background image

Table 1: I/O Terminal Blocks, Functions, Ratings, Requirements, and Cables

To Determine Wire Size
and Maximum Cable

Length

1

Function, Ratings, and Requirements

Terminal
Labels

Terminal Block Label

See Guideline A in

Table 2

.

Analog Output - Voltage Mode (0–10 VDC)

10 VDC maximum output voltage

10 mA maximum output current

External 1k to 50k ohm load required

OUTn

CONFIGURABLE

(Outputs)

See Guideline C in

Table 2

.

Binary Output 24 VAC Triac

Connects OUT to OCOM when activated.

External Power Source:

30 VAC maximum voltage to load

0.5 A maximum output current

1.3 A at 25% duty cycle

40 mA minimum load current

Same as (Configurable)

OUTn

.

Analog Output Signal Common

: All

Configurable Outputs defined as Analog Outputs
share a common, which is isolated from all other
commons except the Binary Input common.

OCOMn

Binary Output Signal Common

: All

Configurable Outputs defined as Binary Outputs
are isolated from all other commons, including
other Configurable Output commons.

1

Table 2

defines cable length guidelines for the various wire sizes that may be used for input and output wiring.

Table 2: Cable Length Guidelines for Recommended Wire Sizes

Assumptions

Maximum Cable Length
and Type

Wire Size/Gauge and Type

Guideline

100 mV maximum voltage drop

Depending on the cable length
and the connected input or
output device, you may have to
define an offset in the setup
software for the input or output
point.

457 m (1,500 ft) twisted wire

1.5 mm

2

(18 AWG) stranded

copper

A

297 m (975 ft) twisted wire

0.8 mm (20 AWG) stranded copper
297 m (975 ft) twisted wire

183 m (600 ft) twisted wire

0.6 mm (22 AWG) stranded copper
183 m (600 ft) twisted wire

107 m (350 ft) twisted wire

24 AWG stranded copper 107 m
(350 ft) twisted wire

100 mV maximum voltage drop

Depending on the cable length
and the connected input or
output device, you may have to
define an offset in the setup
software for the input or output
point.

229 m (750 ft) twisted wire

1.5 mm

2

(18 AWG) stranded

copper

B

137 m (450 ft) twisted wire

0.8 mm (20 AWG) stranded copper
297 m (975 ft) twisted wire

91 m (300 ft) twisted wire

0.6 mm (22 AWG) stranded copper
183 m (600 ft) twisted wire

61 m (200 ft) twisted wire

24 AWG stranded copper 107 m
(350 ft) twisted wire

N/A

See

Figure 4

to determine

cable length.

Use twisted wire cable.

See

Figure 4

to select wire

size/gauge.

Use stranded copper wire.

C

5

FX-PCV1656 Programmable VAV Box VAV Controllers Installation Instructions

Содержание FX-PCV1656

Страница 1: ...Cs Release 10 1 and higher of FX PCT can be used to switch the Field Bus communications protocol in FX PC Controllers to be either the standard BACnet Master Slave Token Passing MS TP or the N2 protocol BACnet MS TP is the default communications protocol for all new controllers Switchable communications protocols provide a cost effective upgrade and modernization path for customers with existing N...

Страница 2: ...656 controller with removable FC and SA buses and power terminal blocks FX PCV1656 controller with attached ball valve linkage required mounting hardware included in linkage Installation Instructions Materials and Special Tools Needed T 20 TORX driver 1 4 in flat blade screwdriver Mounting Observe these guidelines when mounting an FX PCV Note Protect the FX PCV controller from dripping water conde...

Страница 3: ... the actuator gear release and rotate the handle until the actuator coupler is fully counterclockwise 10 Install the valve actuator over the ball valve mounting flange Depending on the installation position the assembly in any one of four 90 increments on the valve Note For proper operation the actuator must drive the valve counterclockwise to open Port A when viewed from above the valve 11 Tighte...

Страница 4: ...r 1k Platinum and A99B Silicon Temperature Sensor Negative Temperature Coefficient NTC Sensor 10K Type L 10K Johnson Controls Type II is equivalent to Type L or 2 252K Type II See Guideline A in Table 2 Binary Input Dry Contact Maintained Mode 1 second minimum pulse width Internal 12 V 15k ohm pull up Same as Universal INn Universal Input Common for all Universal IN terminals ICOMn Note All Univer...

Страница 5: ...h Guidelines for Recommended Wire Sizes Assumptions Maximum Cable Length and Type Wire Size Gauge and Type Guideline 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to define an offset in the setup software for the input or output point 457 m 1 500 ft twisted wire 1 5 mm 2 18 AWG stranded copper A 297 m 975 ft twisted wire 0 8 mm 20 A...

Страница 6: ...Figure 4 Maximum Wire Length by Current and Wire Size 6 FX PCV1656 Programmable VAV Box VAV Controllers Installation Instructions ...

Страница 7: ... 15 VDC Supply Power for Devices on the SA Bus SA PWR 24 AWG 3 pair CAT 3 Cable 30 5 m 100 ft RJ 12 6 Position Modular Port provides FC Bus Communications FC Bus provides 15 VDC Power for FC BUS Wireless Bluetooth Commissioning Converter Wireless ZigBee Field Bus Router 0 8 mm to 1 5 mm 2 20 to 18 AWG 2 wire 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24 VAC HOT 24 24 VAC Power Supply Commo...

Страница 8: ...ntinue setting lower numbered switches until the total equals the intended address For example if the intended device address is 21 set Switch 16 to ON first then set Switch 4 ON followed by Switch 1 16 4 1 21 3 Set Switch 128 to ON only for controllers on an FX ZFR Series Wireless Field Bus application For all hard wired SA and FC Bus applications ensure that Switch 128 is set to OFF Note Do not ...

Страница 9: ... 24 VAC supply from the controller 2 Remove the FC Bus connector from the controller 3 Set the address switch set to the desired N2 address 4 Set the address switch segment labeled 128 to OFF 5 Reconnect the 24 VAC supply to the controller 6 Using an FX PCT tool connection at the FX PC controller s SA bus download the firmware and controller application file The download process asks to confirm sw...

Страница 10: ...in progress not ready for normal operation SA Bus devices offline such as Netsensors Off Steady No faults On Steady Device fault or no application loaded Off Steady Red FAULT Blink 2 Hz Data transmission normal communication Off Steady No data transmission auto baud in progress On Steady communication lost waiting to join communication ring Blink 2 Hz Green FC BUS Blink 2 Hz Data transmission norm...

Страница 11: ...SB dongle For additional information on the ZFR USBHA 0 ZigBee dongle refer to the FX ZFR Series Wireless Field Bus System Technical Bulletin LIT 12011660 or FX ZFR Series Wireless Field Bus System Quick Reference Guide LIT 12011696 ZFR USBHA 0 Refer to the FX PC Series Programmable Controllers and Related Products Product Bulletin LIT 12011657 for a complete list of available FX PCX Expansion I O...

Страница 12: ...cessor 1 MB flash memory and 512 KB RAM Memory UI Analog Input Mode 15 bit resolution on UIs CO Analog Output Mode FX PCV1656 only 0 10 VDC 200 mV Universal Input Mode Configurable Output Mode Accuracy 4 N m 35 lb in minimum shaft length 44 mm 1 3 4 in Actuator Rating Mounts to VG1000 Series 1 2 inch through 1 inch ball valves Mounting 165 x 125 x 73 mm 6 5 x 4 92 x 2 9 in Center of Output Hub to ...

Страница 13: ... E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY Building Efficiency 507 E Michigan Street Milwaukee WI 53202 Johnson Controls is a registered trademark of Johnson Controls Inc All other marks herein are the marks of their respective owners 2016 Johnson Controls Inc www johnsoncontrols com Published in U S A 13 FX PCV1656 Programmable VAV Box VAV Controllers ...

Отзывы: