Operating manual - SAB 120-151 A-frame (including ATEX)
008668 en 2019.08
25/61
4.8
Sound measurement and noise data
4.8.1
Noise data
Noise data is stated in:
SWL
: A-weighted
s
ound po
w
er
l
evel
SPL
: A-weighted
s
ound
p
ressure
l
evel, in free field over reflecting plane (1 m distance).
•
Noise data is based on measurements according to ISO 9614-2.
•
The stated SPL values are calculated using the formula 8.3 in ISO 3744.
•
The stated values are for a complete unit operating in 100% capacity.
4.8.2
Noise data for SAB 120-151
Evaporating temperature, TE
-15°C
Condensing temperature, TC
+35°C
Refrigerant
R717/HCFC/HFC
Speed
2950 rpm
For 60 Hz-driven compressors, add +2 dBA to the stated levels.
Type of unit
SWL
SPL
SAB 120 S
100
83
SAB 120 M
101
84
SAB 120 L
103
86
SAB 120 E
104
87
SAB 151 S
106
88
SAB 151 M
107
89
SAB 151 L
107
89
SAB 151 E
108
90
Table 5
Noise data for other operating conditions can be provided by Johnson Controls Denmark on
request.
Note:
•
The actual SPL value on site will be between the stated SPL and SWL depending on the
acoustic environment in the machine room.
•
In a typical machine room without any noise absorbing materials, the actual SPL will be
approximately 14 dBA higher than the stated SPL (free field value).
•
Checking the actual SPL must therefore always be accompanied by measurements of the
acoustic environment of the machine room. Alternatively, ISO 9614-2 could be followed
at the installation site to obtain SWL comparable values.
•
Be aware of local/national requirements for the use of ear protection. Generally, it is rec-
ommended to use ear protection in machine rooms.