FEU2610 Field Equipment Controller Installation Instructions
9
Analog OUT
OUT
n
Analog Output, Voltage Mode
Sources 0-10 VDC output voltage
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Row
A
)
Analog Output, Current Mode
Sources 4-20 mA output current
External 300 ohm maximum load required
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable
(Row
B
)
OCOM
n
The signal common for all Analog OUT terminals; isolated
from all other terminal commons.
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Same as OUT. See OUT cable
type.)
Binary OUT
(Jumper Set
to External)
OUT
n
Binary Output, 24 VAC Triac
Connects OUT to OCOM when activated
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Row
C
)
OCOM
n
The signal common for Binary OUT terminals; isolated
from all other terminal commons, including Binary Output
(BO) terminal commons.
Binary OUT
(Jumper Set
to Internal)
OUT
n
Sources 24~ Power (Hot)
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Row
C
)
OCOM
n
Binary Output, 24 VAC Triac
Connects OCOM to 24~ Power (Com) when activated.
30 VAC maximum output voltage
0.5 A maximum output current
40 mA minimum load current
Configurable
OUT
OUT
n
Analog Output, Voltage Mode
Sources 0-10 VDC
External 1k ohm minimum load required
10 VDC maximum output voltage
10 mA maximum output current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Row
A
)
Binary Output 24 VAC Triac mode
Connects OUT to OCOM when activated.
30 VAC maximum output voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
Maximum 6 cycles per hour with M9220-BGx-3
40 mA minimum load current
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Row
C
)
OCOM
n
Analog Output: The signal common for
all
analog
Configurable Output (CO) terminals; isolated from all
other terminal commons, excluding BI terminal commons
Binary Output: The signal common for binary-configured
CO terminals; isolated from
all
other terminal commons,
including other CO terminal commons
0.6 mm (22 AWG) stranded, 2-wire
twisted, non-shielded cable for
runs of <30 m (90 ft)
(Same as OUT. See OUT cable
type.)
Sensor
2,
Sensor
Provides SA Bus communication network.
RJ-12 6-position modular connector
24 AWG 3-pair CAT 3 Cable
<30.5 m (100 ft)
Table 1: Field Controller Platform Wiring List (Part 2 of 3)
Terminal
Block
Terminal
Labels
Function and Electrical Ratings/Requirements
Recommended Cable Type
and Length
1