Wiring Considerations and Guidelines for Network Integrations

Table 2: NAE-S Ethernet Network Rules

Category

Rules/Maximums Allowed

General

Star topology with network hubs/switches

Number of Devices

Maximum of 1000 devices can be connected to one site in the 

Metasys

 network.

2,000 m (6,600 ft) for plastic/glass fiber optic with external adapter

Line Length and Type

10/100 BaseT: 100 m (330 ft) Cat5/Cat6 cable
1000 BaseT: 100 m (330 ft) Cat5e/Cat6 cable

Terminations

No line terminators allowed.

Table 3: Guidelines for BACnet Protocol MS/TP Network Topology

Category

Rules/Maximums Allowed

General

NAE-S models support up to two MS/TP Bus trunks, daisy chain topology only.

Number of Devices

100

1

1

 devices per FC Bus with no more than two repeaters between NAE-S and any device and

a maximum of 50 devices between repeaters
1,500 m (5,000 ft)

1

 cable without a repeater

4,500 m (15,000 ft) cable from NAE-S to the farthest FC Bus device (three bus segments of

1,500 m [5,000 ft] each, separated by repeaters)

Line Length and Type

2

2

2,000 m (6,600 ft) between two fiber modems

Cable Type

Stranded 0.6 mm (22 AWG) 3-wire twisted, shielded cable is recommended.
Stranded 0.6 mm (22 AWG) shielded 4-wire (two twisted-pairs) shielded cable is acceptable.

Note: 

The + and - bus leads should be a twisted pair. On applications using 4-wire

(two twisted-pairs) cable, isolate and insulate unused conductor. Refer to the 

MS/TP

Communications Bus Technical Bulletin (LIT-12011034)

 for more information.

Terminations

Two FC devices with EOL switches in the ON position, one at each end of each FC Bus

segment

1

If TEC Thermostat Controllers or third-party devices are used on the FC Bus, the maximum total number of devices is 64 and the

maximum length is 1,219 m (4,000 ft).

2

Refer to the 

MS/TP Communications Bus Terminal Bulletin (LIT-12011034) 

for information on cable types and lengths.

Table 4: Guidelines for N2 network topology

Category

Rules and Maximums

NAE-S models support up to two N2 Bus trunks.

General

Only daisy-chained devices (with maximum stub length of 3 m [10 ft] to any device)

Number of Devices NAE-S models support up to 100 N2 devices per N2 Bus, with no more than two repeaters between

NAE-S and any N2 device and a maximum of 50 devices between repeaters.
1,500 m (5,000 ft) twisted pair cable without a repeater
4,500 m (15,000 ft) twisted pair cable from NAE-S and the farthest N2 device (three segments of

1,500 m [5,000 ft] each, separated by repeaters)

Line Length and

Type

2,000 m (6,600 ft) between two fiber modems

Cable

Solid or stranded 1.0 mm (18 AWG) 3-wire is recommended
Solid or stranded 0.5 mm (24 AWG) larger 3-wire or 4-wire (two twisted-pairs) is acceptable

Note: 

Use only twisted pair wire. On applications using 4-wire (two twisted-pairs) cable,

isolate and insulate unused conductor.

NAE-S Installation Guide

5

Содержание NAE-S

Страница 1: ...hysical Features Figure 2 NAE S Physical Features Table 1 Secure Network Engine physical features Callout Description 1 24 VDC power terminal for encryption board 2 RS 232 serial ports hidden under cover 3 Field controller buses FC Bus or N2 Bus terminal with end of line switches 4 24 VAC power terminal 5 Wall mount feet 6 Security screw one of two 7 System status LEDs with system reboot switch 8 ...

Страница 2: ...s free of corrosive vapors and observe the environmental limitations listed in the section Do not mount the NAE S on surfaces that are prone to vibration such as duct work or in areas where electromagnetic emissions from other devices or wiring can interfere with network engine communication Allow sufficient space for running cable and wire making terminal connections and accessing battery compart...

Страница 3: ...ly requires 120 VAC power to provide a 24 VDC output that plugs directly into a port on the front of the NAE S FC Bus Terminal Block The two FCs Bus connections on the NAE S models are removable keyed terminal blocks labeled FC A and FC B The FC bus connections are optically isolated RS 485 ports with keyed 4 position terminal blocks that communicate at 9600 19 200 38 400 or 76 800 baud Use an FC ...

Страница 4: ...ns and Guidelines for Network Integrations section To wire the network engine follow these steps 1 Connect the Ethernet cable to the RJ 45 8 pin Ethernet port Figure 2 2 Connect the Building Automation System BAS network cables to the appropriate ports For N2 or MS TP networks connect the 3 wire bus cable to one of the removable 4 terminal plugs labeled FC A or FC B Figure 6 Note If an N2 Bus or M...

Страница 5: ...ns using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Terminations Two FC devices with EOL switches in the ON position one at each end of each FC Bus segment 1 If TEC Thermostat Controllers or third party devices are used on the FC Bus the maximum total number of devices is 64 and the...

Страница 6: ...charging period Figure 8 NAE S Data Protection Battery Setting the End of the Line Switches The network devices at each end of an FC Bus segment must be set as network terminated devices The network engine has two EOL switches one for each FC Bus that enable you to set the NAE S as a network terminated device on the bus To set the network engine as an FC Bus terminated device position the switch o...

Страница 7: ...hting sequence occurs 1 The network engine emits one short beep indicating that the BIOS startup was successful 2 The PEER COM RUN and GENL FAULT LEDs turn on indicating that the OS is booting up The FC A and FC B LEDs also turn on 3 The PEER COM RUN FC A FC B and GENL FAULT LEDs shut off The RUN LED flashes to indicate that the network engine software is loading 4 When the RUN LED goes On Steady ...

Страница 8: ...tware is not running 24 VAC Green On Steady On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the network engine can be running on battery power Also see the POWER LED BATT FAULT Red Off Steady On Steady Battery fault Replace the battery Battery is not connected or cannot be charged The BATT FAULT LED may remain On for up to 24 hours after initially powe...

Страница 9: ...ss 2 power supply North America at 50 60 Hz 20 VAC minimum to 30 VAC maximum DeltaPSU Power Supply for Internal Module with Embedded Encryption Technology Input Dedicated nominal 100 240 VAC Class 1 power supply North America at 50 60 Hz 85 VAC minimum to 264 VAC maximum Output 24 VDC 22 VDC minimum to 26 VDC maximum Power Consumption 50 VA maximum Power Specifications for Encryption Board Dedicat...

Страница 10: ...ce United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in ...

Отзывы: