COMMUNICATIONS SETUP

FRICK

®

 QUANTUM™ LX

COMPRESSOR

Version 7.0x

Form 090.020-CS (APRIL 2013)

 COMUNICATIONS SETUP

File: 

SERVICE MANUAL - Section 90

Replaces: 

090.020 CS (SEP 11)

Dist: 

3, 3a, 3b, 3c

Содержание Frick QUANTUM LX

Страница 1: ...COMMUNICATIONS SETUP FRICK QUANTUM LX COMPRESSOR Version 7 0x Form 090 020 CS APRIL 2013 COMUNICATIONS SETUP File SERVICE MANUAL Section 90 Replaces 090 020 CS SEP 11 Dist 3 3a 3b 3c ...

Страница 2: ...ing Up Communication 18 Frick Protocol 19 Description 19 Frick Protocol Specifications 19 Quantum Protocol Specifications 26 Data Packet 26 SECTION 3 QUANTUM LX ALLEN BRADLEY COMMUNICATION 35 Overview Of Half And Full Duplex Theory 35 SLC 500 Suggested Setup 36 Channel Configuration 36 Read Message Setup Example 36 Write Message Setup Example 36 ALLEN BRADLEY PROGRAMMING OVERVIEW 37 Channel Config...

Страница 3: ... Board Values 64 Calculated Values 66 Mode Values 67 Timer Values 75 Setpoint Values 76 Commands 97 DBS Setpoint Values 98 General Setpoint Values 99 VSD Vyper Setpoint Values 99 SECTION 7 WARNING SHUTDOWN MESSAGE CODES 103 SECTION 8 Q5 CONTROLLER 110 Main Board History And Identification 110 Communications Connector Locations 110 SERIAL COMMUNICATIONS HARDWARE 111 General Description 111 COM 1 an...

Страница 4: ... Module 130 Wiring The Module 131 RS 232 Connections 131 RS 422 Connections 131 RS 485 Connections 131 APPENDIX B 132 Quantum LX Ethernet Communications Wiring 132 APPENDIX C 133 Quantum LX Local Ethernet Configurations 133 APPENDIX D 134 Quantum LX Ethernet Network Configurations 134 APPENDIX E 135 Quantum LX Serial Communications Wiring 135 Serial Communications Wiring Diagrams 138 To Customer R...

Страница 5: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 5 SECTION 1 INTRODUCTION TO THE QUANTUM CONTROL SYSTEM ...

Страница 6: ... see after the unit has been powered up This is called the Home screen Be aware that the content of this screen may differ from situation to situation based upon the actual configuration and in stalled options The Operating or Home screen HOW TO USE THIS MANUAL The purpose of this manual is provide the necessary information protocols data registers wiring etc to allow the end user to reliably comm...

Страница 7: ...an address of 216 27 61 137 you can simply enter in www jci com as an example Although the actual process is more detailed and complicated than this basic explanation the end result is that most of the work is being done invisibly The following write up describes how to set up the Quantum LX to do this behind the scenes work so that it can communicate both at the Internet level and at a local Ethe...

Страница 8: ...ins more intelligence than a hub Unlike hubs network switches are capable of inspecting the data packets as they are received determining the source and destination device of a packet and forwarding that packet appropriately By delivering messages only to the connected device that it was intended for net work switches conserve network bandwidth and offer generally better performance than hubs The ...

Страница 9: ...rs4sure com 10 RJ1145 Computercablestore com Connectors RJ 45 For Shielded 4 pair solid wire cable P 15007 Stonewall Cable Inc RJ 45 For Un shielded 4 pair solid wire cable 5 554169 3 Tyco Electronics 1 5E45 010 Computercablestore com P 15029 Stonewall Cable Inc Cable Tester Ethernet Cable Tester Continuity only TST 5150 Cablesforless com TS075A R2 Black Box Complete Cable I O Qualification Tester...

Страница 10: ... devices attached to your local network are routed to other gateways and networks A router is a Gateway device that routes packets between different physical networks A gateway is a network point that acts as an entrance to another network Subnet Mask A TCP IP number used to determine to which TCP IP subnet a device belongs Devices in the same subnet can be communicated with locally without going ...

Страница 11: ...t area that can be used in conjunction with the Host Name For example if the Host Name is Booster1 you could set the Server String to print something like DockBooster or some other ad ditional information about the unit The Server String has no control function it is strictly an informational area E MAIL DATA The purpose of the E Mail data feature is to allow the controller to send a Warning or Sh...

Страница 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...

Страница 13: ...into the industrial environment it was quickly noted that because of the high electrical noise potential from electric motors valves solenoids fluorescent light ing etc that the noise immunity characteristics of RS 232 protocol was grossly lacking Additionally the distances between the communicating equipment on the factory floor was much greater than that within the typical office environment For...

Страница 14: ...display Active Valid communications are actively occurring Failed An invalid command was received by the port This could be due to a bad checksum value a wiring issue or hardware problem at either the transmitting host or receiving Quantum LX end Baud Rate The baud rate defines the speed at which external communications can occur The higher the baud rate the faster the communications It is best to...

Страница 15: ...te of the internal communications of the I O boards The possible displayed states are Off Loss of or intermittent communications failures to the internal Quantum LX I O boards Active Indicates that normal I O communica tions are occurring Failed Loss of communications a shutdown message will be generated Redetect IO Comms Select this key to detect all con nected Analog and Digital boards If a boar...

Страница 16: ...riginal file appears in the following example Quantum to Quantum LX MAP Addresses Q LX LX Description 0 1026 Compressor Motor Start Signal 1 1027 Compressor Motor Starter Feedback Compressor Interlock 2 1028 Oil Pump Start Signal 3 1029 Oil Pump Feedback 4 1003 Capacity Increase 5 1002 Capacity Decrease 6 1005 Volume Increase 7 1004 Volume Decrease Q4 Quantum Version 5 0 and earlier addresses Quan...

Страница 17: ...00 38400 38400 38400 57600 57600 57600 115200 115200 115200 Data Bits 7 7 7 8 8 8 Stop Bits 1 1 1 2 2 2 Parity None None None Even Even Even Odd Odd Odd Protocol None None None Frick Frick Frick Modbus ASCII Modbus ASCII Modbus ASCII Modbus RTU Modbus RTU Modbus RTU AB DF1 Full Duplex AB DF1 Full Duplex AB DF1 Full Duplex AB DF1 Half Duplex AB DF1 Half Duplex AB DF1 Half Duplex DBS Motor Starter D...

Страница 18: ...eters and select a baud rate 3 Next setup the Quantum LX for the desired communication protocol Select the protocol from the Communications screen 4 Set the baud rate of the Comm Port to coincide with the setup of your device s communication port 5 Enter the Quantum LX ID This will be used to identify commands that are sent to it 6 Wire to the first panel via RS 232 Quantum 4 RS 422 or RS 485 to t...

Страница 19: ... 8 TX Transmit 5 RX Receive 4 RX Receive The following is a complete list of available Frick Protocol commands COMMAND CODE and DESCRIPTION I Returns compressor status I nformation R Compressor sta R t control S Compressor S top control A Return full load A mps information V Slide V alve Slide stop control MC Change M ode of C ompressor MV Change M ode of Slide V alve P Return P ressures informati...

Страница 20: ...ing control commands are for remote con trol of a compressor A compressor should be in both remote compressor mode and remote Slide Valve or capacity mode for remote control COMPRESSOR START CONTROL IDRID Command structure Command Description Start command sequence ID Compressor ID code 01 14 etc R Sta R t compressor command ID ID code repeated for verification NOTE The compressor must be in the r...

Страница 21: ... and would then automatically turn off NOTE the Slide Valve must be in the remote mode for this command to be executed Time is not accrued each command restarts timer Returned Answer for L or U commands Character Position Description of returned data 1 A cknowledge 2 3 ID code verified Carriage return line feed Returned Answer for S command Character Position Description of returned data 1 2 3 Sli...

Страница 22: ...ed Answer If using the S command the returned pressure will be XXXX 4 characters followed by a CR LF If using the D O or F commands the returned pressure will be XXX 3 characters followed by a CR LF If using the A command the returned data would be XXXXXXXXXXXX 12 characters followed by a CR LF RETURN TEMPERATURES COMMAND IDTX Command structure Command Description Start command sequence ID Compres...

Страница 23: ...osition byte 47 1 ID ones position byte 48 1 ID Checksum of all data pos 1 to 47 49 1 CR code 13 50 1 LF code 10 51 1 0 null terminator char QUERY SETPOINTS DATA IDQ2 Command structure Command Description Start command sequence ID Compressor ID code 01 14 etc Q2 Q uery Setpoints command Returned Answer Character Position Byte s Setpoint Name Comment 1 2 3 3 Future 4 5 6 3 Future 7 8 9 3 MLC amps s...

Страница 24: ...s The following is the complete list of setpoints that may be changed while in the change setpoints command 01xxxy Capacity Control Setpoint y deleted for KpaA BarA ver 02xxxy Change Low Suction Shutdown Set point y deleted for KpaA BarA ver 03xxxy Capacity Low Suction Alarm Setpoint y deleted for KpaA BarA ver 04xxx Change High Press Shutdown Setpoint xxxx is used for KpaA BarA ver 05xxx Change H...

Страница 25: ...Warning 0 Safe 1 Warning 13 Compressor Aux Fail Shutdown 0 Safe 1 Shutdown 14 Pump Aux Fail Shut down 0 Safe 1 Shutdown 15 Oil Level Shutdown 0 Safe 1 Shutdown 16 Unused 0 17 High Oil Filter Pressure Warning 0 Safe 1 Warning 18 Unused 0 19 Aux 1 Alarm Shutdown 0 Safe 1 Shutdown 20 Aux 2 Alarm Shutdown 0 Safe 1 Shutdown 21 Low Motor Current Shutdown 0 Safe 1 Shutdown 22 Sensor Fault 0 Safe 1 Warnin...

Страница 26: ...ntitled Hyperterminal later in this manual After setting up Hyperterminal and ensuring that all wiring and jumper configurations are correct type a symbol This is the character that will alert all of the Quantum panels on the communications line that data is on its way Following the symbol type the ID code of the Quantum that you wish to query for instance 01 for the first Quantum After the ID num...

Страница 27: ...erating Status Display Page 2 D3 Operating Status Display Page 3 D4 Operating Status Display Page 4 F1 Warnings Shutdowns Annunciation Page 1 F2 Warnings Shutdowns Annunciation Page 2 F3 Warnings Shutdowns Annunciation Page 3 MA Compressor mode Autocycle MM Compressor mode Manual MR Compressor mode Remote S2 Compressor sequence activate S3 Compressor sequence de activate T1 Read a value from the T...

Страница 28: ...urn Line Feed COMPRESSOR START COMMAND IDCT Command structure Command Description Start command sequence ID Compressor ID code 01 14 etc CT C ompressor S T art CS Checksum CR Carriage Return Returned Answer Character Position Description of returned data 1 A cknowledge 2 3 ID code verified Carriage Return Line Feed SLIDE VALVE CONTROL COMMANDS IDCUXX Command structure Command Description Start com...

Страница 29: ...Kilowatts 94 102 Slide Valve 103 111 Slide Stop 112 120 Process Temperature 121 122 Checksum Carriage Return Line Feed if successful RETURN OPERATING STATUS Page 2 Data IDD2 Command structure Command Description Start of command sequence ID Compressor ID code 01 14 etc D2 Operating Status D ata Page 2 command CS Checksum CR Carriage Return RETURNED ANSWER Character Position Description of returned...

Страница 30: ...Feed if successful RETURN OPERATING STATUS Page 3 Data IDD3 Command structure Command Description Start of command sequence ID Compressor ID code 01 14 etc D3 Operating Status D ata Page 3 command CS Checksum CR Carriage Return RETURNED ANSWER Character Position Description of returned data 1 A cknowledge 2 3 ID code 4 12 Communication Port 1 Code 13 21 Communication Port 2 Code 22 30 I O Communic...

Страница 31: ...Message Code 12 107 114 Date 12 as mm dd yy 115 122 Time 12 as hh mm ss 123 Space 124 125 Checksum Carriage Return Line Feed if successful RETURN Alarms Shut downs Page 3 Data IDF3 Command structure Command Description Start of command sequence ID Compressor ID code 01 14 etc F3 F ailure Annunciation command Page 3 CS Checksum CR Carriage Return RETURNED ANSWER Character Position Description of re...

Страница 32: ...mple 1 above would look like A01 000018731F the plus sym bol indicates that the data value re turned is positive The response to example 2 above would look like A01 00001873 00004901 00002949 0 0005652 0027249 00008211 00013354 00000656 0000288109 NOTE The following commands are for remote control of a compressor A compressor should be in both remote compres sor mode and remote Slide Valve or capa...

Страница 33: ...TE COMMAND IDS3 Command structure Command Description Start of command sequence ID Compressor ID code 01 14 etc S3 S equence Activate 3 CS Checksum CR Carriage Return RETURNED ANSWER Character Position Description of returned data 1 A cknowledge 2 3 ID code Carriage Return Line Feed if successful SLIDE VALVE MODE AUTOMATIC COMMAND IDVA Command structure Command Description Start of command sequenc...

Страница 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...

Страница 35: ...r than once every couple of seconds there will be temporary slowdowns during these processes Additionally keeping the Quantum LX busy writing to Flash memory will interfere with the communica tions to its I O Boards A communication failure to an I O board will cause the compressor to shutdown Control commands such as starting the compressor are also sent with a write command For more detail and a ...

Страница 36: ...it Time x20ms 20 System Mode Driver DF1 Half Duplex Leader or DF1 Full Duplex User Mode Driver Generic ASCII Write Protect DISABLED Mode Changes DISABLED Mode Attention Character 0x1b default System Mode Character S default User Mode Character U default Edit Resource File Owner Timeout Sec 60 Passthru Link ID decimal 1 READ MESSAGE SETUP EXAMPLE Read Write Message Type Peer To Peer Read Write Read...

Страница 37: ...l from an Allen Bradley AB SLC500 proces sor AB RSLogix500 programming software has been used for the following examples however these examples can also be used for the AB RSLogix5 software CHANNEL CONFIGURATION The following are representations of the channel con figuration screens from the AB RSLogix500 program ming software for the SLC500 Enter values as shown in order to establish communicatio...

Страница 38: ...ICATIONS SETUP 090 020 CS APRIL 13 Page 38 System Configuration Message Sequence Logic Use the following logic to sequence read and write mes sage to the Quantum LX panel This logic prevents hang up due to lost communications or message errors ...

Страница 39: ...ne compressor provided the messages are alternated between compressors This time delay is not required for Quantum V 5 0x or earlier Message Read Logic Use the following logic to read data from the Quantum LX panel To read more data or to read data from several compressors copy paste these rungs as needed then modify the control block and setup screen parameters accordingly The following message r...

Страница 40: ... SLC500 Data Table Address Data file location in the SLC500 Size in Elements of data file to read Channel Port location on the SLC processor Channel 0 is the RS 232 port Target Device Quantum Panel Data Table Address Data file location in the Quan tum LX controller Local Node Quantum LX ID Octal MESSAGE READ SETUP SCREEN The following setup screen is programmed to obtain 28 consecutive data files ...

Страница 41: ...o several compressors copy paste these rungs as needed then modify the control block and setup screen parameters ac Continued on next page cordingly The following write message instruction will be executed when counter 5 0 logic shown above is equal to 1 and when called upon by the change compressor mode bit B3 2 When B3 2 is off the counter will be in cremented to execute the next message in the ...

Страница 42: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 42 Continued from previous page ...

Страница 43: ...mode it is in For example a 0 is sent if it is in manual or a 10 is sent if it is in automatic or a 20 is sent if it is in Remote Commu nications The value zero 0 is used to represent an OFF status and a DISABLED option The value one 1 which is received as a 10 is used to represent an ON status and an ENABLED option Only data values that are designated as setpoints are modifiable Read Only is used...

Страница 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...

Страница 45: ...from the Quantum The Leader uses Function Code 6 Load Register to request to change a setpoint or to send a command such as starting the compressor Up to one hundred and twenty fi ve 125 data elements can be read with one read request The address references are numbered relative to the Frick addresses in the Quantum Data Table see MODBUS Addressing Note in the Quantum Data Table section of this ma...

Страница 46: ...rican Standard Code for Information Interchange each character byte in a message is sent as 2 ASCII characters This mode allows time intervals of up to a second between characters during transmission without generating errors Some particulars about MODBUS ASCII The device address field of the message frame contains two characters 16 bits The function code field of the message frame will contain tw...

Страница 47: ...rmal response the func tion code in the response is an echo of the function code in the query The data bytes contain the data collected by the Quantum such as register val ues or status If an error occurs the function code is modifi ed to indicate that the response is an er ror response and the data bytes contain a code that describes the error The error check fi eld allows the leader to confi rm ...

Страница 48: ...bit byte is exclusive ORed with the reg ister s current value and the process repeats for eight more shifts as described above The final contents of the register after all the bytes of the message have been applied is the CRC value When the CRC is appended to the message the low order byte is appended first followed by the high order byte 00 H O Address 87 L O Address 00 H O of data registers 01 L...

Страница 49: ... actual Discharge Pressure value of a compressor Using the address tables found later in this manual locate the address for Discharge Pressure In this case it is Frick Address 2003 dec imal Since this is the only address we are interested in obtaining the value of send the following message 01 03 07 D3 00 01 21 CRLF Where Message Start Quantum ID Read Function H O address hex L O address hex H O o...

Страница 50: ...s hex L O address hex H O of Data Registers L O of Data Registers Error Correction Code Carriage Return Line Feed In order to ensure that the Quantum in question re ceives the data request accurately we must append an Error Check byte to the end of the message This is accomplished by adding each of the byte pairs hex that we have generated thus far 01 03 07 D3 00 01 DF hex Next subtract DF hex fro...

Страница 51: ...ss hex H O of Data Value L O of Data Value Error Correction Code Carriage Return Line Feed In this particular example we are strictly looking to write a data value so we will be performing a write function 06 7150 decimal equals 1BEE hex Looking at our exam ple we see that we need a H O High Order address and a L O Low Order address Since all data sent and received is in ASCII Hex Byte format we n...

Страница 52: ...ection Code Carriage Return Line Feed ASCII Response Example If the packet was properly received by the Quan tum you should see an immediate response in Hy perTerminal In the Query Response read function example used earlier a response of 01030205D025 hex was received Where Message Start Quantum ID Read Function of Bytes Returned Data Error Correction Code 01 03 02 05 D0 25 Once again the fi rst p...

Страница 53: ... of Bytes Returned Data Error Correction Code RTU Query Read Example NOTE Hyperterminal cannot be used to test RTU In the following example a MODBUS command is sent to obtain the actual Discharge Pressure value of a compressor Refer to the following example to see what this message packet would look like START ADD FUNC STARTING ADDRESS OF REGISTERS TO LOAD CRC CHECK END T1 T2 T3 T4 01 03 07 D3 00 ...

Страница 54: ... setting is not changed Reference the Quantum Data Tables in this manual for the address listing and description of data A command has been provided that selects whether data to and from the Quantum will be returned in the units that are the default pressure in PSIA and temperature in Degree C or in the units that are selected to display at the panel MODBUS NOTES This has been an example of how th...

Страница 55: ... met so that communica tions may be established quickly with the Quantum so that time is not lost in trying to troubleshoot a potentially simple problem A connection from a Comm port of a computer running Microsoft Windows can be used to connect to a serial port of the Quantum SETTING UP HYPERTERMINAL You will need to locate either a lap top or desktop computer that has Hyperterminal installed Tur...

Страница 56: ...S ASCII section of this manual for information on MODBUS Set the five boxes as follows then click OK Bits per second 9600 must match the Quan tum Data bits 8 Parity None Stop Bits 1 Flow Control None The following screen will appear This is the screen whereby all communications out of the computer and into it will be shown When valid data is typed in here then sent the connected device recognizes ...

Страница 57: ...Proceed to the Testing Communications section TESTING COMMUNICATIONS Set the keyboard for CAPS so that all capital letters will be typed Type in the following command 01I then press ENTER This command will request the Quan tum with ID 01 to send a packet of Information If the communications is working properly there should be an immediate response from the first Quantum The response should look so...

Страница 58: ...for more detailed troubleshooting If no data appears or if the data does not match the spe cifi c protocol requirements that you are using then check the following Verify that the communications wiring matches that shown in the drawings at the end of this manual Access the Communications screen and verify that the Quantum ID is set to the same value that you are trying to access Also check that th...

Страница 59: ... 8 99 63 c 14 E ctrl N SO 57 39 9 100 64 d 15 F ctrl O SI 58 3A 101 65 e 16 10 ctrl P DLE 59 3B 102 66 f 17 11 ctrl Q DC1 60 3C 103 67 g 18 12 ctrl R DC2 61 3D 104 68 h 19 13 ctrl S DC3 62 3E 105 69 i 20 14 ctrl T DC4 63 3F 106 6A j 21 15 ctrl U NAK 64 40 107 6B k 22 16 ctrl V SYN 65 41 A 108 6C l 23 17 ctrl W ETB 66 42 B 109 6D m 24 18 ctrl X CAN 67 43 C 110 6E n 25 19 ctrl Y EM 68 44 D 111 6F o ...

Страница 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...

Страница 61: ...odbus Address Data Table Pages 1001 1061 N10 1 N10 61 41002 41062 Digital Board Values 62 63 2000 2081 N20 0 N20 81 42001 43001 Analog Board Values 64 65 3000 3081 N30 0 N30 81 43001 43082 Calculated Values 66 67 4000 4566 N40 0 N45 66 44001 44567 Mode Values 68 74 6000 6046 N60 00 N60 46 46001 46047 Timer Values 75 7060 8558 N100 60 N115 58 47061 48559 Setpoint Values 76 96 8910 8924 N119 10 N119...

Страница 62: ...nal None 0 Output 1032 N10 32 41033 R Oil Pump 2 Start Signal 2 15 1033 N10 33 41034 R Oil Pump 2 Feed back 2 16 Input 1036 N10 36 41037 R High Liquid Level Shutdown 1 14 Input 1037 N10 37 41038 R Regulator Mode A 1 19 1038 N10 38 41039 R Regulator Mode B 1 20 1042 N10 42 41043 R Shutdown 1 23 Output 1043 N10 43 41044 R Warning 1 22 1044 N10 44 41045 R Balance Piston 1 12 1045 N10 45 41046 R Panel...

Страница 63: ...N10 83 41084 R User Defined Digital Output 1 2 7 Output 1084 N10 84 41085 R User Defined Digital Output 2 2 8 1085 N10 85 41086 R User Defined Digital Output 3 2 18 1086 N10 86 41087 R User Defined Digital Output 4 None 0 1087 N10 87 41088 R User Defined Digital Output 5 None 0 1088 N10 88 41089 R User Defined Digital Output 6 None 0 1089 N10 89 41090 R User Defined Digital Output 7 None 0 1090 N1...

Страница 64: ...2027 R Remote Control Setpoint 1 12 Input 2027 N20 27 42028 R Motor Current 1 16 2028 N20 28 42029 R RPM NOTE RPM values are NOT multi plied by 10 in Allen Bradley and MODBUS protocols 2 16 2029 N20 29 42030 R KW Monitoring None 0 2031 N20 31 42032 R User Defined Analog Input 1 2 5 Input 2032 N20 32 42033 R User Defined Analog Input 2 2 6 2033 N20 33 42034 R User Defined Analog Input 3 2 7 2034 N2...

Страница 65: ... Compressor Vibration Discharge 1 18 2073 N20 73 42074 R Motor Vibration Shaft Side 1 19 2074 N20 74 42075 R Motor Vibration Opposite Shaft Side 1 20 2075 N20 75 42076 R Condenser Analog Step 1 1 5 Output 2076 N20 76 42077 R Condenser Analog Step 2 1 6 2077 N20 77 42078 R Motor Temperature Shaft Side None 0 Input 2078 N20 78 42079 R Motor Temperature Opposite Shaft Side None 0 2079 N20 79 42080 R ...

Страница 66: ...l 3059 N30 59 43060 R Calculated Volume Ration Economizer 3060 N30 60 43061 R Current Regulation Value Pressure 3061 N30 61 43062 R Current Regulation Setpoint 3062 N30 62 43063 R Estimated Kilowatts kW 3063 N30 63 43064 R Panel Temperature Temperature 3070 N30 70 43071 R Safety 1 Message Most Recent Note 1 Integer 3071 N30 71 43072 R Safety 2 Message 3072 N30 72 43073 R Safety 3 Message 3073 N30 ...

Страница 67: ...44003 R Prelube 0 Not in Prelube 1 In Prelube 4003 N40 3 44004 R Postlube 0 Not in Postlube 1 In Postlube 4004 N40 4 44005 R Shutdown 0 No Shutdowns 1 Shutdown 4005 N40 5 44006 R Warning 0 No Warning 1 Warning 4006 N40 6 44007 R Recycle Delay Time 0 Not In Recycle Delay 1 In Recycle Delay 4007 N40 7 44008 R Compressor mode 0 Manual 1 Automatic 2 Remote Communications 3 Remote IO 5 Remote Sequencin...

Страница 68: ...0 Recip 3 4014 N40 14 44015 R Regulation Mode 0 Regulation 1 1 Regulation 2 2 Regulation 3 3 Regulation 4 4015 N40 15 44016 R Regulation Mode 1 Direction 0 Forward 1 Backward 4016 N40 16 44017 R Regulation Mode 2 Direction 4017 N40 17 44018 R Regulation Mode 3 Direction 4018 N40 18 44019 R Regulation Mode 4 Direction 4019 N40 19 44020 R Compressor Drive Type 0 Screw Comp with Constant Electric Dri...

Страница 69: ...bit Vyper Phase C Baseplate Temperature 28 Inhibit Low Proc Leaving Temp 29 Inhibit Low Engine JW Temperature 30 Inhibit Maximum Capacity Position 31 Inhibit Minimum Capacity Position 50 Force Unload Volume Increase 51 Force Unload Motor Current 52 Force Unload Low Suction Regulation 1 53 Force Unload Low Suction Regulation 2 54 Force Unload Low Suction Regulation 3 55 Force Unload Low Suction Reg...

Страница 70: ...gital Auxiliaries 12 Power Fail Restart 13 Start Inhibit Low Oil Pressure 14 Running 15 Start Inhibit In Discharge Pressure Blowdown 4071 N40 71 44072 R Capacity Status 0 Idle 1 Load 2 Unload 4072 N40 72 44073 R Volume Status 0 Idle 1 Increase 2 Decrease 4073 N40 73 44074 R Language Local Display Only 0 English 1 French 2 Chinese 3 Portuguese 4 Polish 5 Chinese 6 Spanish 7 Russian 8 Italian 4074 N...

Страница 71: ...7 R401a 18 R402a 19 R404a 20 R410a 21 R50 22 R500 23 R502 24 R503 25 R507 26 R508 27 R508b 28 R600 29 R600a 30 R717 31 R718 32 R728 33 R729 34 R744 35 R771 50 User Defined 4237 N42 37 44238 R Oil Pump Status 0 Off 1 Running 4239 N42 39 44240 R PID 1 Control 0 Disabled 1 Running 2 Always 4242 N42 42 44243 R PID 2 Control 0 Disabled 1 Running 2 Always 4245 N42 45 44246 R PID 3 Control 0 Disabled 1 R...

Страница 72: ...96 R Sequencing Sys 1 Comp 5 Capacity Mode 4396 N43 96 44397 R Sequencing Sys 1 Comp 6 Capacity Mode 4397 N43 97 44398 R Sequencing Sys 1 Comp 7 Capacity Mode 4398 N43 98 44399 R Sequencing Sys 1 Comp 8 Capacity Mode 4407 N44 07 44408 R Sequencing Enable System 1 0 Disabled 1 Enabled 4417 N44 17 44418 R Sequencing Sys 1 Comp 1 Comp Status 0 Off 1 Running 20 Starting 30 Stopping 31 Stopping High Ca...

Страница 73: ...Comp 5 Comp Status 4472 N44 72 44473 R Sequencing Sys 2 Comp 6 Comp Status 4473 N44 73 44474 R Sequencing Sys 2 Comp 7 Comp Status 4474 N44 74 44475 R Sequencing Sys 2 Comp 8 Comp Status 4483 N44 83 44484 R Sequencing Sys 3 Comp 1 Comp Mode 0 Manual 1 Automatic 2 Remote Communications 3 Remote IO 5 Remote Sequencing 4484 N44 84 44485 R Sequencing Sys 3 Comp 2 Comp Mode 4485 N44 85 44486 R Sequenci...

Страница 74: ... Sys 3 Comp 7 Comp Status 4524 N45 24 44525 R Sequencing Sys 3 Comp 8 Comp Status 4533 N45 33 44534 R Oil Pump Mode 0 Manual 1 Automatic 4534 N45 34 44535 R Screen Saver 0 Disabled 1 Enabled 4539 N45 39 44540 R Starter Alarms 4540 N45 40 44541 R Starter Trips 4547 N45 47 44548 R Input Module Capacity Mode Selection 0 Disabled 1 Enabled 4548 N45 48 44549 R Permissive Start Enable 0 Disabled 1 Start...

Страница 75: ... N60 19 46020 R Oil Injection Timer 6020 N60 20 46021 R Starting Load Inhibit Timer 6021 N60 21 46022 R Capacity Pulldown Timer 6022 N60 22 46023 R General 60 Second Timer 6023 N60 23 46024 R Recycle Delay Timer 6024 N60 24 46025 R Oil Charging Timer 6025 N60 25 46026 R Differential Pressure OK Timer 6026 N60 26 46027 R Slide to Zero Timer 6027 N60 27 46028 R General 1 Second Timer 6028 N60 28 460...

Страница 76: ... N101 57 47158 R W Regulation Mode 1 Low Cycle Time 7158 N101 58 47159 R W Regulation Mode 1 Auto Cycle Start Pressure 7159 N101 59 47160 R W Regulation Mode 1 Auto Cycle Start Delay Minutes 7160 N101 60 47161 R W Regulation Mode 1 Auto Cycle Stop Pressure 7161 N101 61 47162 R W Regulation Mode 1 Auto Cycle Stop Delay Minutes 7162 N101 62 47163 R W Regulation Mode 1 Load Inhibit Pressure 7163 N101...

Страница 77: ...tion Pressure Mode 2 Load Inhibit Pressure 7223 N102 23 47224 R W Low Suction Pressure Mode 2 Force Unload 7226 N102 26 47227 R W Mode 2 Prop Band Pressure 7227 N102 27 47228 R W Mode 2 Integration Time Seconds 7250 N102 50 47251 R W Regulation Mode 3 Setpoint Pressure 7252 N102 52 47253 R W Regulation Mode 3 High Dead Band Pressure Magnitude 7253 N102 53 47254 R W Regulation Mode 3 Low Dead Band ...

Страница 78: ... 7315 N103 15 47316 R W Regulation Mode 4 Warning 7316 N103 16 47317 R W Regulation Mode 4 Shutdown Delay Seconds 7317 N103 17 47318 R W Regulation Mode 4 Warning Delay 7318 N103 18 47319 R W Low Suction Pressure Shutdown Mode 4 Pressure 7319 N103 19 47320 R W Low Suction Pressure Shutdown Mode 4 Delay Seconds 7320 N103 20 47321 R W Low Suction Pressure Warning Mode 4 Pressure 7321 N103 21 47322 R...

Страница 79: ...47391 R W High RPMs Shutdown Delay 7391 N103 91 47392 R W High RPMs Warning Delay Seconds 7392 N103 92 47393 R W High Manifold Pressure Load Inhibit Pressure 7393 N103 93 47394 R W High Manifold Pressure Force Unload 7394 N103 94 47395 R W High Manifold Pressure Shutdown 7395 N103 95 47396 R W High Manifold Pressure Warning 7396 N103 96 47397 R W High Manifold Pressure Shutdown Delay Seconds 7397 ...

Страница 80: ... R W Time Schedule Monday 4th Mode Hour 2 7440 N104 40 47441 R W Time Schedule Monday 4th Mode Minute 2 7441 N104 41 47442 R W Time Schedule Tuesday 1st Mode Hour 1 7442 N104 42 47443 R W Time Schedule Tuesday 1st Mode Minute 1 7443 N104 43 47444 R W Time Schedule Tuesday 2nd Mode Hour 2 7444 N104 44 47445 R W Time Schedule Tuesday 2nd Mode Minute 2 7445 N104 45 47446 R W Time Schedule Tuesday 3rd...

Страница 81: ...p Frequency 2 Bottom 7489 N104 89 47490 R W Skip Frequency 2 Top 7490 N104 90 47491 R W Skip Frequency 3 Bottom 7491 N104 91 47492 R W Skip Frequency 3 Top 7492 N104 92 47493 R W Skip Frequency 4 Bottom 7493 N104 93 47494 R W Skip Frequency 4 Top 7494 N104 94 47495 R W Skip Frequency 5 Bottom 7495 N104 95 47496 R W Skip Frequency 5 Top 7500 N105 00 47501 R W Demand Cycling On Pressure Magnitude 75...

Страница 82: ...B 7558 N105 58 47559 R W Insufficient Oil Pressure Safety Offset Pressure Magnitude 7559 N105 59 47560 R W Insufficient Oil Pressure Shutdown Capacity Value Percent 7560 N105 60 47561 R W Insufficient Oil Pressure Shutdown Delay Seconds 7561 N105 61 47562 R W Insufficient Oil Pressure Load Inhibit Capacity Value Percent 7562 N105 62 47563 R W Insufficient Oil Pressure Force Unload Capacity Value 7...

Страница 83: ...08 47609 R W Condenser High Limit Percent 7609 N106 09 47610 R W Condenser Low Limit 7610 N106 10 47611 R W Condenser Control Setpoint Pressure 7611 N106 11 47612 R W Condenser High Dead Band Pressure Magnitude 7612 N106 12 47613 R W Condenser Low Dead Band 7613 N106 13 47614 R W Condenser High Step Delay Seconds 7614 N106 14 47615 R W Condenser Low Step Delay 7615 N106 15 47616 R W Condenser Orde...

Страница 84: ...107 02 47703 R W Auxiliary Input 3 Delay 7703 N107 03 47704 R W Auxiliary Input 4 Delay 7704 N107 04 47705 R W Auxiliary Input 5 Delay 7705 N107 05 47706 R W Auxiliary Input 6 Delay 7706 N107 06 47707 R W Auxiliary Input 7 Delay 7707 N107 07 47708 R W Auxiliary Input 8 Delay 7708 N107 08 47709 R W Auxiliary Input 9 Delay 7709 N107 09 47710 R W Auxiliary Input 10 Delay 7710 N107 10 47711 R W Auxili...

Страница 85: ...ry Analog 3 Low Shutdown Delay Seconds 7756 N107 56 47757 R W Auxiliary Analog 3 Low Warning Pressure 7757 N107 57 47758 R W Auxiliary Analog 3 Low Warning Delay Seconds 7760 N107 60 47761 R W Auxiliary Analog 4 High Shutdown Pressure 7761 N107 61 47762 R W Auxiliary Analog 4 High Shutdown Delay Seconds 7762 N107 62 47763 R W Auxiliary Analog 4 High Warning Pressure 7763 N107 63 47764 R W Auxiliar...

Страница 86: ...804 N108 04 47805 R W Auxiliary Analog 8 Low Shutdown Pressure 7805 N108 05 47806 R W Auxiliary Analog 8 Low Shutdown Delay Seconds 7806 N108 06 47807 R W Auxiliary Analog 8 Low Warning Pressure 7807 N108 07 47808 R W Auxiliary Analog 8 Low Warning Delay Seconds 7810 N108 10 47811 R W Auxiliary Analog 9 High Shutdown Pressure 7811 N108 11 47812 R W Auxiliary Analog 9 High Shutdown Delay Seconds 78...

Страница 87: ...log 13 High Warning Delay Seconds 7854 N108 54 47855 R W Auxiliary Analog 13 Low Shutdown Pressure 7855 N108 55 47856 R W Auxiliary Analog 13 Low Shutdown Delay Seconds 7856 N108 56 47857 R W Auxiliary Analog 13 Low Warning Pressure 7857 N108 57 47858 R W Auxiliary Analog 13 Low Warning Delay Seconds 7860 N108 60 47861 R W Auxiliary Analog 14 High Shutdown Pressure 7861 N108 61 47862 R W Auxiliary...

Страница 88: ... Analog 18 High Warning Pressure 7903 N109 03 47904 R W Auxiliary Analog 18 High Warning Delay Seconds 7904 N109 04 47905 R W Auxiliary Analog 18 Low Shutdown Pressure 7905 N109 05 47906 R W Auxiliary Analog 18 Low Shutdown Delay Seconds 7906 N109 06 47907 R W Auxiliary Analog 18 Low Warning Pressure 7907 N109 07 47908 R W Auxiliary Analog 18 Low Warning Delay Seconds 7910 N109 10 47911 R W Auxili...

Страница 89: ...ID 1 High Limit Percent 8006 N110 06 48007 R W PID 1 Low Limit 8007 N110 07 48008 R W PID 1 When Running Off Value 8008 N110 08 48009 R W PID 2 Setpoint None 8009 N110 09 48010 R W PID 2 Deadband 8010 N110 10 48011 R W PID 2 Proportional Band 8011 N110 11 48012 R W PID 2 Integral Gain Real 8012 N110 12 48013 R W PID 2 Derivative Gain 8013 N110 13 48014 R W PID 2 High Limit Percent 8014 N110 14 480...

Страница 90: ...53 N110 53 48054 R W PID 7 High Limit Percent 8054 N110 54 48055 R W PID 7 Low Limit 8055 N110 55 48056 R W PID 7 When Running Off Value 8056 N110 56 48057 R W PID 8 Setpoint None 8057 N110 57 48058 R W PID 8 Deadband 8058 N110 58 48059 R W PID 8 Proportional Band 8059 N110 59 48060 R W PID 8 Integral Gain Real 8060 N110 60 48061 R W PID 8 Derivative Gain 8061 N110 61 48062 R W PID 8 High Limit Pe...

Страница 91: ...or 1 Temperature Shutdown Temperature 8143 N111 43 48144 R W High Motor Stator 1 Temperature Shutdown Delay Seconds 8144 N111 44 48145 R W High Motor Stator 2 Temperature Warning Temperature 8145 N111 45 48146 R W High Motor Stator 2 Temperature Warning Delay Seconds 8146 N111 46 48147 R W High Motor Stator 2 Temperature Shutdown Temperature 8147 N111 47 48148 R W High Motor Stator 2 Temperature S...

Страница 92: ...ressor 2 ID 8302 N113 02 48303 R W Sequencing System 1 Compressor 3 ID 8303 N113 03 48304 R W Sequencing System 1 Compressor 4 ID 8304 N113 04 48305 R W Sequencing System 1 Compressor 5 ID 8305 N113 05 48306 R W Sequencing System 1 Compressor 6 ID 8306 N113 06 48307 R W Sequencing System 1 Compressor 7 ID 8307 N113 07 48308 R W Sequencing System 1 Compressor 8 ID 8308 N113 08 48309 R W Sequencing ...

Страница 93: ...ng System 1 Compressor 8 Minimum Capacity 8343 N113 43 48344 R W Sequencing System 1 Compressor 1 Follower Command None 8344 N113 44 48345 R W Sequencing System 1 Compressor 2 Follower Command 8345 N113 45 48346 R W Sequencing System 1 Compressor 3 Follower Command 8346 N113 46 48347 R W Sequencing System 1 Compressor 4 Follower Command 8347 N113 47 48348 R W Sequencing System 1 Compressor 5 Follo...

Страница 94: ...7 N114 27 48428 R W Sequencing System 2 Compressor 1 Run Time Integer 8428 N114 28 48429 R W Sequencing System 2 Compressor 2 Run Time 8429 N114 29 48430 R W Sequencing System 2 Compressor 3 Run Time 8430 N114 30 48431 R W Sequencing System 2 Compressor 4 Run Time 8431 N114 31 48432 R W Sequencing System 2 Compressor 5 Run Time 8432 N114 32 48433 R W Sequencing System 2 Compressor 6 Run Time 8433 ...

Страница 95: ... W Sequencing System 3 Compressor 2 Start 8510 N115 10 48511 R W Sequencing System 3 Compressor 3 Start 8511 N115 11 48512 R W Sequencing System 3 Compressor 4 Start 8512 N115 12 48513 R W Sequencing System 3 Compressor 5 Start 8513 N115 13 48514 R W Sequencing System 3 Compressor 6 Start 8514 N115 14 48515 R W Sequencing System 3 Compressor 7 Start 8515 N115 15 48516 R W Sequencing System 3 Compr...

Страница 96: ...ompressor 1 Follower Command None 8544 N115 44 48545 R W Sequencing System 3 Compressor 2 Follower Command 8545 N115 45 48546 R W Sequencing System 3 Compressor 3 Follower Command 8546 N115 46 48547 R W Sequencing System 3 Compressor 4 Follower Command 8547 N115 47 48548 R W Sequencing System 3 Compressor 5 Follower Command 8548 N115 48 48549 R W Sequencing System 3 Compressor 6 Follower Command 8...

Страница 97: ...commands that are sent through serial communications and the Capacity Mode must be in remote com munications to accept load and unload commands that are sent Note 2 To read the proper Temperature Pressure units use Frick address 4566 To change write to the Temperature Pressure units use Frick address 8920 Note 3 Mode must already be enabled Note 4 The value passed with this command is the position...

Страница 98: ...48971 R Bypass Time Seconds 8971 N119 71 48972 R Constant Current Level Percent 8972 N119 72 48973 R Ramp Time Seconds 8973 N119 73 48974 R DBS Version Real 8974 N119 74 48975 R Last Trip Current Amps 8975 N119 75 48976 R Last Trip Heatsink Temp Temperature 8976 N119 76 48977 R Last Trip RTD Temp 8977 N119 77 48978 R Last Trip Thermal Capacity Percent 8978 N119 78 48979 R Last Trip FLA Amps 8979 N...

Страница 99: ...ead Write Description of Data Units 9200 N122 00 49201 R W Vyper Drive Standby Time Minutes 9210 N122 10 49211 R Vyper Drive Auto Speed Command NOTE RPM values are NOT multiplied by 10 in Allen Bradley and MODBUS protocols RPM 9211 N122 11 49212 R Vyper Drive Run Command None 9215 N122 15 49216 R Vyper Drive Current Fault None 9216 N122 16 49217 R Vyper Drive Current Warning 9218 N122 18 49219 R V...

Страница 100: ... 53 49254 R Harmonic Filter L1 L2 Voltage 9254 N122 54 49255 R Harmonic Filter L2 L3 Voltage 9255 N122 55 49256 R Harmonic Filter L3 L1 Voltage 9256 N122 56 49257 R Harmonic Filter L1 Total Harmonic Distortion Percent 9257 N122 57 49258 R Harmonic Filter L2 Total Harmonic Distortion 9258 N122 58 49259 R Harmonic Filter L3 Total Harmonic Distortion 9259 N122 59 49260 R Harmonic Filter L1 Filter Cur...

Страница 101: ...to IB Checksum Errors 9289 N122 89 49290 R Vyper Drive Software Reboots 9290 N122 90 49291 R Vyper Drive Phase B Baseplate Temperature Temperature 9291 N122 91 49292 R Vyper Drive Phase C Baseplate Temperature 9295 N122 95 49296 R Vyper Drive Fault 1 9296 N122 96 49297 R Vyper Drive Warning 1 9297 N122 97 49298 R Vyper Drive Fault 2 9298 N122 98 49299 R Vyper Drive Warning 2 9299 N122 99 49300 R V...

Страница 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...

Страница 103: ...ntially displayable The numeric value to the left of each message corresponds to the value that is read from the Safety Message addresses Frick address 3070 3079 As an example if Frick address 3070 were being read and it returned a value of 51 then referring to the chart on the following pages it would be found that the code of 51 represents Oil Level Shutdown 3 Balance Piston 1 Shutdown 4 Balance...

Страница 104: ...ng 117 Low Auxiliary Analog 9 Shutdown 118 Low Auxiliary Analog 9 Warning 119 High Auxiliary Analog 10 Shutdown 120 High Auxiliary Analog 10 Warning 121 Low Auxiliary Analog 10 Shutdown 122 Low Auxiliary Analog 10 Warning 123 Low Suction Pressure Sensor Fault 124 Low Discharge Pressure Sensor Fault 125 High Discharge Pressure Sensor Fault 126 Low Comp Oil Pressure Sensor Fault 127 High Comp Oil Pr...

Страница 105: ... 203 Oil Pump 1 Auxiliary Warning 204 Oil Pump 1 Auxiliary Shutdown 205 Oil Pump 2 Auxiliary Warning 206 Oil Pump 2 Auxiliary Shutdown 207 Low Comp Oil Pressure Warning 208 Low Comp Oil Pressure Shutdown 209 Low Oil Pressure Shutdown 2 210 High Compressor Vib Warning Suction 211 High Compressor Vib Warning Discharge 212 High Compressor Vib Shutdown Suction 213 High Compressor Vib Shutdown Discharg...

Страница 106: ...ring Temp Warning 338 Low Process Entering Temp Shutdown 339 Low Process Entering Temp Warning 340 High Motor Temp Warning Shaft Side WARNING SHUTDOWN MESSAGE CODES Continued 341 High Motor Temp Warning Opp Shaft Side 342 High Motor Temp Shutdown Shaft Side 343 High Motor Temp Shutdown Opp Shaft Side 344 High Motor Stator 1 Temp Warning 345 High Motor Stator 1 Temp Shutdown 346 High Motor Stator 2...

Страница 107: ...gh Auxiliary Analog Input 7 Sensor Warning 426 Low Auxiliary Analog Input 8 Sensor Warning 427 High Auxiliary Analog Input 8 Sensor Warning WARNING SHUTDOWN MESSAGE CODES Continued 428 Low Auxiliary Analog Input 9 Sensor Warning 429 High Auxiliary Analog Input 9 Sensor Warning 430 Low Auxiliary Analog Input 10 Sensor Warning 431 High Auxiliary Analog Input 10 Sensor Warning 432 Low Auxiliary Analo...

Страница 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...

Страница 109: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 109 SECTION 8 Q5 CONTROLLER ...

Страница 110: ...umber of jumpers present on both the Q5 and the Interface board These jumpers MAY need to be modified by qualified personnel to configure the Quan tum 5 for specific applications The Q5 utilizes Flash Card technology There is a Flash Card socket located on the under side of this main board The Q5 board has the LX Operating System pre loaded at the factory so this Flash Card feature will primarily ...

Страница 111: ... will be explained in the section entitled Com 4 Description Communications Ports on the Q5 Interface Board Q5 SERIAL COMMUNICATIONS HARDWARE Q5 GENERAL DESCRIPTION User connections for serial communications to and from the Q5 are located on the Interface board and can use RS 422 and or RS 485 hardware protocol These hardware protocols can be connected via Com 3 and Com 4 for RS 485 and Com 1 and ...

Страница 112: ...X RX 1 RX RX RS 485 Signal Wiring Connector Pin Signal COMM 1 P10 COMM 2 P11 COMM 3 P17 COMM 4 P16 5 GND 4 N C 3 N C GND 2 TX RX TX RX 1 TX RX TX RX The following pictorial shows a cutaway view of the Interface board as well as the jumpers LED s and signal pinouts to allow the end user to communi cate to COMM 1 P10 and COMM 2 P11 using RS 422 485 protocol and to use COMM 3 P16 to com municate via ...

Страница 113: ...ntitled RS 422 485 COMM 1 P10 COMM 2 P11 Board Jumpers for the func tion of each of the jumpers associated with COMM 2 Notice also the two LED indicators that are pointed out D26 LED will flash each time that the Quantum transmits TX data D25 LED will flash each time that data is received RX If communications cannot be established us ing COMM 2 then note the status of these two LED s D25 and D26 I...

Страница 114: ... Notice that in the figure entitled RS 422 485 Connectors Jumpers and LED Location there are no jumpers associated with COMM 3 If communications with the Quantum 5 can not be established using COMM 3 then access the Communications Setup screen and verify that the proper Panel ID Baud rate data bits and protocol has been setup and matches that of the initiating device COMM 4 P17 NOTE Although COMM ...

Страница 115: ...e whether the data is IN or OUT Re ceive or Send and the actual data in Hexadecimal format This information can be used to compare against the data be ing sent and received at the other end of the communications link to verify proper operation Refer to the section on Hyper terminal for some examples of how this screen may be used SERVICE ModBus TCP Log DESCRIPTION This screen allows the technician...

Страница 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...

Страница 117: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 117 SECTION 9 Q4 CONTROLLER ...

Страница 118: ... primarily be utilized for future program updates When calling Frick Company for service or help it will greatly assist us if the type of board is known either Q1 2 3 or 4 Additionally Frick will request the Sales Order number and the Operating System version number this can be found on the About screen The more informa tion available at the time of the call the better able we will be to assist yo...

Страница 119: ...ls PL6 Com 3 RS 485 TB1 Com 1 RS 422 485 TB2 Com 2 RS 422 485 TB3 Com 2 RS 232 Communications Ports on the Q4 Daughter Board COM 1 AND COM 2 DESCRIPTION The board pictured in the previous column actually has three serial communications ports labeled as TB1 TB2 and TB3 TB1 is known as Com 1 and is reserved solely for RS 422 485 communications It can be used for external communications to the out si...

Страница 120: ...RS 232 for COM2 TB3 RS 422 for COM2 TB2 Standard Setting RS 232 Com 2 TB3 Communications Signals TB3 Connector Pin Signal 1 2 3 Transmit Data TX Received Data RX Ground COM COM 3 PL6 The following pictorial shows the communications board as well as the jumpers LED s and signal pin outs to allow the end user to communicate to Com 3 PL6 using RS 232 protocol Refer to the table en titled Com 3 PL6 Co...

Страница 121: ...own COM1 No pull down RS 422 RX LK8 In Out Pull up COM1 No pull up RS 422 RX LK9 In Out Pull down COM1 No pull down RS 422 TX LK10 In Out Pull up COM1 No pull up RS 422 TX LK16 A B COM1 RS 422 TB1 COM1 RS 485 TB1 Standard Setting COM 2 TB2 The following pictorial shows the communica tions board as well as the jumpers LED s and signal pinouts to allow the end user to communi cate to Com 2 TB2 using...

Страница 122: ...85 for COM2 TB2 LK 17 A B COM2 RS 422 TB2 COM2 RS 485 TB2 Standard Setting RS 485 WIRING AND JUMPERS The following table describes the RS 485 connector pin outs and their associated communications signals RS 422 TB1 Communications Signal Wiring TB1 Connector Pin Signal 2 TX RX 1 TX RX COM 1 TB1 The following pictorial shows the communica tions board as well as the jumpers LED s and signal pinouts ...

Страница 123: ...r further details TROUBLESHOOTING RS 422 Com 1 TB1 Notice that in the table entitled RS 422 Com 1 TB1 Board Jumpers that there are six jumpers associated with TB1 Note LK11 must be set to position B and LK17 must be set to position A Notice also the two LED indicators that are in the figure D3 LED will flash each time that the Quan tum 4 transmits TX data D2 LED will flash each time that data is r...

Страница 124: ... LX cannot respond On the Communications Setup screen verify that the proper Panel ID Baud rate data bits and protocol matches that of the initiating device Com 2 TB2 Notice that in the figure entitled RS 485 Com 2 TB2 Connector Jumpers LED Location there are seven jumpers associated with TB2 Refer to table entitled RS 485 TB2 Board Jumpers for the function of each of these jumpers Note LK11 must ...

Страница 125: ...ee whether the data is IN or OUT Re ceive or Send and the actual data in Hexadecimal format This information can be used to compare against the data be ing sent and received at the other end of the communications link to verify proper operation Refer to the section on Hyper terminal for some examples of how this screen may be used SERVICE ModBus TCP Log DESCRIPTION This screen allows the technicia...

Страница 126: ...PL11 PL15 LK4 LK3 PL5 COM 2 RS 232 3 2 1 KB D8 PL1 PL2 SW1 ON 1 2 3 4 5 6 7 8 0 1 2 RS 422 1 2 3 4 COM 1 LK6 B A LK5 LK7 LK6 LK4 LK1 LK3 LK17 LK5 A B 1 2 3 4 RS 422 TB1 TB2 LK2 LK1 PL3 PL4 LK2 PL1 PL8 PL7 PL9 PL13 PL12 PWR SUSP FLASH LK12 LK11 PL24 PL18 PL19 PL17 LK8 LK9 LK10 PL16 PL10 PL14 TB3 Verify that LK11 is set to A position B A Com 2 TB3 Com 3 PL6 RS 232 Connector Jumper Location TX RX COM...

Страница 127: ...1 2 3 4 COM 2 RS 422 RS 485 TB1 1 2 3 4 COM 1 RS 422 RS 485 LK17 A B LK11 B A LK16 A B Verify the jumpers in these locations RS 485 Test Configuration 4 Pin Connector 4 1 RX TX RX TX RX TX RX TX 1 4 4 Pin Connector SOFTWARE SETUP FOR THE COMMUNICATIONS LOOP BACK TEST On the Communications screen shown below ensure that the settings are as follows Compressor ID 0 255 does not matter Comm Baud Rate ...

Страница 128: ...hree buttons appear on this screen 1 Test Comm 1 Comm 2 2 Test Comm 1 Comm 3 3 Test Comm 2 Comm 3 Ensure that the proper test harness is installed and the associated jumpers are in their correct positions for the particular test to be performed Pressing the appropriate test key will initiate the test A dialog box will appear with one of the following messages 1 Testing This will appear as the test...

Страница 129: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 129 SECTION 10 APPENDICES ...

Страница 130: ...e housing has a small tab located just below the bottom most terminal block of each end Hold the module as shown in the following pictorial Locking Tabs Disassembling the module Press the tabs using the thumb and finger and with your other hand carefully slide the circuit board out of the housing Ensure that proper anti static guidelines are fol lowed while handling the circuit board The following...

Страница 131: ...owing figure for the pin connections showing how to wire a standard 9 Pin RS 232 connector directly to the Frick Communications Converter Module RS 232 Connections Refer to the following figure for the pin connections show ing how to wire the Converter Module converts from RS 232 to RS 422 485 to the 10 pin Com 3 PL6 connector on the Quantum Com 3 PL6 RS 232 Wiring To Frick Communications Converte...

Страница 132: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 132 APPENDIX B QUANTUM LX ETHERNET COMMUNICATIONS WIRING ...

Страница 133: ...ANTUM LX LOCAL ETHERNET CONFIGURATIONS Typical Small Local Quantum LX Ethernet Configuration Typical Large Local Quantum LX Ethernet Configuration Switch Switch Switch Computer Computer Quantum LX Quantum LX Quantum LX Quantum LX Quantum LX Quantum LX Quantum LX Switch Computer Quantum LX Quantum LX ...

Страница 134: ...ORK CONFIGURATIONS Computer Computer Typical Small Quantum LX Ethernet Network Configuration Quantum LX Quantum LX Ethernet Network Internet Switch Computer Typical Large Quantum LX Ethernet Network Switch Switch Switch Internet Ethernet Network Quantum LX Quantum LX Quantum LX Quantum LX Quantum LX Quantum LX Quantum LX ...

Страница 135: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 135 APPENDIX E QUANTUM LX SERIAL COMMUNICATIONS WIRING ...

Страница 136: ...ommunications port Typical MODBUS ASCII Setup DCS Distributed Control System OR PLC With serial interface adapter card that supports our MODBUS and or our AB SLC 500 DF1 protocol SEE ABOVE Generic DCS PLC Setup RS 232 RS 422 Quantum RS 422 RS 485 RS 232 to 422 485 Converter RS 232 RS 232 to 422 485 Converter Quantum RS 232 RS 232 Quantum Quantum Quantum Quantum Quantum Quantum Quantum ...

Страница 137: ...cal Allen Bradley DF1 Setup PLC 5 SLC 504 SLC 5 04 DH PLC 5 DH Panel View Operator Interface RS 232 to 422 485 Converter RS 422 RS 485 SLC 5 04 DH DCS Distributed Control System with PLC 5 communication driver AB Special Application Examples ASCII RS 232 Serial Card Installed in the DCS RS 232 KF2 Quantum Quantum Quantum Quantum Quantum Quantum Quantum Quantum Quantum Quantum Quantum Quantum ...

Страница 138: ...COMPRESSOR 1 1 2 3 4 To Customer Remote Computer DCS System RX TX RX TX BLK CLR COMPRESSOR 2 1 2 3 4 BLK CLR Q3 OR 3 OR Q4 4 COM 2 TB2 Q5 5 COM 2 P11 COMPRESSOR 3 BLK CLR 1 2 3 4 Q3 OR 3 OR Q4 4 COM 2 TB2 5 5 6 7 8 BLK CLR Q1 OR 2 COM 2 P12 BLK GRN BLK RED Q3 OR 4 COM 2 TB2 BLK GRN BLK RED 1 2 3 4 5 4 9 8 BLK RX RX Cable Belden 9829 24 AWG or Equal To Customer Remote Computer DCS System TX TX 5 6 ...

Страница 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...

Страница 140: ...Form 090 020 CS 2013 04 Supersedes 090 020 CS SEP 11 Subject to change without notice Printed In USA GUI 1M 20 2013 Johnson Controls Inc ALL RIGHTS RESERVED JOHNSON CONTROLS 100 CV Avenue P O Box 997 Waynesboro PA USA 17268 0997 Phone 717 762 2121 FAX 717 762 8624 www johnsoncontrols com ...

Отзывы: