6 M9200 Series Electric Spring Return Actuator Product/Technical Bulletin
W
iring
!
CAUTION: Equipment Damage Hazard.
Disconnect all power supplies
before wiring connections are
made, or prior to performing
maintenance. Check all wiring
connections before applying
power to the system.
Short-circuited or improperly
connected wires will result in
permanent damage to the
equipment.
IMPORTANT:
Make all wiring connections in
accordance with the National
Electrical Code and local regulations.
Because of the actuator’s movement
during operation, wire strain reliefs
must be provided.
Refer to Figure 9 for the applicable M9200 actuator.
Te rm in al B loc k 1
2 4 VA C
2 4 V D C
C W C C W
C O M
Floating Con trol
M od els: A G A , A G C , A G D , an d A G E
O n/O ff C on trol
2 4 VA C
2 4 V D C
0 -20 m A
0 -10 V
0 -10 V
~
+
Pro portional C ontro l
M od els: H G A an d H G C
2 4V
+
+
+
+
1 2 3 4
1 2 3 4
1 2 3 4 5 6
^
-
~
+
R esistive Inp ut C o ntro l
M od els: JG A a nd JG C
+
+
^
-
1 2 3 4 5 6
C O M
^
-
C C W C W
+
O n/O ff C on trol
M od els: B G A an d B G C
C W *
1 2 3
*
2 4 VA C
2 4 V D C
^
-
~
+
~
+
~
+
1 = C om m on
2 = P ow e r
3 = C alibration O u t
4 = C urre nt In pu t
5 = Volta ge In pu t
6 = Fee d back O u tpu t
1 00 -10 k ohm s
0 -10 V
2 4V
~
+
^
-
Te rm in al B loc k 2
C W
0 %
1 00 %
11 1 2 1 3
Feed back
Po ten tiom eter
M od els: A G D = 0 -13 5 oh m s
A G E = 0 -10 00 o hm s
N C
N O
N O
N C
2 1 22 23 24 25 2 6
S w itch S 1
1 0°
S w itch S 2
8 0°
A uxiliary Sw itch es
(S h ow n F acto ry S et)
M od els: A G C , B G C ,
H G C , a nd JG C
N o te: Term ina ls 3 an d 4 fun ction as
C C W an d C W refe re nces w h en
th e R esistive m od els are in the
D A m o de , b u t a s C W a nd C C W
re feren ce s w he n the se m o de ls
are in the R A m od e.
* C W ro tatio n for the O n /O ff m ode ls w h en th e co up le r is
in se rte d in th e fron t o f the a ctua tor, b ut C C W rotation
w he n it is in serted in th e ba ck o f the a ctua tor.
~
+
^
-
C O M C W
C O M
Figure 9: Wiring for M9200 Models
IMPORTANT:
There is a 25-second delay before
the actuator (except the BGA and
BGC models) responds after power
is applied.
Do not switch 24 VAC from CW to
CCW (or CCW to CW) in less than
0.5 seconds.