background image

Table 5: Wireless Field Bus Device Address

Address Description

Device
Address

Reserved addresses for wired slave devices
(not valid for FX-PC controllers).

FX-PC Series Controllers ship with 128 ON
and the remaining address switches OFF,
rendering the controller's wired slave devices,
which do not operate on FX-PC field busses.

0 to 3

(Switch 128
ON)

Valid for FX-PC Series Controllers on

wireless

FC Buses only

.

4 to 127

(Switch 128
ON)

Note:

Do

not

connect an FX-PC Series

controller with these device addresses
to an active

wired

SA or FC Bus.

When a controller with one of these
device addresses is connected to a
wired field bus, the field bus is
rendered inoperable until the controller
is disconnected or Switch 128 is set
to OFF.

Setup and Adjustments

Important:

Electrostatic discharge can damage
controller components. Use proper
electrostatic discharge precautions during
installation, setup, and servicing to avoid
damaging the controller.

Setting the N2 Controller Address to
Be Greater than 127

N2-configured controllers support the full range of
possible N2 device addresses provided by the N2 protocol
standard (1-255). However, these controllers require
special configuration for addresses above 127.

Use the following instructions for controller addresses
greater than 127.

Note:

Before you perform this procedure, make sure
that your controller has been converted from
BACnet to N2 protocol first. Refer to the

Modernization Guide for Legacy N2 Controllers
(LIT-12012005)

for more information.

Note:

This special configuration is required because
controller addresses above 127 were originally
intended for use with the Wireless Field Bus
system.

1.

Disconnect the 24 VAC supply from the controller.

2.

Remove the FC Bus connector from the controller.

3.

Set the address switch set to the desired N2 address.

4.

Set the address switch segment labeled 128 to OFF.

5.

Reconnect the 24 VAC supply to the controller.

6.

Using an FX-PCT tool connection at the FX-PC
controller’s SA bus, download the firmware and
controller application file. The download process
asks to confirm switching the communication protocol
to N2.

7.

Click OK.

8.

After the download is finished, disconnect the
24 VAC supply from the FX-PC controller.

9.

Set the address switch segment labeled 128 to ON.

10. Reattach the FC Bus connector to the FX-PC

controller.

11. Reconnect the 24 VAC supply to the FX-PC

controller.

Setting the EOL Switch

Each FX-PC controller has an end-of-line (EOL) switch,
which, when set to ON (up), sets the controller as a
terminating device on the bus. See

Figure 6

for the EOL

switch location on the FX-PC controller. The default EOL
switch position is OFF (down). The amber EOL LED
illuminates to show the EOL is active.

Figure 6: EOL Switch Positions

To set the EOL switch on an FX-PC controller:
1. Determine the physical location of the controller on

the SA or FC Bus.

2. Determine if the controller must be set as a

terminating device on the bus.

Note:

The EOL termination rules for SA Buses and
FC Buses are different. Refer to the

FX-PC

Series Controllers MS/TP Communications
Bus Technical Bulletin (LIT-12011670)

for

detailed information regarding EOL termination
rules and EOL switch settings on SA and FC
Buses.

3. If the controller is a terminating device on the FC Bus,

set the EOL switch to ON. If the controller is not a
terminating device on the bus, set the EOL switch to
OFF.

Note:

When the EOL switch is set to ON, the LED
light on the face of the controller is illuminated.

9

FX-PCV1656 Programmable VAV Box VAV Controllers Installation Instructions

Содержание FX-PCV1656

Страница 1: ...Cs Release 10 1 and higher of FX PCT can be used to switch the Field Bus communications protocol in FX PC Controllers to be either the standard BACnet Master Slave Token Passing MS TP or the N2 protocol BACnet MS TP is the default communications protocol for all new controllers Switchable communications protocols provide a cost effective upgrade and modernization path for customers with existing N...

Страница 2: ...656 controller with removable FC and SA buses and power terminal blocks FX PCV1656 controller with attached ball valve linkage required mounting hardware included in linkage Installation Instructions Materials and Special Tools Needed T 20 TORX driver 1 4 in flat blade screwdriver Mounting Observe these guidelines when mounting an FX PCV Note Protect the FX PCV controller from dripping water conde...

Страница 3: ... the actuator gear release and rotate the handle until the actuator coupler is fully counterclockwise 10 Install the valve actuator over the ball valve mounting flange Depending on the installation position the assembly in any one of four 90 increments on the valve Note For proper operation the actuator must drive the valve counterclockwise to open Port A when viewed from above the valve 11 Tighte...

Страница 4: ...r 1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 2 Binary Input Dry Contact Maintained Mode 1 second minimum pulse width Internal 12 V 15k ohm pull up Same as Universal INn Universal Input Common for all Universal IN terminals ICOMn Note All Univer...

Страница 5: ...h Guidelines for Recommended Wire Sizes Assumptions Maximum Cable Length and Type Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to define an offset in the setup software for the input or output point 457 m 1 500 ft twisted wire 1 5 mm 2 18 AWG stranded copper A 297 m 975 ft twisted wire 0 8 mm 20 A...

Страница 6: ...Figure 4 Maximum Wire Length by Current and Wire Size 6 FX PCV1656 Programmable VAV Box VAV Controllers Installation Instructions ...

Страница 7: ... 15 VDC Supply Power for Devices on the SA Bus SA PWR 24 AWG 3 pair CAT 3 Cable 30 5 m 100 ft RJ 12 6 Position Modular Port provides FC Bus Communications FC Bus provides 15 VDC Power for FC BUS Wireless Bluetooth Commissioning Converter Wireless ZigBee Field Bus Router 0 8 mm to 1 5 mm 2 20 to 18 AWG 2 wire 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC HOT 24 24 VAC Power Supply Commo...

Страница 8: ...ntinue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switch 16 to ON first then set Switch 4 ON followed by Switch 1 16 4 1 21 3 Set Switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC Bus applications ensure that Switch 128 is set to OFF Note Do not ...

Страница 9: ... 24 VAC supply from the controller 2 Remove the FC Bus connector from the controller 3 Set the address switch set to the desired N2 address 4 Set the address switch segment labeled 128 to OFF 5 Reconnect the 24 VAC supply to the controller 6 Using an FX PCT tool connection at the FX PC controller s SA bus download the firmware and controller application file The download process asks to confirm sw...

Страница 10: ...in progress not ready for normal operation SA Bus devices offline such as Netsensors Off Steady No faults On Steady Device fault or no application loaded Off Steady Red FAULT Blink 2 Hz Data transmission normal communication Off Steady No data transmission auto baud in progress On Steady communication lost waiting to join communication ring Blink 2 Hz Green FC BUS Blink 2 Hz Data transmission norm...

Страница 11: ...SB dongle For additional information on the ZFR USBHA 0 ZigBee dongle refer to the FX ZFR Series Wireless Field Bus System Technical Bulletin LIT 12011660 or FX ZFR Series Wireless Field Bus System Quick Reference Guide LIT 12011696 ZFR USBHA 0 Refer to the FX PC Series Programmable Controllers and Related Products Product Bulletin LIT 12011657 for a complete list of available FX PCX Expansion I O...

Страница 12: ...cessor 1 MB flash memory and 512 KB RAM Memory UI Analog Input Mode 15 bit resolution on UIs CO Analog Output Mode FX PCV1656 only 0 10 VDC 200 mV Universal Input Mode Configurable Output Mode Accuracy 4 N m 35 lb in minimum shaft length 44 mm 1 3 4 in Actuator Rating Mounts to VG1000 Series 1 2 inch through 1 inch ball valves Mounting 165 x 125 x 73 mm 6 5 x 4 92 x 2 9 in Center of Output Hub to ...

Страница 13: ... E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Johnson Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Controls Inc www johnsoncontrols com Published in U S A 13 FX PCV1656 Programmable VAV Box VAV Controllers ...

Отзывы: