Operating manual - SAB 120-151 A-frame (including ATEX)
008668 en 2019.08
53/61
SABROE
designation
Compressor
model
Discharge flange to
separator flange
Suction flange
Bolt size
Torque
(Nm)
Bolt size
Torque
(Nm)
SAB 120
XJF 120
M20
203
M22
390
SAB 151
XJF 151
M22
226
M24
500
Table 14: Torque requirements
Note:
Based on:
a.
Gaskets-Garlock® Blue-Gard® 3300 or Klingersil C-4430
b.
Bolts-class 8.8 or stronger hex head bolts, lightly oiled and clean.
8.3
Monitoring of operation
To ensure satisfactory operation, it is required that you enter certain routines in a logbook on a
regular basis. You can use the items listed in the
Start-up log
, which is page 2 of the
Checklist
il-
lustrated in Fig. 20. The service engineer will need this information in connection with, for exam-
ple, error reports.
In addition to the items listed in the start-up log, all other activities of service, maintenance or re-
pair work must be entered into your logbook as required by EN 378 and national laws.
Checklist
Along with this Operating manual we have provided a
Checklist
, as shown in Fig. 20, which will
serve as a help to the service engineer and
must be filled in during commissioning and
start-up
.
Keep the filled-in checklist, and send a copy to SABROE Factory as documentation that the unit
has been installed and commissioned correctly. The checklist will be required in case of a warranty
issue.