MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin
5
Wiring
!
WARNING: Risk of Electric Shock.
To avoid electric shock or damage to equipment,
disconnect all power supplies before wiring any
connections. More than one disconnect may be
necessary to completely de-energize equipment.
Wiring Sensors and Binary Inputs
Wire the sensors and binary input (if used) as shown
in Figures 8-9. The Sensor (S1 or S2) and Sensor
Common (SC) wires are interchangeable when
using the A99B temperature sensors. The binary
input shares a common terminal with the sensors.
SC S1
S2
D
V1
V1
V2
V2
Internal to Control
Auxiliary
Temperature
Sensor
Binary
Input
(Switch)
Main
Temperature
Sensor
Sensor
Common
12VAC
O1
O1
O2
O2
Note: Black boxes indicate unused terminals.
B
L
K
W
H
T
R
E
D
G
R
N
Figure 8: Wiring the Control Module MS
Loosen screw to open terminal;
tighten screw to secure wiring.
Insert wiring here.
V1
V1
V2
V2
O1
O1
O2
O2
D
D
S2
S2
SC
SC
S1
S1
Note: Black boxes indicate unused terminals.
Figure 9: Rear View of the Control Module
Use
Temperature Sensor Offset
to compensate for
sensor leads longer than 300 ft (if
F is used) or
165 m (if
C is used). See Table 1 and
Temperature
Management
Functions: Temperature Sensor Offset
.
Table 1: Sensor Wire Size and Length
Wire Size and Length
Offset
18 AWG
20 AWG
22 AWG
300-599 ft
190-374 ft
120-239 ft
1 F
600-899 ft
375-564 ft
240-349 ft
2 F
900+ ft
565+ ft
350+ ft
3 F
165-329 m
105-204 m
65-129 m
1 C
330-495 m
205-310 m
130-195 m
2 C
Wiring the Relay Pack
!
WARNING: Risk of Electric Shock.
To avoid electric shock or damage to equipment,
disconnect all power supplies before wiring any
connections. More than one disconnect may be
necessary to completely de-energize equipment.
See Figure 10 for arrangement of terminals on the
terminal block in the relay pack. See Figures 11-12 for
sample wiring diagrams. Follow these wiring guidelines:
All wiring must conform to the National Electrical
Code and local regulations.
Use 14 AWG copper wire for motor loads up to 12 FLA
and non-inductive loads up to 15 A.
Use 12 AWG copper wire with an insulation rating of
75°C (minimum) for motor loads up to 16 FLA and
non-inductive loads up to 20 A.
Use wire no longer than 50 feet (15 m).
All circuits must have a common disconnect and be
connected to the same pole of the disconnect.
Relay
Pack
Terminal
Block
Terminal
Labels
on
Circuit
Board
NO1 CM1
L2
120
(Not
Used)
NO2 CM2
NO4
NC4
CM4
NC2
240
NC3
CM3
NC1
NO3
Figure 10: Relay Pack Terminal Block