Figure 3: FAC2611 Physical Features
Table 1: FAC2611 Physical Features
Physical Feature: Description and References
Callout
Binary Output (BO) Source Power Selection Jumpers: Position jumpers to select internal or external 24 VAC
supply power for Binary Outputs. (see
Binary Output (BO) Source Power Selection Jumpers
1
Device Address DIP Switch Block (see
)
2
Mounting Clips (see
)
3
Configurable Outputs (CO) Terminal Block: Can be defined as Voltage Analog Output (0-10 VDC) or Binary Output
(24 VAC Triac). (see
4
Analog Output (AO) Terminal Block: Can be defined as Voltage Analog Output (0-10 VDC) Current Analog Output
(4-20 mA). (see
5
24 VAC, Class 2 Supply Power Terminal Block (see
6
Cover Lift Tab (see
7
Field Controller (FC) Bus Terminal Block (see
8
Sensor Actuator (SA) Bus Terminal Block (see
)
9
Sensor Port: (SA Bus) RJ-12 6-Pin Modular Jack (see
)
10
Binary Input (BI) Terminal Block: Dry Contact Maintained or Pulse Counter/Accumulator Mode (see
11
Universal Inputs (UI) Terminal Block: Can be defined as Voltage Analog Input (0-10 VDC), Current Analog Input
(4-20 mA), Resistive Analog Inputs (0-600k ohm), or Dry Contact Binary Input. (see
12
End-of-Line (EOL) Switch, located under the cover. (see
Setting the End-of-Line (EOL) Switch
)
13
LED Status Indicators (see
14
FC Bus Port (RJ-12 6-pin Modular Jack) (see
15
Binary Outputs (BO) Terminal Block: 24 VAC Triac (see
)
16
4