Table 2: GS3000 Gas Detection Sensor Series setup menu
Specification
Requirements
Description
CO strobe trip
Only if you install the CO sensor
The factory default setting is 150 ppm. The
buzzer alarm trip point for CO may be set to
OFF or from 20 ppm to 500 ppm in 10 ppm
increments. The strobe may operate as a
CO alarm, a NO
2
alarm or both, depending
on the trip point settings. If set to OFF, the
strobe does not operate as a CO alarm.
CO strobe delay
Only if you enable the strobe, you install the
CO sensor, and the CO Strb Trip is not set to
OFF
The factory default setting is 5 min. The CO
strobe delay may be set from 0 min to 10
min in 1 min increments.
NO
2
strobe trip
Only if you enable the strobe and you install
the NO
2
sensor
The factory default setting is 2 ppm. The
strobe alarm trip point for NO
2
may be set
to OFF or from 1 ppm to 10 ppm in 1 ppm
increments. The strobe may operate as a
CO alarm, a NO
2
alarm or both, depending
on the trip point settings. If set to OFF, the
strobe does not operate as a NO
2
alarm.
NO
2
strobe delay
Only if you enable the strobe, you install the
NO
2
, and the NO
2
Strb Trip is not set to OFF
The factory default setting is 5 min. The NO
2
strobe delay may be set from 0 min to 10
min in 1 min increments.
Strobe test
Only if you enable the strobe
Use the
UP
or
DOWN
buttons to toggle the
strobe ON or OFF. Press the
MENU
button to
reset to OFF and advance.
Alarm 1
Only if you install two sensors
Press the
UP
or
DOWN
button to scroll
through the available options of CO or NO
2
.
Alarm 1 may be assigned to either sensor.
The default assignment is CO.
GS3000 Gas Detection Sensor Series Installation Guide
9