background image

Table 4: Guidelines for N2 network topology

Category

Rules and Maximums

Terminations

Preferred Termination Configuration

: Two N2 devices with EOL switches in the ON position, one

at each end of each N2 Bus segment

Minimally Required Termination Configuration

: At least one N2 device with an EOL switch in

the ON position somewhere on each N2 Bus segment

Setup and Adjustments

Installing the Data Protection Battery

Important: 

Do not apply 24 VAC power to the

network engine before installing the data protection

battery.

To install the data protection battery for the NAE-S:

1.  Remove the battery from its packaging. Remove the

battery cover on the NAE-S to expose the battery

compartment (Figure 8).

2.  Carefully plug the NAE-S battery connector from

the battery compartment into the connector on the

battery cable (Figure 8).

3.  Place the battery into the compartment (Figure 8).
4.  Slide one end of the battery strap into the hole on

the opposite side of the strap (Figure 8), and loop the

strap tightly around the battery to minimize battery

movement.

5.  Replace the cover of the battery compartment.
6.  Apply 24 VAC power to the network engine.

Important: 

The data protection battery must

maintain a small residual charge. The battery ships

from the factory with a small residual charge. You

should connect 24 VAC power to the network engine

immediately after connecting the battery to ensure

that the battery does not completely lose its charge,

which may damage the battery.

Note: 

The 24 VAC power to the network engine

charges the data protection battery. At initial

startup, the battery requires a charging period of

at least 2 hours before it supports data protection

if power fails. Maximum protection (up to three

consecutive power failures without recharging time)

requires a 24-hour charging period.

Figure 8: NAE-S Data Protection Battery

Setting the End-of-the-Line Switches

The network devices at each end of an FC Bus segment

must be set as network terminated devices. The network

engine has two EOL switches (one for each FC Bus) that

enable you to set the NAE-S as a network terminated

device on the bus.
To set the network engine as an FC Bus terminated device,

position the switch on the EOL switch block to the ON

position (Figure 9).

Figure 9: FC Bus EOL Switch in the Factory Default ON

(Up) Position

Note: 

The NAE-S is shipped with the EOL switches

for both FC Buses in the initial factory position, ON

(Figure 9). If the NAE-S is not a terminated device on

the FC Bus, reposition the switch on the EOL switch

block to the Off (down) position.

Set the EOL switches appropriately for the FC A and FC B

buses. The NAE-S follows the same rules as other switch-

terminating devices listed in the 

Setting Terminations

sections of the 

N2 Communications Bus Technical Bulletin

(LIT-636018)

 and the 

MS/TP Communications Bus Technical

Bulletin (LIT-12011034)

.

Powering on the NAE-S

Before powering the NAE-S network engine, make sure

the cable from the encryption board power supply is

connected to the engine. After applying 24 VAC power, the

network engine requires approximately 3 minutes to start

up and become operational.
Startup is complete and the NAE-S is ready to be

configured when the (green) RUN LED is On steady and

the (red) GEN FAULT LED is Off. See 

LED Test Sequence at

Startup

 for LED locations.

Disconnecting Power from NAE-S

Important: 

The data protection battery must be

installed and charged before disconnecting the 24

VAC supply power.

The 24 VAC supply power is disconnected from the

network engine by removing the terminal block plug from

the power terminal port on the unit (Figure 2).
If the 24 VAC supply power to the network engine

is disconnected or lost, the network engine is

nonoperational. The POWER LED remains On, and the

NAE-S Installation Guide

6

Содержание NAE-S

Страница 1: ...hysical Features Figure 2 NAE S Physical Features Table 1 Secure Network Engine physical features Callout Description 1 24 VDC power terminal for encryption board 2 RS 232 serial ports hidden under cover 3 Field controller buses FC Bus or N2 Bus terminal with end of line switches 4 24 VAC power terminal 5 Wall mount feet 6 Security screw one of two 7 System status LEDs with system reboot switch 8 ...

Страница 2: ...s free of corrosive vapors and observe the environmental limitations listed in the section Do not mount the NAE S on surfaces that are prone to vibration such as duct work or in areas where electromagnetic emissions from other devices or wiring can interfere with network engine communication Allow sufficient space for running cable and wire making terminal connections and accessing battery compart...

Страница 3: ...ly requires 120 VAC power to provide a 24 VDC output that plugs directly into a port on the front of the NAE S FC Bus Terminal Block The two FCs Bus connections on the NAE S models are removable keyed terminal blocks labeled FC A and FC B The FC bus connections are optically isolated RS 485 ports with keyed 4 position terminal blocks that communicate at 9600 19 200 38 400 or 76 800 baud Use an FC ...

Страница 4: ...ns and Guidelines for Network Integrations section To wire the network engine follow these steps 1 Connect the Ethernet cable to the RJ 45 8 pin Ethernet port Figure 2 2 Connect the Building Automation System BAS network cables to the appropriate ports For N2 or MS TP networks connect the 3 wire bus cable to one of the removable 4 terminal plugs labeled FC A or FC B Figure 6 Note If an N2 Bus or M...

Страница 5: ...ns using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Terminations Two FC devices with EOL switches in the ON position one at each end of each FC Bus segment 1 If TEC Thermostat Controllers or third party devices are used on the FC Bus the maximum total number of devices is 64 and the...

Страница 6: ...charging period Figure 8 NAE S Data Protection Battery Setting the End of the Line Switches The network devices at each end of an FC Bus segment must be set as network terminated devices The network engine has two EOL switches one for each FC Bus that enable you to set the NAE S as a network terminated device on the bus To set the network engine as an FC Bus terminated device position the switch o...

Страница 7: ...hting sequence occurs 1 The network engine emits one short beep indicating that the BIOS startup was successful 2 The PEER COM RUN and GENL FAULT LEDs turn on indicating that the OS is booting up The FC A and FC B LEDs also turn on 3 The PEER COM RUN FC A FC B and GENL FAULT LEDs shut off The RUN LED flashes to indicate that the network engine software is loading 4 When the RUN LED goes On Steady ...

Страница 8: ...tware is not running 24 VAC Green On Steady On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the network engine can be running on battery power Also see the POWER LED BATT FAULT Red Off Steady On Steady Battery fault Replace the battery Battery is not connected or cannot be charged The BATT FAULT LED may remain On for up to 24 hours after initially powe...

Страница 9: ...ss 2 power supply North America at 50 60 Hz 20 VAC minimum to 30 VAC maximum DeltaPSU Power Supply for Internal Module with Embedded Encryption Technology Input Dedicated nominal 100 240 VAC Class 1 power supply North America at 50 60 Hz 85 VAC minimum to 264 VAC maximum Output 24 VDC 22 VDC minimum to 26 VDC maximum Power Consumption 50 VA maximum Power Specifications for Encryption Board Dedicat...

Страница 10: ...ce United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in ...

Отзывы: