Installing the repeaters
1. Identify appropriate locations for the repeaters, and install them at a height that prevents
interference from staff and customers.
2. Mount the repeaters with or without brackets. Secure the repeaters with screws, tie-wraps, or
double-sided tape.
3. Connect the repeaters to a power supply; the repeaters flash blue on connection.
Overview of temperature sensors
The internal and external temperature sensors monitor the temperature of a unit of refrigeration
equipment. The maximum range of each temperature sensor is 25 m.
Install the E10 internal temperature sensors and the E11 external temperature sensors in a secure
location inside a refrigeration cabinet. For the E11 temperature sensors, feed the probe through an
appropriate location in the cabinet and use a p clip to secure the bulb in place.
Each temperature sensor ships with a set of stickers that display a serial code. The serial code
on the stickers matches the serial code on the side of the sensor. Attach these stickers to the
refrigeration units to track and trace the temperature sensors.
Note:
• The sensors can record temperatures from -40° to 95° in refrigerated or hot hold cabinets.
Replace the negative temperature coefficient (NTC) external probe to suit the application.
See the following figures for examples of typical sensor placement.
Figure 6: Typical view of well and wall cabinets
11
PENN Connected PC10 Install and Commissioning Guide