Introduction—FC-2000 Introduction 9
aim 2 00 m d
AIM-200 Addressable Intelligent Module
The AIM-200 Addressable Intelligent Module serves as an interface
between the FC-2000 and intelligent/addressable devices. To the
CPU, the AIM-200 looks like an IZM-8 Initiating Zone Module. On
its single SLC circuit, the AIM-200 can communicate with up to
99 intelligent detectors (1551J, 2551J, and 5551J) and 99 addressable
modules (M500MJ, M501MJ, M502MJ, M510CJ, and BGX-101L).
The 198 devices are mapped into 8 software zones. The status of
these zones is reported to the CPU. The AIM-200 includes a digital
display for identifying the exact device address within a zone. The
display is also used to display device types and analog detector
sensitivity values.
The system can communicate up to 192 AIM-200 points on LCD-80
or ACM annunciators when so programmed.
For more information refer to AIM-200 Addressable Intelligent
Module section of this manual.
crm-4mod
CONTROL
RELAY
GREEN - ON
YELLOW- TROUBLE
ON/OFF
MODULE
TYPE
LAMPS
SWITCH
CONTROL
RELAY
GREEN - ON
YELLOW- TROUBLE
ON/OFF
MODULE
TYPE
LAMPS
SWITCH
CRM-4 Control Relay Module
Provides four standard dry Form-C alarm contacts rated for 5 amps
@120 VAC or 28 VDC (resistive). Each relay is field programmable
to respond to a single initiating device circuit, a group of circuits, or
all initiating device circuits. Each relay features manual ON/OFF
control switches and can be disabled or enabled as needed. Slide-in
labels are provided with each module.