QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 69
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Value Code
4022
N40:22
44023
R
Load Inhibit / Force Unload
0 = None
1 = Inhibit-Motor Current
2 = Inhibit-Low Suction Regulation 1
3 = Inhibit-Low Suction Regulation 2
4 = Inhibit-Low Suction Regulation 3
5 = Inhibit-Low Suction Regulation 4
6 = Inhibit-High Discharge Temperature
7 = Inhibit-High Discharge Pressure Mode 1
8 = Inhibit-High Discharge Pressure Mode 2
9 = Inhibit-High Suction Pressure
10 = Inhibit-Low Oil Flow
11 = Inhibit-Separator Velocity
12 = Inhibit-Low RPMs
13 = Inhibit-High Manifold Pressure
14 = Inhibit-Regulation Mode 1
15 = Inhibit-Regulation Mode 2
16 = Inhibit-Regulation Mode 3
17 = Inhibit-Regulation Mode 4
18 = Inhibit-Starting
19 = Inhibit-Capacity Pulldown
20 = Inhibit-At Maximum Load
21 = Inhibit-Vyper Converter Heatsink Temperature
22 = Inhibit-Vyper Ambient Temperature
23 = Inhibit-Harmonic Filter Baseplate Temperature
24 = Inhibit-Vyper Baseplate Temperature
25 = Inhibit-Vyper Phase A Baseplate Temperature
26 = Inhibit-Vyper Phase B Baseplate Temperature
27 = Inhibit-Vyper Phase C Baseplate Temperature
28 = Inhibit - Low Proc. Leaving Temp.
29 = Inhibit – Low Engine JW Temperature
30 = Inhibit – Maximum Capacity Position
31 = Inhibit – Minimum Capacity Position
50 = Force Unload-Volume Increase
51 = Force Unload-Motor Current
52 = Force Unload-Low Suction Regulation 1
53 = Force Unload-Low Suction Regulation 2
54 = Force Unload-Low Suction Regulation 3
55 = Force Unload-Low Suction Regulation 4
56 = Force Unload-Regulation Mode 1
57 = Force Unload-Regulation Mode 2
58 = Force Unload-Regulation Mode 3
59 = Force Unload-Regulation Mode 4
60 = Force Unload-High Discharge Temperature
61 = Force Unload-High Discharge Pressure Mode 1
62 = Force Unload-High Discharge Pressure Mode 2
63 = Force Unload-High Suction Pressure
64 = Force Unload-Low Oil Flow
65 = Force Unload-Separator Velocity
66 = Force Unload-Low RPMs
67 = Force Unload-High Manifold Pressure
68 = Force Unload-Stopping
69 = Force Unload-Vyper Converter Heatsink Temp.
70 = Force Unload-Vyper Ambient Temp.
71 = Force Unload-Harmonic Filter Baseplate Temp.
72 = Force Unload-Vyper Baseplate Temp.
73 = Force Unload-Vyper Phase A Baseplate Temp.
74 = Force Unload-Vyper Phase B Baseplate Temp.
75 = Force Unload-Vyper Phase C Baseplate Temp.
76 = Unload - Low Proc. Leaving Temp.
77 = Force Unload – Maximum Capacity Position
78 – Force Unload – Minimum Capacity Position
MODE VALUES: (Continued)
Содержание Frick QUANTUM LX
Страница 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Страница 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Страница 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Страница 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Страница 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Страница 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Страница 109: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 109 SECTION 8 Q5 CONTROLLER ...
Страница 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Страница 117: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 117 SECTION 9 Q4 CONTROLLER ...
Страница 129: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 129 SECTION 10 APPENDICES ...
Страница 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...