6 G—G770BGJ 100% Lockout, Microprocessor-Based Intermittent Pilot Ignition Control
IMPORTANT: These instructions are intended as a guide for qualified
personnel installing or servicing Johnson Controls
ignition controls. Carefully follow all instructions in this
sheet and all instructions on the appliance. Limit repairs,
adjustments, and servicing to the operations listed in this
sheet or on the appliance.
!
WARNING: Fire or Explosion Hazard. Avoid serious injury by
carefully following precautions in this sheet and all
instructions on the appliance. Limit repairs,
adjustments, and servicing to the operations listed in
this sheet or on the appliance.
!
WARNING: Fire or Explosion Hazard. If the control is installed
in an area that is exposed to water (dripping,
spraying, rain, etc.), it must be protected. If the
control has been exposed to water in any way, do not
use it.
!
WARNING: Shock Hazard. Avoid electrical shock and
equipment damage. Disconnect electrical power and
turn off gas before wiring control into circuit.
Location/Mounting
!
CAUTION: Equipment Damage Hazard. Do not mount control
where it will be exposed to direct infrared radiation
from the main burner or to temperatures in excess of
the maximum product temperature rating.
Choose a location that provides the shortest, direct cable route to the spark
electrode, pilot burner/igniter-sensor assembly. Easy access to the
terminals is desired for wiring and servicing. The G770BGJ may be
mounted in any position. Mount the control on a grounded metal surface
with No. 8 machine or No. 6 sheet metal screws.
Installation and
Wiring
Ignition Control