Figure 13: Door magnet and reed switch
Installing and commissioning the door sensors
1. To power on the sensor, swipe it once from top to bottom with a magnet. See
for more information. The following light sequence indicates connection to the
network:
- Sensor light turns blue
- Sensor light flashes green approximately 4 times
- Sensor light turns off
2. On the Android device, in the upper-right of the PENN Commissioner app, tap
+
.
3. Commission a sensor in one of the following ways:
- Tap
SCAN
to open the camera. Scan the QR code or the barcode on the side of the sensor.
- In the
Or Enter Device MAC Address
field, enter the unique 16-digit serial number found on
the side of the sensor.
4. Follow the remaining on-screen instructions and enter the required data for each sensor.
5. Mount the sensor with or without a bracket near the chiller or freezer room door. Secure the
sensor with screws, tie-wraps, or double-sided tape.
Note:
Install another repeater nearby if the door sensor is more than 25 m from the
gateway.
6. Attach the magnet and reed strip to the frame of the chiller or freezer room door with a
maximum gap of 20 mm.
7. Attach a sticker to a visible location on the refrigeration unit.
PENN Connected PC10 Install and Commissioning Guide
16