background image

Introduction—FC-2000 Introduction     17

Fire Alarm System Limitations

An automatic fire alarm system is typically made up of smoke detectors,
heat detectors, manual pull stations, audible warning devices, and a fire
alarm control with remote notification capability, which can provide early
warning of a developing fire.  Such a system, however, does not assure
protection against property damage or loss of life resulting from a fire.

Any fire alarm system may fail for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the
detectors such as in chimneys, in walls, on roofs, or on the other side
of closed doors.  Smoke detectors also may not sense a fire on another
level or floor of a building.  A second floor detector, for example,
may not sense a first floor or basement fire.  Furthermore, all types of
smoke detectors have sensing limitations.  No type of smoke detector
can sense every kind of fire caused by carelessness and safety hazards
like smoking in bed, violent explosions, escaping gas, improper
storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson.

Rate-of-rise heat detectors may be subject to reduced sensitivity over
time.  For this reason, the rate-of-rise feature of each detector should
be tested at least once per year by a qualified fire protection specialist.

Audible warning devices such as horns may not alert people if these
devices are located on the other side of closed or partly open doors or
are located on another floor of a building.

A fire alarm system will not operate without electrical power.  If
AC power fails, the system will operate from standby batteries only
for a specified time.

Equipment used in the system may not be technically compatible with
the control.  It is essential to use only equipment listed for service
with your Johnson Controls fire controller.

Telephone lines needed to transmit alarm signals from a premise to a
central monitoring station may be out of service or temporarily
disabled.

Содержание FC-2000

Страница 1: ...406 Introduction Section Technical Bulletin Issue Date 0794 1994 Johnson Controls Inc 1 Order No 406 010 Introduction Page 3 Description 3 Optional Modules 4 Components 4 Fire Alarm System Limitations...

Страница 2: ...2 Introduction FC 2000 Introduction...

Страница 3: ...pending A typical FC 2000 control panel is illustrated in Figure 1 your system may have more or fewer modules depending on your requirements All systems have a Central Processor Unit CPU Module locate...

Страница 4: ...Cntrl Silence Inhibit None 30 sec onds 50 sec onds 5 minutes C O N T R O L R E L A Y GRE E N ON Y E LLOW TROUB LE ON OF F MODULE T YPE L A M P S SW IT C H IN I TIA T IN G R E L A Y GRE E N ON Y E LLOW...

Страница 5: ...g appliance circuits a remote signaling municipal tie circuit and Form C alarm and trouble contacts Field programming of the system is accomplished from this module via the use of the programming key...

Страница 6: ...FC 2000 CPU Slide In Labels P 3 P2 P4 P5 P6 R27 JP 5 P 7 JP1 JP2 T B2 CB 1 F1 1 2 3 4 5 6 7 8 1 2 3 4 5 6 JP3 Battery Fuse 20A 3AG 1 2 T B1 T B3 MPS 24A The MPS 24A supplies the regulated power neede...

Страница 7: ...mpatible with 25 VRMS speakers Speaker zone selection is performed by the Voice Control Module VCM 4 For more information on the AA 120 refer to the Fire Management Accessories Manual FAN 445 avps24 1...

Страница 8: ...tyle B initiating device circuits Circuits are power limited and are user programmable for standard fire waterflow alarm supervisory service or command inputs Also provided are end of line resistors d...

Страница 9: ...in a zone The display is also used to display device types and analog detector sensitivity values The system can communicate up to 192 AIM 200 points on LCD 80 or ACM annunciators when so programmed F...

Страница 10: ...rated for 10 amps at 125 VAC and 30 VDC resistive The module is provided with a ribbon for connection to the driving relay module icm 4mod INDICATING CIRCUIT GREEN ON YELLOW TROUBLE ON OFF MODULE TYP...

Страница 11: ...T 4 ENABLE B TCM 2 and TCM 4 Time Control Modules The TCM 2 Time Control Module provides single hazard releasing device service including a programmable delay timer cross zone manual release and abort...

Страница 12: ...vacuation system the Audio Message Generator AMG 1 provides a variety of tones including a slow whoop yelp yeow siren hi lo or steady tone A built in microphone allows for paging through speaker circu...

Страница 13: ...MODE LINE TROUBLE PHONE TROUBLE PAGE P5 FFT 7S Fire Fighters Telephone The FFT 7S Fire Fighter s Telephone provided with the TCC 1 basic equipment package operates like the FFT 7 without paging capab...

Страница 14: ...T contains 16 red alarm and 16 yellow trouble LEDs 16 momentary touch pad switches for controlling each point a system trouble LED an ON LINE POWER LED and a local piezo sounder with a silence acknowl...

Страница 15: ...by an ACM 32A providing a maximum of 64 points Note The AEM 32A cannot be used to expand the ACM 16AT For more information on these annunciator modules refer to the Fire Management Accessories Manual...

Страница 16: ...of 64 points LDM R32 The LDM R32 Relay Expander Module LDM R32 provides the LDM 32 or LDM E32 with 32 dry Form A normally open contacts The relay module serves as a remote to the particular lamp drive...

Страница 17: ...ery kind of fire caused by carelessness and safety hazards like smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits children playing w...

Страница 18: ...by professional fire alarm installers following written procedures supplied with each device System inspection and testing should be scheduled monthly or as required by national and or local fire cod...

Страница 19: ...Introduction FC 2000 Introduction 19 Notes...

Страница 20: ...20 Introduction FC 2000 Introduction Notes Controls Group FAN 406 507 E Michigan Street FC 2000 Technical Manual P O Box 423 Rev Level Milwaukee WI 53201 Printed in USA...

Отзывы: