Terminal Wiring Guidelines,
Functions, Ratings, and
Requirements

Input and Output Wiring Guidelines

Table 3

provides information and guidelines about the

functions, ratings, and requirements for the controller
input and output terminals; and references guidelines for
determining proper wire sizes and cable lengths.

In addition to the wiring guidelines in

Table 3

, observe

these guidelines when wiring controller inputs and
outputs:

Run all low-voltage wiring and cables separate from
high-voltage wiring.

All input and output cables, regardless of wire size or
number of wires, should consist of stranded, insulated,
and twisted copper wires.

Shielded cable is not required for input or output
cables.

Shielded cable is recommended for input and output
cables that are exposed to high electromagnetic or
radio frequency noise.

Inputs/outputs with cables less than 30 m (100 ft)
typically do not require an offset in the software setup.
Cable runs over 30 m (100 ft) may require an offset
in the input/output software setup.

Table 3: FAC2611 Terminal Blocks, Functions, Ratings, Requirements, and Cables

Determine Wire Size and
Maximum Cable Length

Function, Ratings, Requirements

Terminal
Label

Terminal Block
Label

Same as (Universal)

INn

Note:

Use 3-wire cable for
devices that source
power from the +15V
terminal.

15 VDC Power Source

for active (3-wire) input devices

connected to the Universal IN

n

terminals.

Provides 100 mA total current

+15 V

UNIVERSAL

(Inputs)

See Guideline

A

in

Table 4

.

Analog Input - Voltage Mode (0–10 VDC)

10 VDC maximum input voltage

Internal 75k ohm Pull-down

INn

See Guideline

B

in

Table 4

.

Analog Input - Current Mode (4–20 mA)

Internal 100 ohm load impedance

Note:

Current loop jumpers are fail-safe to maintain a
closed 4 to 20 mA current loop, even when the
power to the controller is interrupted or off. See

UI

Current Loop Jumpers

.

See Guideline

A

in

Table 4

.

Analog Input - Resistive Mode (0–600k ohm)

Internal 12 V. 15k ohm pull up

Qualified Sensors: 0-2k ohm potentiometer, RTD (1k Nickel
[Johnson Controls

®

sensor], 1k Platinum, and A99B Silicon

Temperature Sensor) Negative Temperature Coefficient
(NTC) Sensor

See Guideline

A

in

Table 4

.

Binary Input - Dry Contact Maintained Mode

1 second minimum pulse width

Internal 12 V. 15k ohm pull up

Same as (Universal)

INn

Universal Input Common

for all Universal Input terminals

Note:

All Universal ICOM

n

terminals share a common,

which is isolated from all other commons.

ICOMn

13

FAC2611-0U Advanced Application Field Equipment Controller Installation Instructions

Содержание FAC2611-0U

Страница 1: ...e Metasys System UL 864 10th Edition UUKL ORD C100 13 UUKLC Smoke Control System Technical Bulletin LIT 12012487 Switchable Communications Protocols The Family Controllers and network sensors communicate using the standard BACnet protocol based on the ANSI ASHRAE 135 2004 The BACnet protocol is a standard for ANSI ASHRAE and the International Standards Organization ISO for building controls Most F...

Страница 2: ...ctions sheet Materials and Special Tools Needed three fasteners appropriate for the mounting surface M4 screws or 8 screws one 20 cm 8 in or longer piece of 35 mm DIN rail and appropriate hardware for DIN rail mount only small straight blade screwdriver for securing wires in the terminal blocks Mounting Observe these guidelines when mounting a field controller Ensure the mounting surface can suppo...

Страница 3: ...ft the controller off the DIN rail Wall Mount Applications To mount a field controller directly on a wall or other flat vertical surface 1 Pull the two bottom mounting clips outward and ensure they are locked in the extended position as shown in Figure 2 2 Mark the mounting hole locations on the wall using the dimensions in Figure 2 and one of the mount positions shown in Figure 1 Or hold the cont...

Страница 4: ...ck see Supply Power Terminal Block 6 Cover Lift Tab see Removing the Controller Cover 7 Field Controller FC Bus Terminal Block see FC Bus Terminal Block 8 Sensor Actuator SA Bus Terminal Block see SA Bus Terminal Block 9 Sensor Port SA Bus RJ 12 6 Pin Modular Jack see Sensor Port 10 Binary Input BI Terminal Block Dry Contact Maintained or Pulse Counter Accumulator Mode see Table 3 11 Universal Inp...

Страница 5: ...led information on wiring an N2 network refer to the N2 Communications Bus Technical Bulletin LIT 636018 FAC Terminal Blocks and Bus Ports See Figure 3 for terminal block and bus port locations on the FAC2611 controller Observe the following guidelines when wiring a controller Input and Output Terminal Blocks On most field controller models all of the fixed input terminal blocks are mounted on the...

Страница 6: ...s The Sensor port is connected internally to the SA bus terminal block See Comm Bus and Power Supply Terminal Block Rating and Requirements Table for more information The Sensor Port pin assignment is shown in Figure 6 Supply Power Terminal Block The 24 VAC supply power terminal block is a gray removable 3 terminal plug that fits into a board mounted jack on the top right of the controller Wire th...

Страница 7: ...L 864 UUKL UUKLC Listed Metasys system devices Termination Details A set of Johnson Controls termination diagrams provides details for wiring inputs and outputs to the controllers See the figures in this section for the applicable termination diagrams Table 2 Termination Details Termination Diagrams Type of Input Output Type of Field Device UI Temperature Sensor UI Voltage Input External Source UI...

Страница 8: ...Device UI Voltage Input Self Powered UI Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop 8 FAC2611 0U Advanced Application Field Equipment Controller Installation Instructions ...

Страница 9: ... of Field Device UI Feedback from EPP 1000 UI or BI Dry Contact Binary Input AO 0 10 VDC Output to Actuator External Source AO 0 10 VDC Output to Actuator Internal Source AO Current Output 9 FAC2611 0U Advanced Application Field Equipment Controller Installation Instructions ...

Страница 10: ... Input Output Type of Field Device AO 24 VAC Triac Output Switch Low External Source AO Analog Output Current AO 4 20 mA Output to Actuator AO 4 20 mA Output to Actuator 10 FAC2611 0U Advanced Application Field Equipment Controller Installation Instructions ...

Страница 11: ...Where Applicable BO 24 VAC Binary Output Switch Low Externally Sourced Triac Jumpers Where Applicable BO 24 VAC Binary Output Switch High Externally Sourced Triac Jumpers Where Applicable BO Incremental Control to Actuator Switch High Externally Sourced Triac Jumpers Where Applicable 11 FAC2611 0U Advanced Application Field Equipment Controller Installation Instructions ...

Страница 12: ...TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection SA Bus Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Network Stat with Terminals Fixed Address 199 12 FAC2611 0U Advanced Application Field Equipment Controller Installation Instructions ...

Страница 13: ...gs Requirements Terminal Label Terminal Block Label Same as Universal INn Note Use 3 wire cable for devices that source power from the 15V terminal 15 VDC Power Source for active 3 wire input devices connected to the Universal INn terminals Provides 100 mA total current 15 V UNIVERSAL Inputs See Guideline A in Table 4 Analog Input Voltage Mode 0 10 VDC 10 VDC maximum input voltage Internal 75k ohm...

Страница 14: ... Analog Output Voltage Mode 0 10 VDC 10 VDC maximum output voltage 10 mA maximum output current Required an external load of 1 000 ohm or more Note The Analog Output AO operates in the Voltage Mode when connected to devices with impedances greater than 1 000 ohm Devices that drop below 1 000 ohm may not operate as intended for Voltage Mode applications OUTn ANALOG Outputs Analog Output Current Mod...

Страница 15: ...ed to External EXT power Binary Output Common for OUTn terminal Note Each Binary Output Common terminal OCOMn is isolated from all other commons including other Binary Output Common terminals OCOMn See Guideline C in Table 4 Binary Output 24 VAC Triac Internal Power Source Sources internal 24VAC power 24 HOT OUTn BINARY Output Power Selection Jumper positioned to Internal INT power Binary Output 2...

Страница 16: ...y Connects OUTn to OCOMn when activated External Power Source Requirements 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle Maximum 6 cycles hour with M9220BGx 3 40 mA minimum load current Same as Configurable OUTn Analog Output Signal Common All Configurable Outputs COs defined as Analog Outputs AOs share a common which is isolated from all other commons except th...

Страница 17: ...u may have to define an offset in the setup software for the input or output point 229 m 750 ft twisted wire 1 0 mm 18 AWG stranded copper B 137 m 450 ft twisted wire 0 8 mm 20 AWG stranded copper 91 m 300 ft twisted wire 0 6 mm 22 AWG stranded copper 61 m 200 ft twisted wire 0 5 mm 24 AWG stranded copper N A See Figure 8 to determine cable length Use twisted wire cable See Figure 8 to select wire...

Страница 18: ... Functions Ratings Requirements and Cables Recommended Cable Type Function Electrical Ratings Requirements Terminal Labels Terminal Block Port Label 0 6 mm 22 AWG stranded 3 wire twisted shielded cable recommended FC Bus Communications FC BUS 1 Signal Reference Common for Bus communications COM Isolated terminal optional shield drain connection SHLD Bluetooth Commissioning Converter retractable ca...

Страница 19: ...eration Set a valid and unique device address on the controller before applying power to the controller on the bus To set the device addresses on Metasys field controllers 1 Set all of the switches on the address DIP switch block 128 through 1 to Off 2 Set one or more of the seven address switches 64 though 1 to ON so that the sum of the switch numbers set to ON equals the intended device address ...

Страница 20: ...ontroller application file The download process asks to confirm switching the communication protocol to N2 7 Click OK 8 After the download is finished disconnect the 24 VAC supply to the controller 9 Set the address switch segment labeled 128 to ON 10 Reattach the FC Bus connector to the controller 11 Reconnect the 24 VAC supply to the controller Removing the Controller Cover Important Electrostat...

Страница 21: ...tion de l controller avant tout réglage du Binary Output Source Power Selection Jumpers Le non respect de cette précaution risque de provoquer une décharge électrique Binary Output BO Source Power Selection Jumpers Risk of Electric Shock Disconnect supply power to the field controller before attempting to adjust the Binary Output Source Power Selection Jumpers Failure to disconnect the supply powe...

Страница 22: ... loop circuit even when power to the controller is interrupted or off Important Current Loop jumpers must be in the Disabled default position for all UIs that are not set up to operate as 4 20 mA analog inputs Table 7 identifies the current loop switches associated with each UI on the FAC2611 controller Table 7 FAC2611 UI Inputs and Jumper Labels Switch Label on Current Loop DIP Switch Block Board...

Страница 23: ...unication Off Steady No Data Transmission auto baud in progress On Steady Communication lost waiting to join communication ring Blink 2 Hz Green FC BUS On Steady EOL switch in ON position Off Steady EOL switch in Off position Off Except on terminating devices Amber EOL Repair Information The MS FAC2611 0U model is UL 864 10th Edition UUKL ORD C100 13 UUKLC listed for smoke control If a field contr...

Страница 24: ... hours when supply power to the controller is disconnected Real Time Clock Backup Power Supply 6 Universal Inputs Defined as 0 10 VDC 4 20 mA 0 600k ohm or Binary Dry Contact 2 Binary Inputs Defined as Dry Contact Maintained or Pulse Counter Accumulator Mode 3 Binary Outputs Defined as 24 VAC Triac selectable internal or external source power 4 Configurable Outputs Defined as 0 10 VDC or 24 VAC Tr...

Страница 25: ...evision 7 Listed BACnet Advanced Application Specific Controller B ASC The performance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products APAC Single Point of Contact NA SA Si...