8    M9200 Series Electric Spring Return Actuator Product/Technical Bulletin

C

alibration

Jumper Settings

Floating (AGA, AGC, AGD, and AGE) and on/off (BGA
and BGC) models do not have jumper settings.
Resistive (JGA and JGC) models are factory set for
direct acting with Jumper W1 in the DA position.

Proportional (HGA and HGC) models are factory set
with Jumper W1 in the DA position, Jumper W2 in the
0 to 10 VDC or 0 to 20 mA position, and Jumper W3
in the fixed position. (See Figure 13.)

Ze ro  P o ten tiom e ter

S p an  P o te ntio m e te r

A d ju stab le

Fixe d

Jum per W 3

Fa ctory S et

  Te rm in al B lo ck 2

Fe ed b ack

P o te ntiom e te r

(S e e  Fig u re  9.)

(C C W )  R A

(C W ) D A

Jum per W 1

Fa ctory S et

Jum per W 2

 

  1   2   3   4  5   6    

Fa ctory S et

Vo ltag e Inp ut

0 -10  V D C       2 -10  V D C

C u rren t  Inp ut

0 -20  m A         4 -20  m A  

Fe ed b ack  O up ut

0 -10  V D C       2 -10  V D C

(1 ) C o m m o n
(2 ) P o w er
(3 ) C a lib ra tio n O utp u t
(4 ) C u rren t Inp ut
(5 ) Vo ltag e Inp ut
(6 ) Fe ed b ack  O utpu t

D irect  A ctin g  (D A )

R e ve rse  A ctin g  (R A )

R o tatio n D ire ctio n

w ith  Incre asin g  S ig na l

Term ina l
B lock 1

Figure 13: Calibrating M9216 Proportional Models

Direction of Action

Drive direction is dependent on the position of Jumper
W1 and the spring return direction as shown in Table
2. To change the spring return direction, see the

Spring Return Direction

 section.

Table 2: Settings for Direction of Action

Location of

Jumper W1/

Direction of

Spring
Return

Drive

Direction with

a Minimum

Input Signal

Drive

Direction with

a Maximum

Input Signal

DA/CCW

CCW

CW

RA/CCW

CW

CCW

DA/CW

CW

CCW

RA/CW

CCW

CW

To set an actuator for reverse acting, proceed as
follows for the appropriate model:

Proportional (HGA and HGC) and Resistive
(JGA and JGC) Models

1.  Move Jumper W1 from the factory set DA position

to the RA position. (See Figure 14.)

2.  Apply power and then a control signal to the

actuator to verify proper operation. (See Table 2.)

Note:

HGA and HGC models may require
potentiometer settings. Proceed to the

Potentiometer Settings

 section.

Floating (AGA, AGC, AGD, and AGE) Models

For floating models, reverse the control wiring
connections from Terminals 3 and 4 to Terminals 4
and 3. (See Figure 9, 

Terminal Block 1

.)

On/Off (BGA and BGC) Models

RA is selected by changing the actuator coupler for
on/off operation. (See the 

Spring Return Direction

section.)

Содержание M9200 Series

Страница 1: ... 2 to 10 VDC signal Figure 1 M9200 Series Spring Return Actuator Features and Benefits Bi directional Fail safe Spring Return Allows selectable rotation spring return direction simplifying installation Four Control Input Types Meets the needs of most applications Wide Range Resistive Input Interfaces to 3 wire resistive controllers from 100 to 10 000 ohms Zero and Span Adjustment on Proportional M...

Страница 2: ...ler to add safety devices or alarm systems that protect against and or warn of control failure M9200 actuators operate on 24 VAC at 50 60 Hz or 24 VDC They use a DC motor with stall detection circuitry that operates throughout the entire stroke The proportional and resistive actuators employ noise filtering techniques on the control signal to eliminate response to spurious noise Rotation is mechan...

Страница 3: ...or the Locking Clip Smooth Half of Sleeve Locking Clip Limit Stop Position Indicator Splines Tab Coupler Back of the Actuator Widest Gap in Sleeve Teeth Figure 3 Changing the Spring Return Direction 3 Insert the sleeve into the back of the actuator with the smooth half of the sleeve inserted first Note Make sure the widest gap in the sleeve teeth align with the two guide marks on the back of the a...

Страница 4: ...or slot to prevent actuator binding and premature wear 1 Refer to the A Dimensions in Table 1 and Figure 5 to ensure the anti rotation bracket tab fits midway in the actuator slot Table 1 Shaft Sizes and Distances from the Anti rotation Bracket to Shaft Center Shaft Diameter 5 8 in 1 2 in 3 8 in A Dimensions 8 1 4 in 8 5 16 in 8 3 8 in See Figure 5 209 mm 211 mm 213 mm 0 U bolt with Clamp Nuts 2 A...

Страница 5: ...ition and retighten the screws to a maximum of 30 lb in 3 4 N m Examples of rotation limiter adjustments For a range of 30 adjust both limiters fully up To set a rotation range of 45 adjust one rotation limiter to 30 and the other to 15 To set a range of 60 adjust one limiter to 30 and leave the other at 0 5 Reinsert the manual crank into the manual override gear 6 Repeat Steps 2 through 5 to set ...

Страница 6: ... 2 3 4 5 6 Resistive Input Control Models JGA and JGC 1 2 3 4 5 6 COM CCW CW On Off Control Models BGA and BGC CW 1 2 3 24 VAC 24 VDC 1 Common 2 Power 3 Calibration Out 4 Current Input 5 Voltage Input 6 Feedback Output 100 10k ohms 0 10V 24V Terminal Block 2 CW 0 100 11 12 13 Feedback Potentiometer Models AGD 0 135 ohms AGE 0 1000 ohms NC NO NO NC 21 22 23 24 25 26 Switch S1 10 Switch S2 80 Auxili...

Страница 7: ...ring diagrams in Figure 9 5 Replace the actuator cover and retighten the cover screw With the Conduit Adaptor M9000 100 included Refer to Figure 11 and proceed as follows 1 Push the plastic plug out of the conduit opening with fingertip 2 Slide the capture nut into the slot located inside of the conduit opening See Figure 11 Capture Nut Figure 11 Capture Nut 3 Insert the conduit adaptor into the c...

Страница 8: ...tional Models Direction of Action Drive direction is dependent on the position of Jumper W1 and the spring return direction as shown in Table 2 To change the spring return direction see the Spring Return Direction section Table 2 Settings for Direction of Action Location of Jumper W1 Direction of Spring Return Drive Direction with a Minimum Input Signal Drive Direction with a Maximum Input Signal ...

Страница 9: ...he calibration output 5 Use a 1 8 in 3 mm flat blade screwdriver to turn the zero potentiometer fully CW and the span potentiometer fully CCW 6 Apply the minimum zero point control signal required for positioning the actuator at the minimum position 7 Monitor DC calibration output To adjust the zero potentiometer turn it CCW until the voltmeter displays 0 volts or slightly less 0 1 volt 8 Adjust t...

Страница 10: ...ments Edge of Switch Cam S1 Edge of Switch Cam S2 0 CCW Figure 14 Switch Cam Angle Settings Note The normally closed contact closes and the normally open contact opens See Figure 9 Terminal Block 2 Auxiliary Switches Adjusting Switch Cam S2 To change the angle of Switch Cam S2 to 70 1 Push in and turn the manual crank CW Using the 0 to 90 nodule guides rotate the coupler until the position indicat...

Страница 11: ...trols CD 1300 direct mount applications DMPR KC254 Inside Frame Mounting Kit for Johnson Controls damper applications requiring the actuator within the airstream M9000 100 Conduit Adaptor Kit M9000 103 14 VA Transformer 120 24 VAC 60 Hz M9000 104 14 VA Transformer 230 24 VAC 60 Hz M9000 151 Base Mount Linkage Kit for remote inside duct floor mounting M9000 153 Crank Arm Kit for remote mounting M90...

Страница 12: ... Double Throw rated at 24 VAC 1 5A inductive 3A resistive 35 VA maximum per switch Spring Return Factory Setting CCW Direction is selectable with the coupler Mechanical Output Running torque 140 lb in 16 N m Rotation Range Adjustable from 30 to 90 mechanically limited to 93 Rotation Timing 70 to 130 seconds for 0 to 140 lb in 0 to 16 N m 90 seconds nominal at 50 rated load Powered rotation is fast...

Отзывы: