QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 25
RETURN FAILURE COMMAND:
#IDF
Command structure:
Command Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
F
Return Discrete
(F)
ailures List
Returned Answer:
Character
Position
Alarm
Description
1
High Discharge Pressure
Shutdown
0 = Safe
1 = Shutdown
2
High Discharge Pressure
Warning
0 = Safe
1 = Warning
3
Low Suction Pressure
Shutdown
0 = Safe
1 = Shutdown
4
Low Suction Pressure
Warning
0 = Safe
1 = Warning
5
Low Oil Pressure Shut-
down and/or Differential
Oil Pressure Shutdown
0 = Safe
1 = Shutdown
6
Low Oil Pressure Warning 0 = Safe
1 = Warning
7
High Oil Temp. Shutdown
0 = Safe
1 = Shutdown
8
High Oil Temp. Warning
0 = Safe
1 = Warning
9
Low Oil Temp. Shutdown
0 = Safe
1 = Shutdown
10
Low Oil Temp. Warning
0 = Safe
1 = Warning
11
High Discharge Temp.
Shutdown
0 = Safe
1 = Shutdown
12
High Discharge Temp.
Warning
0 = Safe
1 = Warning
13
Compressor Aux. Fail-
Shutdown
0 = Safe
1 = Shutdown
14
Pump Aux. Fail- Shut-
down
0 = Safe
1 = Shutdown
15
Oil Level Shutdown
0 = Safe
1 = Shutdown
16
Unused - 0
17
High Oil Filter Pressure
Warning
0 = Safe
1 = Warning
18
Unused - 0
19
Aux. 1 Alarm/Shutdown
0 = Safe
1 = Shutdown
20
Aux. 2 Alarm/Shutdown
0 = Safe
1 = Shutdown
21
Low Motor Current -
Shutdown
0 = Safe
1 = Shutdown
22
Sensor Fault
0 = Safe
1 = Warning
23
Unused - 0
24
Unused - 0
NOTE:
Returns a 24 char data string followed by ID, CR, LF.
CLEAR FAILURE COMMAND:
#IDKFID
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
KF
(K)
Clear
(F)
ailures
ID
(ID)
code repeated for veri
fi
cation
Returned Answer:
Character
Position
Description
1
(A)
cknowledge
2, 3
(ID)
code veri
fi
ed
(Carriage return, line feed)
CLEAR ANTIRECYCLE COMMAND:
#IDKRID
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
KR
(K)
Clear
(R)
ecycle Delay
ID
(ID)
code repeated for veri
fi
cation
Returned Answer:
Character
Position
Description
1
(A)
cknowledge
2, 3
(ID)
code veri
fi
ed
(Carriage return, line feed)
Содержание Frick QUANTUM LX
Страница 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Страница 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Страница 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Страница 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Страница 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Страница 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Страница 109: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 109 SECTION 8 Q5 CONTROLLER ...
Страница 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Страница 117: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 117 SECTION 9 Q4 CONTROLLER ...
Страница 129: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 129 SECTION 10 APPENDICES ...
Страница 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...