User Manual: NEO System
22
Rev.0.3
XB
XA Speakers line A of amplification
channel X.
XB Speakers line B of amplification
channel X.
Table 14 - Speaker Line Outputs
2.4.7 Inputs Outputs of Audio Sources
a)
Record Output
The equipment has a line level balanced audio output, which includes
a switching signal active at low level (TTL). It allows monitoring and
recording of messages sent from the emergency microphone. When
a warning is issued by live voice (microphone), to one or more voice
evacuation zones, the recording output will be activated, reproducing
the emission signal at the zone or voice evacuation zones. In that
case, the output operation is activated at a low level.
The connection is made by euroblock female connector and 4-pin 3.81 mm pitch (supplied
with the unit). The wire size range for each pole of this connector is: 0.14
→
1.5 mm2 (30
→
14 AWG).
Marking
Descrition
Type
Signals
Activation
REC
OUT
Balanced Audio at line level
Ouput
┴
+
-
Message from emergency microphone broadcasted by any zone
through voice evacuation
REC
OUT
Recording output activation
Ouput
┴
M
0V DC
Table 15 - REC Output
b)
Priority Input (PRIO Input)
NEO-Extension models have a PRIO Input instead of a REC Output. The priority input for
PA mode is activated through a contact closure in pin “M”, when active. The PA LED light
will blink. The audio of this input will be routed to every output while the activation signal is
active, unless the system enters into Emergency mode, in which case, the emergency
inputs will have priority and the routing will be assigned according to the evacuation.
c)
Paging Microphones and System Devices Input
The NEO 8060 has a special input for microphones where MPS-8Z and
VAP-1 units are connected. It is an input that combines line-level audio
control signals and power supply for up to 8 devices in bus mode. This line
uses input number 5 of the available audio inputs, therefore when it is
being used, input number 5 will be occupied. For more information about
the connection of this input, see chapter 4.2.
The connection is made via Ethernet cable, T568B standard. Maximum
connection distance for the entire bus is 1000m (914.4 yrd).
Marking
Description
Types
Signals
Activation
MIC/
REMOTE
Balanced Audio at line level
Input
Protocol
NA
Figure 25 - REC
Output
Figure 26 - ACSI
Bus Input