Ordering Information

Table 6: NAE-S Ordering Information

Product Code Number

Description

MS-NAE551S-2

Includes one RS-232C serial port, two RS-485 ports (FC-A and FC-B), one Ethernet port,

and one MS-BAT1010-0 Data Protection Battery. Supports two N2 or two BACnet MS/

TP (RS-485) trunks (or one N2 trunk and one BACnet MS/TP trunk). Supports up to 100

devices on each trunk. Requires a 24 VAC power supply.

MS-NAE551S-702

Replacement for a non-functional NAE551S-2.

Table 7: Accessories Ordering Information

Product Code Number

Description

MS-NAESCBL-0

Commissioning cable and non-metallic reset probe.

PAN-PWRSP

96 VA 120/24 VAC Power Assembly (Transformer, receptacle, 5 A, overcurrent circuit

breaker)

DRP-24V48W1AZ (Rev04)

CliQ DIN Rail 24 VDC Power Supply with connecting cable, manufactured by DeltaPSU,

power supply unit of Delta

®

 Electronics Group

MS-BAT1010-0

Replacement data protection battery for NAE-S. Rechargeable gel cell battery with a

typical life of 3 to 5 years at 70°F (21°C).

Technical Specifications

Table 8: NAE551S-2 Technical Specifications

Product Code Number

MS-NAE551S-2

Note: 

The NAE-S comes from the factory with 

Metasys

 Release 8.0 firmware, but you

may field-upgrade the engine to Release 10.1.

Power Requirements

MS-NAE551S-2 Engine:

Dedicated nominal 24 VAC, Class 2 power supply (North America) at 50/60 Hz (20 VAC

minimum to 30 VAC maximum)

DeltaPSU Power Supply for Internal Module with Embedded Encryption Technology:

Input: Dedicated nominal 100–240 VAC, Class 1 power supply (North America), at 50/60

Hz (85 VAC minimum to 264 VAC maximum)
Output: 24 VDC (22 VDC minimum to 26 VDC maximum)

Power Consumption

50 VA maximum

Power Specifications for

Encryption Board

Dedicated nominal 24 VDC, input voltage range 85–264 VAC (120–375 VDC), output

current 2.0A

Ambient Operating

Conditions

32 to 122°F (0 to 50°C); 10 to 90% RH, 86°F (30°C) maximum dew point

Ambient Storage Conditions -40 to 158°F (-40 to 70°C); 5 to 95% RH, 86°F (30°C) maximum dew point

Data Protection Battery

Supports data protection on power failure. Rechargeable gel cell battery: 12 V, 1.2 Ah,

with a typical life of 3 to 5 years at 70°F (21°C); Product Code Number: MS-BAT1010-0

Clock Battery

Maintains real-time clock through a power failure. Onboard cell; typical life 10 years at

70°F (21°C)

Processor

1.6 GHz Intel

®

 Atom

®

 processor

Memory

4 GB flash nonvolatile memory for operating system, configuration data, and operations

data storage and backup
1 GB SDRAM for operations data dynamic memory for all models

Network and Serial

Interfaces

One Ethernet port; 10/100/1000 Mbps; 8-pin RJ-45 connector (Use Cat5 or Cat6 cable)
Two optically isolated RS-485 ports; 9600, 19.2k, 38.4k, or 76.8k baud; pluggable and

keyed 4 position terminal blocks (RS-485 terminal blocks available)

NAE-S Installation Guide

9

Содержание NAE-S

Страница 1: ...hysical Features Figure 2 NAE S Physical Features Table 1 Secure Network Engine physical features Callout Description 1 24 VDC power terminal for encryption board 2 RS 232 serial ports hidden under cover 3 Field controller buses FC Bus or N2 Bus terminal with end of line switches 4 24 VAC power terminal 5 Wall mount feet 6 Security screw one of two 7 System status LEDs with system reboot switch 8 ...

Страница 2: ...s free of corrosive vapors and observe the environmental limitations listed in the section Do not mount the NAE S on surfaces that are prone to vibration such as duct work or in areas where electromagnetic emissions from other devices or wiring can interfere with network engine communication Allow sufficient space for running cable and wire making terminal connections and accessing battery compart...

Страница 3: ...ly requires 120 VAC power to provide a 24 VDC output that plugs directly into a port on the front of the NAE S FC Bus Terminal Block The two FCs Bus connections on the NAE S models are removable keyed terminal blocks labeled FC A and FC B The FC bus connections are optically isolated RS 485 ports with keyed 4 position terminal blocks that communicate at 9600 19 200 38 400 or 76 800 baud Use an FC ...

Страница 4: ...ns and Guidelines for Network Integrations section To wire the network engine follow these steps 1 Connect the Ethernet cable to the RJ 45 8 pin Ethernet port Figure 2 2 Connect the Building Automation System BAS network cables to the appropriate ports For N2 or MS TP networks connect the 3 wire bus cable to one of the removable 4 terminal plugs labeled FC A or FC B Figure 6 Note If an N2 Bus or M...

Страница 5: ...ns using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Terminations Two FC devices with EOL switches in the ON position one at each end of each FC Bus segment 1 If TEC Thermostat Controllers or third party devices are used on the FC Bus the maximum total number of devices is 64 and the...

Страница 6: ...charging period Figure 8 NAE S Data Protection Battery Setting the End of the Line Switches The network devices at each end of an FC Bus segment must be set as network terminated devices The network engine has two EOL switches one for each FC Bus that enable you to set the NAE S as a network terminated device on the bus To set the network engine as an FC Bus terminated device position the switch o...

Страница 7: ...hting sequence occurs 1 The network engine emits one short beep indicating that the BIOS startup was successful 2 The PEER COM RUN and GENL FAULT LEDs turn on indicating that the OS is booting up The FC A and FC B LEDs also turn on 3 The PEER COM RUN FC A FC B and GENL FAULT LEDs shut off The RUN LED flashes to indicate that the network engine software is loading 4 When the RUN LED goes On Steady ...

Страница 8: ...tware is not running 24 VAC Green On Steady On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the network engine can be running on battery power Also see the POWER LED BATT FAULT Red Off Steady On Steady Battery fault Replace the battery Battery is not connected or cannot be charged The BATT FAULT LED may remain On for up to 24 hours after initially powe...

Страница 9: ...ss 2 power supply North America at 50 60 Hz 20 VAC minimum to 30 VAC maximum DeltaPSU Power Supply for Internal Module with Embedded Encryption Technology Input Dedicated nominal 100 240 VAC Class 1 power supply North America at 50 60 Hz 85 VAC minimum to 264 VAC maximum Output 24 VDC 22 VDC minimum to 26 VDC maximum Power Consumption 50 VA maximum Power Specifications for Encryption Board Dedicat...

Страница 10: ...ce United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in ...

Отзывы: