Setting the Device Address

FX-PC Series Controllers are master devices on BACnet

®

MS/TP (SA or FC) Buses. Before operating FX-PC
controllers on a bus, you must set a valid and unique
device address for each controller on the bus.

You set an FX-PC controller’s device address by setting
the positions of the switches on the Device Address DIP
switch block at the top of the controller. Device addresses
4 through 127 are the valid addresses for these
controllers.

The DIP switch block has eight switches numbered 128,
64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1 are
device address switches. Switch 128 is a mode switch
that enables an FX-PC controller to operate on an
FX-ZFR Series Wireless Field Bus. Switch 128 must be
set to OFF for all hard-wired SA and FC Bus applications.
Set Switch 128 to ON for wireless FC Bus applications
only.

Figure 5: Device Address Switches Set to 21

Note:

FX-PC Series Controllers ship with Switch 128
ON and the remaining address switches OFF.
This renders the controllers wired slave devices,
which do not interfere on MS/TP Buses and do
not interfere with bus operation. Set a valid and
unique device address on the controller before
applying power to the controller on the bus.

To set the device addresses on an FX-PC Series
Controller:

1. Set all of the switches on the controller’s device

address DIP switch block (128 through 1) to OFF.

2. Set one or more of the seven address switches (64

through 1) to ON, so that the sum of the switch
numbers set to ON equals the intended device
address. See

Table 4

and

Table 5

for valid FX-PC

controller addresses.

Set the highest number switch that is less than or
equal to the intended device address to ON. Then
continue setting lower numbered switches until the
total equals the intended address. For example, if the
intended device address is 21, set Switch 16 to ON
first, then set Switch 4 ON, followed by Switch 1
(16+4+1=21).

3. Set Switch 128 to ON only for controllers on an

FX-ZFR Series Wireless Field Bus application. For

all hard-wired SA and FC Bus applications, ensure
that Switch 128 is set to OFF.

Note:

Do not connect a wirelessly enabled FX-PC
controller to a wired FC Bus.

Refer to the

FX-ZFR Series Wireless Field Bus

System Technical Bulletin (LIT-12011660)

for more

information on device addresses in wireless
applications.

4. Set a unique and sequential device address for each

of the FX-PC controllers connected on the SA or FC
Bus, starting with device address 4.

To ensure the best bus performance, set sequential
device addresses with no gaps in the device address
range (4, 5, 6, 7, 8, 9, and so on). The FX-PC
controllers do not need to be physically connected
on the bus in their numerical device address order.

5. Write each FX-PC controller’s device address on the

white label below the DIP switch block on the
controller’s cover.

Refer to the

FX-PC Series Controllers MS/TP

Communications Bus Technical Bulletin (LIT-12011670)

for more information on FX-PC controller device
addresses and how to set them on MS/TP Buses.

Table 4

and

Table 5

show and describe the valid FC Bus

and SA Bus device addresses for Johnson Controls

®

MS/TP communications bus applications.

Table 4: FC Bus Device Address Descriptions

Address Description

Device
Address

Reserved for FX Supervisory Controller (not
valid for FX-PC controllers).

0

(Switch 128
OFF)

Reserved for peripheral devices (not valid for
FX-PC controllers).

1 to 3

(Switch 128
OFF)

Valid for FX-PC Series Controllers on a

hard-wired

SA Bus or FC Bus.

4 to 127

(Switch 128
OFF)

8

FX-PCV1656 Programmable VAV Box VAV Controllers Installation Instructions

Содержание FX-PCV1656

Страница 1: ...Cs Release 10 1 and higher of FX PCT can be used to switch the Field Bus communications protocol in FX PC Controllers to be either the standard BACnet Master Slave Token Passing MS TP or the N2 protocol BACnet MS TP is the default communications protocol for all new controllers Switchable communications protocols provide a cost effective upgrade and modernization path for customers with existing N...

Страница 2: ...656 controller with removable FC and SA buses and power terminal blocks FX PCV1656 controller with attached ball valve linkage required mounting hardware included in linkage Installation Instructions Materials and Special Tools Needed T 20 TORX driver 1 4 in flat blade screwdriver Mounting Observe these guidelines when mounting an FX PCV Note Protect the FX PCV controller from dripping water conde...

Страница 3: ... the actuator gear release and rotate the handle until the actuator coupler is fully counterclockwise 10 Install the valve actuator over the ball valve mounting flange Depending on the installation position the assembly in any one of four 90 increments on the valve Note For proper operation the actuator must drive the valve counterclockwise to open Port A when viewed from above the valve 11 Tighte...

Страница 4: ...r 1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 2 Binary Input Dry Contact Maintained Mode 1 second minimum pulse width Internal 12 V 15k ohm pull up Same as Universal INn Universal Input Common for all Universal IN terminals ICOMn Note All Univer...

Страница 5: ...h Guidelines for Recommended Wire Sizes Assumptions Maximum Cable Length and Type Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to define an offset in the setup software for the input or output point 457 m 1 500 ft twisted wire 1 5 mm 2 18 AWG stranded copper A 297 m 975 ft twisted wire 0 8 mm 20 A...

Страница 6: ...Figure 4 Maximum Wire Length by Current and Wire Size 6 FX PCV1656 Programmable VAV Box VAV Controllers Installation Instructions ...

Страница 7: ... 15 VDC Supply Power for Devices on the SA Bus SA PWR 24 AWG 3 pair CAT 3 Cable 30 5 m 100 ft RJ 12 6 Position Modular Port provides FC Bus Communications FC Bus provides 15 VDC Power for FC BUS Wireless Bluetooth Commissioning Converter Wireless ZigBee Field Bus Router 0 8 mm to 1 5 mm 2 20 to 18 AWG 2 wire 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC HOT 24 24 VAC Power Supply Commo...

Страница 8: ...ntinue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switch 16 to ON first then set Switch 4 ON followed by Switch 1 16 4 1 21 3 Set Switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC Bus applications ensure that Switch 128 is set to OFF Note Do not ...

Страница 9: ... 24 VAC supply from the controller 2 Remove the FC Bus connector from the controller 3 Set the address switch set to the desired N2 address 4 Set the address switch segment labeled 128 to OFF 5 Reconnect the 24 VAC supply to the controller 6 Using an FX PCT tool connection at the FX PC controller s SA bus download the firmware and controller application file The download process asks to confirm sw...

Страница 10: ...in progress not ready for normal operation SA Bus devices offline such as Netsensors Off Steady No faults On Steady Device fault or no application loaded Off Steady Red FAULT Blink 2 Hz Data transmission normal communication Off Steady No data transmission auto baud in progress On Steady communication lost waiting to join communication ring Blink 2 Hz Green FC BUS Blink 2 Hz Data transmission norm...

Страница 11: ...SB dongle For additional information on the ZFR USBHA 0 ZigBee dongle refer to the FX ZFR Series Wireless Field Bus System Technical Bulletin LIT 12011660 or FX ZFR Series Wireless Field Bus System Quick Reference Guide LIT 12011696 ZFR USBHA 0 Refer to the FX PC Series Programmable Controllers and Related Products Product Bulletin LIT 12011657 for a complete list of available FX PCX Expansion I O...

Страница 12: ...cessor 1 MB flash memory and 512 KB RAM Memory UI Analog Input Mode 15 bit resolution on UIs CO Analog Output Mode FX PCV1656 only 0 10 VDC 200 mV Universal Input Mode Configurable Output Mode Accuracy 4 N m 35 lb in minimum shaft length 44 mm 1 3 4 in Actuator Rating Mounts to VG1000 Series 1 2 inch through 1 inch ball valves Mounting 165 x 125 x 73 mm 6 5 x 4 92 x 2 9 in Center of Output Hub to ...

Страница 13: ... E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Johnson Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Controls Inc www johnsoncontrols com Published in U S A 13 FX PCV1656 Programmable VAV Box VAV Controllers ...

Отзывы: