charging compressor with lubricating oil
Caution!
Only charge oil when the unit pressure is below 6 bar!
Oil charging is carried out by means of a portable oil charging pump, see Fig. 21. Proceed as
follows:
1.
Connect the high-pressure hose, pos. 7, to the service valve, pos. 106, on the unit via the
non-return valve, pos. 12. Use the correct reduction nipple. See Fig. 22.
2.
Place the free end of the suction hose from the pump, pos. 1, together with the by-pass
hose, pos. 2, in the barrel.
3.
Open the ball valve, pos. 9, and service valve, pos. 106, and start the pump, pos. 5.
4.
Circulate the oil until the system is free from air bubbles. Close the ball valve, pos. 9. The
oil will now be charged to the unit.
5.
When the desired amount of oil has been charged to the unit, stop the pump and close the
service valve, pos. 106.
6.
Open the ball valve, pos. 9, carefully to equalise the pressure. The hoses can now be
dismantled.
7.
Loosen the non-return valve carefully to equalise the remaining pressure. Remember to
mount the cap nut on the charge valve and to seal the oil barrel if there is any oil left.
Fig. 21: Oil charging
Length: 460 mm
Height: 350 mm
Width: 340 mm
Weight: 22 kg
Part number: 4541.001
3/8”RG
1/4”RG
1/2”RG
7/8”RG
RG= Pipethread
20
7
9
5
1
2
12
Содержание SABROE SAB 120 E
Страница 1: ...SAB 120 151 A frame including ATEX Screw compressor units Operating manual en ...