  CAUTION: Risk of Property Damage. 

Do not plug or unplug an actuator into a DME 
controller with power applied. Making such a 
connection or disconnection may result in permanent 
damage to the controller or actuator. 

MISE EN GARDE : Risque de dégâts matériels. 

Ne pas connecter ou déconnecter un actionneur d'un 
contrôleur DME sous tension. Une telle connexion ou 
déconnexion risque d'endommager 
irrémédiablement le contrôleur ou l'actionneur. 

 

IMPORTANT: 

Make all wiring connections in 

accordance with the National Electrical Code and 
local regulations. Use proper Electrostatic Discharge 
(ESD) precautions during installation and servicing to 
avoid damaging the actuator’s electronic circuits.

 

The M9206-DNx actuator is supplied with a 
factory-wired 5-pin connector that connects to an 
AD-DME-100-0 Economizer Controller. To wire the 
auxiliary switch on the DNB, refer to Figure 7.

 

Auxiliary Switch

(Shown Factory Set)

White/Yellow
White/Gray
White/Blue

COM
NO
NC

(21)
(23)
(22)

 

Figure 7: Wiring Diagram for the M9206-DNB Model 

Auxiliary Switch (DNB Models) 

The M9206-DNB-3S model has a built-in auxiliary 
switch with a switch adjuster accessible on either face 
of the actuator. (See Figure 1 and Figure 2.) The 
factory setting is 20°. Refer to the 

Auxiliary Switch 

Rating 

in the 

Technical Specifications

 section. 

 

The switch point is continuously adjustable from 
0 to 90°. For the most accurate position of the switch, 
refer to Figure 9 and use the method in the following 
example. 

To change the trip point: 

1.  Position the actuator in the full spring return 

position. 

Note:

  The switch is factory set to trip when the 

actuator reaches the 20° position. 

2.  Turn the switch adjuster until it points to the 

desired switch trip point. 

3.  Connect the switch to an ohmmeter and apply 

power to the actuator through the economizer 
controller. Modify the settings so the actuator 
passes the point where the switch should trip. If 
the point is not in the proper position, turn the 
switch adjuster again to optimize the setting. 

60

4050

70

80

Switch

Adjuster

 

Figure 8: Switch Trip Point Setting  

Repairs and Replacement 

Do not make field repairs. For a replacement or an 
accessory, refer to the 

M9206-DNx Series Electric 

Spring Return Economizer Damper Actuators Product 
Bulletin (LIT-120111)

4    

M9206-DNx Series Electric Spring Return Economizer Damper Actuators Installation Instructions 

Содержание M9206-DN Series

Страница 1: ...supervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du damper actuator The M9206 DNx actuator is designed for use with the Johnson Controls AD DME100 0 Economizer Controller Parts Included The M9206 DNx actuator is included Special Tools Required 5 16 in 8 mm square socket or 3 8 i...

Страница 2: ...omizer applications only Install the actuators on a 1 2 in 13 mm round damper shaft using the M9000 159 anti rotation bracket If the shaft extends less than 3 2 in 80 mm refer to the Removable Coupler section Note The anti rotation bracket is part of the economizer installation but not included with an M9206 DNx actuator If the bracket is missing order one using product code number M9000 159 You m...

Страница 3: ... screw is midway between the 40 and 50 nodule guides 90 45 45 Note The minimum rotation range is 34 5 3 Snap the locking clip securely into the coupler groove to retain the coupler in the actuator Wiring WARNING Risk of Electric Shock Disconnect or isolate all power supplies before making electrical connections More than one disconnection or isolation may be required to completely de energize equi...

Страница 4: ...built in auxiliary switch with a switch adjuster accessible on either face of the actuator See Figure 1 and Figure 2 The factory setting is 20 Refer to the Auxiliary Switch Rating in the Technical Specifications section The switch point is continuously adjustable from 0 to 90 For the most accurate position of the switch refer to Figure 9 and use the method in the following example To change the tr...

Страница 5: ...econds maximum Cycles 60 000 full stroke cycles rated at 53 lb in 6 N m Audible Noise Rating 55 dBA nominal at 1 m Electrical Connection Actuator 17 in 0 43 m cable with 5 pin connector Auxiliary Switch 48 in 1 2 m cable with 18 AWG wire leads Mechanical Connection 1 2 in 13 0 mm diameter round shaft or a 3 8 in 10 mm square shaft Enclosure IP20 Ambient Conditions Operating 25 to 140 F 32 to 60 C ...

Отзывы: