Table 2: GS3000 Gas Detection Sensor Series setup menu
Specification
Requirements
Description
CO Fault Mode timer
Only if you install the CO Sensor
The factory default setting is disable. Use
the
UP
or
DOWN
buttons to set the CO Fault
Mode timer to disable, 3, 4, 5, 6 years or
reset.
When disabled, the device does not sound
the buzzer or provide LCD and status
LED indication when the CO sensor life is
exceeded. When set to 3, 4, 5 or 6 years, the
fault alarm activates to indicate that the CO
sensor life is exceeded.
If set to reset and you press
MENU
, the
fault condition for the CO sensor clears, the
CO life-time timer resets, and the CO Fault
Mode remains at the previous setting. The
timer automatically resets if you replace the
CO sensor. If the required time has already
been exceeded, it cannot be selected.
NO
2
Fault Mode timer
Only if you install the NO
2
sensor
The factory default setting is disable. Use
the
UP
or
DOWN
buttons to set the NO
2
Fault Mode timer to disable, 1, 2, 3, 4 years
or reset.
When disabled, the device does not sound
the buzzer or provide LCD and status LED
indication when the NOsensor reaches end-
of-life. When set to 1, 2, 3. or 4 years, the
fault alarm activates to indicate that the NO
2
sensor life is exceeded. If set to reset and
you press the
MENU
, the fault condition for
the NO
2
sensor clears, the NO
2
lifetime timer
is reset and NO
2
Fault Mode remains at the
previous setting. The timer is automatically
reset if the NO
2
sensor is replaced. If the
required time has already been exceeded, it
cannot be selected.
CO recal mode
Only if you install the CO Sensor
The default setting is 1 year. Use the
UP
or
DOWN
buttons to set the CO recalibration
mode timer to disable, 1, 2, 3 years, or reset.
When disabled, the device does not sound
the buzzer or provide LCD and status LED
indication when the CO sensor requires
recalibration. When set to 1, 2, or 3 years,
the ReCal alarm activates to indicate that the
CO sensor requires recalibration.
If set to reset and you press
MENU
, the
ReCal condition for the CO sensor clears,
the CO ReCal timer resets and the CO ReCal
mode remains at the previous setting. The
timer automatically resets if you replace the
CO sensor. If the required time has already
been exceeded, it cannot be selected. If the
CO sensor is calibrated with gas through the
MENU
, the timer automatically resets.
GS3000 Gas Detection Sensor Series Installation Guide