16
MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack Product/Technical Bulletin
Table 6: SPDT Relay Electrical Ratings
Single-Phase Ratings
24 VAC
120 VAC
208 VAC
240 VAC
Horsepower Rating
—
1/3
3/4
1
AC Full Load Amperes
—
7.2
7.6
8
AC Locked Rotor Amperes
—
43.2
45.6
48
Non-Inductive Amperes
—
8
8
8
Pilot Duty (VA)
50
325
625
750
Technical Specifications
Product
MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack
Electrical Ratings
See Table 6.
Frequency
60 Hz
Power Requirements
120/240 VAC ±10%
Power Consumption
10 VA @ 120/240 VAC
Accuracy
±1.8F
(±1C
)
Sensor Input Range
-40 to 158
F (-40 to +70
C)
A99B Sensor Cable
6-1/2 ft (2 m)
Ambient Operating
Conditions
MS4PMUHVT-11C:
+14 to +140
F (-10 to +60
C); 0 to 95 % RH (noncondensing)
MS4PM12C-11C:
+14 to +140
F (-10 to +60
C); 0 to 95 % RH (noncondensing)
RP4MSUHV-1C:
-40 to +140
F (-10 to +60
C); 0 to 95 % RH (noncondensing)
Ambient Storage
Conditions
MS4PMUHVT-11C:
-22 to +176
F (-30 to +80
C); 0 to 95 % RH (noncondensing)
MS4PM12C-11C:
-22 to +176
F (-30 to +80
C); 0 to 95 % RH (noncondensing)
RP4MSUHV-1C:
-40 to +185
F (-40 to +85
C); 0 to 95 % RH (noncondensing)
Dimensions (H x W x D)
See Figures 3-5.
Agency Listings
UL Listed (US), File SA516, CCN SDFY
UL Listed (Canada), File SA516, CCN SDFY7
Emissions Compliance
FCC (US)
DOC (Canada)
Shipping Weight
See Table 5.
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/Penn Application Engineering at 1-800-275-5676. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423
Published in U.S.A.