FEU2610 Field Equipment Controller Installation Instructions
13
When set to the INT position, the FEU26 is the
power source for the Binary Output and both sides of the load can
be wired directly to the OUTx and COMx terminals.
Setting the jumper to the EXT position isolates the Binary Outputs, and power must come from one or more
external sources. Do not wire the load directly to the OUTx and COMx terminals. Wire one side of the load to the
source and the other side of the load to the OUTx terminal. Wire the other side of the external power source to the
COMx terminal.
Analog Input Load Resistor Enable/Disable
The Analog Input Resistor Enable/Disable jumpers (J10 through J15) are located on the circuit board in the
controller cover. These jumpers can permanently connect the internal 4-20 mA, 100 ohm load resistor to the input
terminals. There is one jumper for each of the Universal Inputs. See
Software configuration of the Universal Input normally selects the enabling or disabling of the analog input load
resistor. In cases when the analog input load resistor must be left connected even when power is OFF to the
controller, set this jumper to the ENABLE position.
Note:
This jumper must be in the DISABLE position for all Universal Input modes other than 4-20 mA.
Commissioning
Commission the FEU26 with the Controller Configuration Tool (CCT). Refer to
Controller Tool Help (LIT-12011147)
for details.
Troubleshooting
Use
J14
UI5
J15
UI6
Table 5: Status LEDs (Part 1 of 2)
Name
Color
Normal
Descriptions
Power/PWR
Green
On Steady
Off Steady = No Power
On Steady = Power is supplied by Primary Voltage.
Fault/FLT
Red
Off Steady
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download
required, or if controller is in Boot mode.
Table 4: Jumper Labels and UI Inputs (Part 2 of 2)
Jumper Position
Universal Input (UI)
Figure 13: Analog Input Resistor Jumper Positions
Jumper
Pins
Jumper positioned
on top two pins
Jumper positioned
on bottom two pins
ENABLE
DISABLE (Default)
F
IG:
An
a
_
Jm
p
r